The fail-safe dip switches are labeled S2 on the 8RO, and switch S3 on the 8ROe and 8IO. Each of the eight rockers on the fail-safe dip switch corresponds to an output on the board. Set the rocker UP to close the relay and turn the output ON during network failure. Set the switch DOWN to open the relay and turn the output OFF during network failure.

9.2.4Wiring Outputs to Points

Old 8ROs

The old design of 8RO (P/N 810-3002) used points with two terminals on them. To connect output devices to these points, wire the point terminals in series with the load, so that the path is closed when the 8RO relay is CLOSED and open when the 8RO relay is OPEN.

New 8ROs and 8RO-FCs

All other E2-compatible output boards, including the new design of 8RO (P/N 810-3005), the 8RO-FC, and have Form C contacts. Figure 9-8shows how to wire the three-terminal Form C contact.

One wire of the two-wire 8RO-FC connection should always be connected to the middle terminal. The second wire must either be connected to the N.C. terminal (if you want the path to be closed when the relay is de-energized) or the N.O. terminal (if you want the path to be open dur- ing power failure.

9.2.5The Output LED

Each output point on an output board has an indicator LED that shows the status of the output. This LED is lit to show the output is ON, and unlit to show the output is OFF.

The definition of ON and OFF in this case is deter- mined by the position of the fail-safe dip switch (see Table 9-3). Therefore, if the output’s switch is UP, an illuminated LED means the path is CLOSED, but if the switch is DOWN, an illuminated LED means the path is OPEN.

9.2.6Output Setup in E2

In order for the E2 to properly control devices that are hooked to an I/O board, you must first tell the E2 what type of output the devices require. This is achieved from the Output Definitions/Status screen.

9.2.6.1Configuring a Point from the Out- put Definitions/Status Screen

To configure a point, go to the Output Definitions/Sta- tus screen:

1.Press to open the Main Menu

2.Press (System Configuration)

3.Press (Output Definitions) The Output Status screen opens:

Figure 9-9- Output Status Screen

To configure a point, use the up and down arrow keys to move the cursor to the point you wish to set up, and press (SETUP).

If you press to set up a 4AO output point, the E2 will automatically transfer you to the Analog Output screen Figure 9-6. For all other output board types, press- ing will bring up a pop-up menu such as the one shown in Figure 9-10. This menu will prompt you to spec- ify the output as either Digital, Pulse, or One Shot. Press

if the output is Digital, press if the output is Pulse,

press if the output is One Shot, or press to cancel setup.

Figure 9-10- Output Data Type Pop-Up Menu

Depending upon what type of output you selected, the Digital Output, (see Section 9.2.6.3, Setting Up Digital Outputs) Pulse Digital Output, or One Shot Digital Output screen will appear.

