Siemens UL 489, UL1066 specifications Basic Data Type 3 Registers and Default Data Points

Page 59

Communication-capable Circuit Breakers

WL Circuit Breaker

Basic Data Type 3 Registers and Default Data Points

Register

Byte

Name

Default Data Point – WL

1

0, 1

Status Register

WL status bits

2

2, 3

Data Block 1

Phase 1 current

3

4, 5

Data Block 2

Phase 2 current

4

6, 7

Data Block 3

Phase 3 current

5

8, 9

Data Block 4

Max current in phase under highest load

6

10, 11

Data Block 5

Current in neutral conductor

7

12, 13

Data Block 6

Phase to phase voltage L1 to L2

8

14, 15

Data Block 7

Phase to phase voltage L2 to L3

9

16, 17

Data Block 8

Phase to phase voltage L3 to L1

10

18, 19

Data Block 9

Phase to neutral voltage L1

11

20, 21

Data Block 10

Phase to neutral voltage L2

12

22, 23

Data Block 11

Phase to neutral voltage L3

13

24, 25

Data Block 12

Average of power factors of 3 phases

14

26, 27

Data Block 13

Total active energy of 3 phases*

15

28, 29

Data Block 14

Total apparent power of 3 phases

16

30

Block 1 property byte

PB of phase 1 current

31

Block 2 property byte

PB of phase 2 current

 

17

32

Block 3 property byte

PB of phase 3 current

33

Block 4 property byte

PB of max current in phase under highest load

 

18

34

Block 5 property byte

PB of current in neutral conductor

35

Block 6 property byte

PB of phase to phase voltage L1 to L2

 

19

36

Block 7 property byte

PB of phase to phase voltage L2 to L3

37

Block 8 property byte

PB of phase to phase voltage L3 to L1

 

20

38

Block 9 property byte

PB of phase to neutral voltage L1

39

Block 10 property byte

PB of phase to neutral voltage L2

 

21

40

Block 11 property byte

PB of phase to neutral voltage L3

41

Block 12 property byte

PB of average of power factors of 3 phases

 

22

42

Block 13 property byte

PB of total active energy of 3 phases*

43

Block 14 property byte

PB of total apparent power of 3 phases

 

*Only 2 bytes of the 4 byte data point will be communicated (range: 0 - 65535MWh)

Table 3-7

For additional information on the controlling documents for the definitions of all MODBUS Public Function Codes referenced may be downloaded in PDF format from the MODBUS website http://www.modbus.org.

3/12

WL MODBUS Communication and Electronic Accessories • January 2005

Image 59
Contents Global network of innovation Powerful ideasCommunication-capable Circuit Breakers Communication-capable Circuit Breaker Registered Trademarks Safety GuidelinesQualified Personnel Correct UsageIntroduction Overview Introduction Content of the ManualGeneral Easy Planning System SolutionsWL Circuit Breakers-Modular Intelligent Cost SavingModbus Communication Bus SystemsCommunication Structure of the WL Circuit Breakers Ethernet WL Circuit Breaker Brief Description of the WL Circuit Breaker Introduction and OverviewCommunications Capability of the Electronic Trip Units ETUs CubicleBUSETU725 ETU727 ETU745 Functional overview of the trip unit systemBasic Functions ETU725 ETU727 ETU745 Setting range of the IgBasic Functions ETU748 ETU755 ETU776 Communication Data points with the same source 755 or Data Availability on the CubicleBUSData point group ETU745 MeteringModbus Module COM16 Pin ConfigurationModbus COM16 Module and the BSS Modbus Installation Guideline Modbus Write Protection DPWriteEnableCubicleBUS + Data Exchange via the COM16 ModuleMeaning Position and text on the cable CubicleBUS Position Rear Microswitch S46 Middle S47 Front S48Meaning Cubicle BUS LED MeaningBreaker Status Sensor BSS General Metering Function PlusWaveform buffer Metering Function PlusHarmonic analysis Maximum distance from voltage transformer Parameters for the settings of the metering functionVoltage Transformers VT AccuracyMetering range 81THDC Extended Protective Function Important functions/parameters for communicationsLoad Management Event and Trip Log Normal Positive Power Flow DirectionSetpoints Minimum for Communicated CurrentsExternal CubicleBUS Modules Rotary SwitchesInstallation CubicleBUS Installation Guidelines Power SupplyMaximum CubicleBUS Configuration All other LEDs Meaning LED DisplayMeaning CubicleBUS LED MeaningDevice Testing the Digital Input and Output ModulesFunctional description for changing parameter sets Technical data for the digital input moduleDigital Input Module Functional descriptionDelay time Digital Output Module with Rotary SwitchSelector switch position to the left Selector switch position to the rightConfigurable Digital Output Module Trigger event Waveform buffer B Technical data for the digital configurable output moduleAnalog Output Module Power value ranges W/VATest function Switch position cosTechnical data for the analog output module Example as illustrated in Graphic ZSI ModuleOperating principle It trips after tZSI = 50 ms. Time saved = 250 ms Technical data for the ZSI moduleCommunication-capable Circuit Breakers General information Output current Inrush current Type Order No Communication-capable Circuit Breakers Modbus Profile for WL Circuit Breaker Supervisory Systems Function 02 Read Discrete Inputs COM16 Supported Function CodesFunction 01 Read Coils Reply Message from slave Function 03 Read Holding RegistersRequest Message to slave Function 07 Read Exception Status Function 04 Read Input RegistersFunction 05 Write Single Coil Function 12 Get Communication Event Log Function 08 DiagnosticsFunction 11 Get Communication Event Counter COM16 slave Send Event What the Event Bytes ContainFunction 15 Write Multiple Coils Function 16 Write Multiple Registers Exception Responses Code Name Meaning Exception CodesBasic Data Type 2 Registers and Default Data Points Default Register ListsBasic Data Type 1 Registers and Default Data Points Basic Data Type 3 Registers and Default Data Points Data bytes Complete List of DatasetsMin Max Bits Sample DatasetByte Register Description Bit Mapping for Breaker Status RegisterWL Configurator Brief Description Communication-capable Circuit Breakers Breaker Data Adapter BDA Breaker Data Adapter Plus BDA Plus Benefits of the BDA Brief Description and System RequirementsDescription BDA as a Hand-Held Device or BDA Plus BDA in Offline Mode or BDA PlusIntranet and Internet BDA Plus as an Ethernet InterfaceGetting started with the BDA Plus What is Java?Circuit breaker requirements Permanent Connection to WL Circuit BreakersTemporary Meaning of the LEDs on the BDA Operation4This table provides technical data for the BDA and BDA Plus Technical data for the BDA and BDA PlusUsually have to be changed. They are shown as a reference Connection to the BDA via the Serial Communication SystemBreaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Definition of Key Terms Connection to the BDA Plus via the Ethernet InterfaceBDA IP Address IP AddressesSubnet Mask ExampleDisplaying Data Operating Instructions and TroubleshootingOffline/Online Mode Languages and HelpPrinting Password ProtectionSentron Operation ExampleTroubleshooting List Fault Description Solution Siemens Energy & Automation, Inc. All Rights Reserved Siemens Energy & Automation, Inc

UL 489, UL1066 specifications

Siemens UL1066 and UL489 are essential components in the landscape of electrical equipment, specifically in circuit protection and control. These standards ensure reliability, safety, and efficiency in various applications, including industrial, commercial, and residential settings.

The Siemens UL1066 is primarily focused on disconnect switches. These devices are designed to isolate electrical circuits, ensuring the safety of both personnel and equipment during maintenance or in case of faults. One of the key features of UL1066 disconnect switches is their high breaking capacity, enabling them to handle significant fault currents without failure. This characteristic is crucial in protecting downstream equipment from damage caused by short circuits. The UL1066 switches are also known for their robust construction, often featuring a metal enclosure that enhances durability and environmental resistance. Additionally, these switches can be operated manually or remotely, offering flexibility in operation and control.

On the other hand, Siemens UL489 circuit breakers provide comprehensive protection against overcurrents and short circuits. These devices not only interrupt fault currents but also protect connected devices from damage due to overload situations. Key features of UL489 circuit breakers include adjustable trip settings, which allow users to customize the response to overcurrent conditions based on specific application requirements. This adaptability makes them suitable for a wide range of environments, from large industrial plants to smaller commercial buildings.

Both UL1066 and UL489 products are constructed with advanced technologies, such as thermal-magnetic or electronic trip mechanisms in UL489 devices, ensuring precise and timely interruption of fault currents. These technologies promote energy efficiency and stability within electrical systems. In addition, many of these devices are equipped with indication features, providing clear visual status cues for quick assessment in emergency situations.

In terms of characteristics, both UL1066 and UL489 devices adhere to rigorous testing and certification processes to meet UL standards. This compliance assures users of their performance and reliability. Furthermore, the devices are designed to accommodate a wide range of operating temperatures and environmental conditions, making them versatile choices for various applications.

In summary, Siemens UL1066 and UL489 devices are paramount in ensuring safety and efficiency in electrical circuits. Their advanced features and robust construction make them indispensable in protecting both personnel and equipment in an array of industrial and commercial applications.