9.2.6.2Using the Output Definitions/Sta-

tus Screen

The Output Definitions/Status screen serves a dual

The 8RO, 8ROe, 8IO, and MultiFlex Outputs

Input and Output Setup 9-11

Image 105
Contents Rev 13 14-SEP-2011 BX HVAC, and CX Convenience Store ControllersPage FCC Compliance Notice Page Table of Contents E2 Hardware Setup Serial Configuration E2 Ethernet Peer Communications Quick Start Software Overview Logging Groups Multiflex CUB Board Holiday Schedules OPERATOR’S Guide to Using the E2 LOW Battery Notification Page E2 Refrigeration Controller IntroductionMrlds E2 Building Con- trollerE2 Convenience Store Controller 1 E2 I/O Network Networking OverviewAble for the RS485 Network NetworkInterconnection With Other E2s Documentation Over ViewOn-Line Help System Overview Software Licensing E2 Hardware Hardware Overview1 E2 Main Processor Board 3 E2 Keypad LEDsPIB LEDs Status Gateway Board I/O Network Boards and PeripheralsMain Board Status CPU LEDs Keyboard StatusMultiFlex 16 Input Board MultiFlex BoardsGateway Model Model Name DescriptionModel Description Name MultiFlex Combination Input/ Output BoardsE2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 MultiFlex RTU BX and CX Only MultiFlex CUBMultiFlex Rooftop Control Board RCB BX and CX Only MultiFlex PAK BoardHand-held Terminal P/N MultiFlex ESR Board10- Hand-held Terminal 8RO and 8ROSMT Relay Boards13- 4AO Analog Output Board P/N 6 4AO Analog Output Board8ROe Dis 16AIe Dis20- Case Controller CC-100P shown ESR8 DisFacility Status Display FSD 6 TD3 Temperature DisplayPage Mounting the E2 MountingStandard Mount Recessed MountStandard Mount Inside Rear of Enclosure Retrofit MountingMounting I/O Boards Blank FaceSingle/Double Enclosures Echelon Devices Boards Without Enclosures Snap Track1 16AIe and 8ROe 3 ESR8 Dis MultiFlex ESR5 TD3 Internal Modem Two-Channel and Four- Channel RepeatersMounting Repeaters Overview Mounting the Two-Channel RepeaterInside Temperature Sensor Sensors and Transduc ErsPressure Transducers Outside Temperature Sen Sor Insertion Temperature ProbeSupply and Return Air Sen Sors Humidity Sensors and Humidistats Product Temperature ProbesMounting Bullet and Pipe Mount Sensors Indoor RH SensorOutdoor RH Sensors Duct-mounted Insertion RH ProbeOutdoor RH sensor P/N Light Level Sensor Dewpoint ProbeLiquid Level Sensors Refrigerant Leak DetectorsPage Setting up the E2 E2 Hardware SetupEnclosure Main Processor BoardPowering the E2 Echelon Card Plug-In P/N 537-4860with mounting screw P/N Add-On E2 PeripheralsModem P/N Description Plug-In Digital I/O Network Card P/N5 E2 RS485 Port Card P/N 537-4890 Battery Testing and ReplacementPlug-In Four-Channel Inter- nal Repeater LEDsBattery Enable Switch Low Battery NotificationBattery Test Battery Replacement Qual- ified Technicians OnlyEchelon Earth Page Serial Device and Soft Ware Setup Serial Configura- tionOverview COM PortsE2 COM# Associations Connector I/O Network RS485 Network and Hardware Setup1 I/O Board Names and Termi Nology BoardMultiFlex-Plus + Board Wiring TypesI/O Network Structure Daisy Chains Network Noise Minimiza TionNetwork ID Numbers Board Numbers Setting the Baud RatePowering the I/O Boards Setting the Terminating and Biasing JumpersBoard Installation Wiring TypesIMC/Prodigy Rooftop Unit Controllers Control Techniques Drive Copeland Discus with Core- Sense Diagnostics ISD3 XR35CX, XR75CX, XEV22 Case Controllers 3.1 XR75CX-Case DisplayEnergy Meter IPro DACOverview Supported System TypesDiagnostic Alarm Descriptions E2 Advisory Advisory and AlarmsCopeland Discus with Core- Sense Protection Light Commercial Thermo StatComfort Alert Descriptions Cause E2 Advisory Comfort Alert CodesHigh/Low Occ/Unocc Space Temperature Alarms Supply Sensor Fail AlarmConditions for Return to Normal RTN on Diag- nostic Codes Diagnostic Alarm Descriptions Diagnostic AlarmsRefrigerant Leak Detection System Rlds Copeland Scroll K5 Refrig- eration Compressor11.1 XM670 XM Series of Case Control Lers11.2 XM679 11.3 XM678RS485 Network and Hardware Setup 6 14 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 NET 16 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 120/208/240 VAC 16AI Installation Guide MultiFlex ESR Installation Guide XEV22D Driver to E2 Installation Guide XR35CX, XR75CX to E2 Installation Guide Page Equipment Specifications Type Ethernet IP Configura TionsE2 Ethernet Peer Communications Hardware Specifica TionsSoftware Specifica Tions Ethernet Network LayoutsClosed Network Layout Open Network Layout Software Setup5Peer Network Tab Set Group Name TroubleshootingWiring Type Echelon Network and Hardware SetupCable Type Retail Solutions Part Number Loop ResistanceMaximum Number of Eche- lon Devices Device TerminationInstalling Echelon Devices Wire RestrictionsPowering Echelon Devices Maximum Total Segment LengthConfiguring Echelon Devices LEDsOpen Echelon Device Connectivity Connected I/O Screen E2 firmware versions 2.81 and above TroubleshootingE2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 One pin when unterminating an E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 MultiFlex Boards All Analog Temperature Sensors and Air Flow Sensors16AI Boards 8IO and Artc BoardsPower Connection Down Sensor Input Type Wiring Dip SwitchWall-mounted Down 207-1000 Refrigerant MA output to input board Sensor Input Type20mA, Up for PulseAssociation ApplicationPulse on Sensor Type DescriptionSetting Up Digital Inputs Set 8RO, 8ROe, 8IO, and MultiFlex OutputsNew 8ROs and 8RO-FCs Old 8ROsSetting Up Digital Outputs Setting Up Analog Outputs Connection Temperature and Digital SensorsHand-Held Terminal Jack Auxiliary Analog Input335-3260 Generic Stepper and Emerson Flow Controls ESV Valve 335-3263 Pulse ValvePin Page Performing a Clean Out Cleaning Out the Con- trollerQuick Start Logging OnSetting Number of Network Devices Boards on the I/O NetworkUnit Controllers Echelon Customizing the Home Screen Setting Number of ApplicationsHeader Common Screen Ele- mentsFunction Keys Help LineScreen Types Status ScreensMain Menu Actions Menu Key Function forActions Menu Item Description Setup Screens System Configuration MenuMenu Option Description 13- System Information Menu System Information MenuSetting the Time and Date Time/Date SetupSet Up Modem 17- TCP/IP Addressing Set Up TCP/IPSet Up Network Baud Rates 10.11.1 COM1 Serial RS232 Baud Rate10.11.2 I/O Network Baud Rate Level Set Up User AccessChanging Required User Access Levels Creating a New User AccountDeleting a User Specify Number of Boards Set Up I/O NetworkSet Up Echelon Net Work Checking Online StatusSpecifying Number Devices Commissioning a Device Service Button MethodHow Echelon Commissioning Works Modbus CommissioningTD3’s Service Button CC-100’s Service ButtonESR8’s Service Button Commissioning the EC-2Manual ID Entry Method License Management33- TCP/IP Screen Locating the Mac Address Web Services37- Alarm Setup Menu Set Up AlarmingSetting up an E2 to be an Alarm Annunciator Specifying Alarm Reporting TypesIntroduction Alarm Report Ing Alarm Dial-OutPriority Settings Set Up Global DataExample Setting Up an Outdoor Temperature Sen- sor Set Up Applications10.18.1 Add/Delete an Application Using and Configuring a Setup ScreenAdd an Application Delete an ApplicationNavigating the Setup Screen Edit MenuEntering Setpoints Function Keys For Setup Index TabsHelp Line Using the Help Key to get Property Help Page Suction Groups Software OverviewIntroduction Standard Suction Group ApplicationHardware Overview Learning ModeCircuit Load Analysis Control/Cycles ParameterInput Sensor Type Wiring Instructions Temperature Differential Strat EgyCondenser Control Air Cooled CondensersFast Recovery Condenser Split ModeEvaporative Condensers Fan ControlRefrigeration Control Standard CircuitsDefrost Control Clean and Door Switches TD3 Temperature Display WiringControl Link CD Case Display Typical Case in a Standard Circuit Case Control Circuits OverviewCase Circuit Control Soft- ware Overview EEVs Liquid Pulse and Liquid Stepper Valve ControlEEPRs Suction Stepper Thermostatic Expansion Valves TXVsOff Cycle Timed Anti-Sweat Control Temperature TerminationDemand Defrost Wait StateDual Temp Control Clean/Wash ModeLight Control Dewpoint Input SourcesFail-Safe Mode Recoverable Sensor FailuresWalk-In Freezer Control Logging Groups Setting Up An Individual Case ControllerData Compression Possible Data ErrorsBase Log Group ClippingLogging Setup Menu Setting Up LoggingLog Reports Logging Group Status ScreenLogging Group Report Application Log ReportSystem Log Report Air Handling Units Temperature ControlAlternate Setpoints Single-Speed FansEconomizer Control Economization EnableTwo-Speed Fans Variable-Speed FansAnalog Economizer Control Digital Economizer ControlDehumidification Control CurtailmentSeparate Setpoints Inputs Sensor Type Wiring InstructionsAHU Zone Control Intelligent Pre-Starts and Pre-StopsZone Control SectionTion Applications That May Be Connected To Zones How Zones WorkMultiFlex RTU Board MultiFlex RCB BoardEconomization Enable Zone TemperatureZone Humidity Input Effect of Enabling Econ- omizationEffect of Enabling Dehu- midification MultiFlex RTUs and RCBsLosing Contact With Zone Applications Stand-Alone MultiFlex RTUsMultiFlex RTU/ARTC and AHU Zone Association MultiFlex CUB Board MultiFlex PAK BoardLighting Schedules Control Method Select Functions of the Lighting Schedule ApplicationStandard Control Light Level Interface CellAlternate Control Schedule Interface CellMulti-Logic Combiner Min ON/OFF Cell Basic Schedule CellProof Cell Offset Solar ControlOutput Light Dimming Demand ControlIntroduction to Demand Limit Control Demand MonitoringShedding Levels Load SheddingPriority Levels DefinitionRotational Shed Last ShedOther Notes About Priority Levels Mode 1 KW Input Is Greater Than Setpoint Mode 3 Integral Error Approaching ZeroHow Demand Control Uses Load Shedding Sensor Control Power Monitoring InputAnalog Sensor Control Cut In/Cut Out Setpoint Con TrolLoop/Sequence Con Trol Logical CombinationControl Cells Loop/Sequence Control Cell Descriptions DiagramOutput Cells Select CellOutput Cell Descriptions How Schedules Work Time Scheduling and HolidaysEvents Absolute and Relative EventsHoliday Schedules Power MonitoringOverlapping RangesHourly LoggingDaily MonthlyHeat/Cool Control Anti-Sweat SetupHow Anti-Sweat Works Unoccupied HysteresisStops Setpoint ResetLead/Lag Analog and Digital CombinersConfiguration Temperature Differential TD StrategyTD Control TD Control Fail-SafesPulse Accumulation AlarmsInputs OutputsIrrigation Control Accumulator Reset TypesHigh Trip Zones and CyclesCycle Scheduling Zone InhibitZone Bypass Inputs Flow Sensor-Related Tests Service ModesHeat Cut In/Cut Out Set- points For Each Stage Cool Cut In/Cut Out Set- points For Each StageModular Chiller Con- trol MCC Flexible CombinerLearning Mode Control/Cycles Parame TerCompressor Control Bypass Valve Control BoilerDigital Scroll Compressor Variable Frequency Drive Com PressorRMS Scale RMS AssetLog Information Device ConstraintsUnlogged Changes Logged ChangesPage Operator’s Guide to Using the E2 E2 Home ScreenBX Home Screen RX Home Screen CX Home Screen Logging On and Access LevelsToggling Full Options System Configuration MenuNavigation MenusActions Menu System Information MenuScreen Types Setup ScreensStatus Screens Summary ScreensIndex Tabs E2 KeypadHeader Icons CursorTab Key Enter KeyKeypad Four Directional Arrow Keys Log In/Out KeyUp/Page Down Keys Ctrl Page Up/Ctrl Page Down KeysCustomizing the Home Screen Manual Defrost and Clean ModeKeys Function EditOverrides List menu and choose End Manual ModeChecking Status Screens Checking Boards OnlineAccessing the Alarm Advi Sory Log AlarmsViewing the Controller Advi Sory Log Date and TimeArea Ctrl Application Prop Erty 12.10.5 Ack/Reset StateAdvisory Message AcknowledgingClearing ResettingViewing Logs and Graphs Facility Status Display FSD AlarmsLocating Logged Inputs Outputs Home/Status ScreensSetting Up Input and Output Pointers Setup ScreensZooming In and Out Log ViewLow Battery Notifica Tion Appendix a Case Type Defaults High Alarm, Low Alarm, and DelayDefrost Type Hdbx 100 lb 200 lb 500 lb Xducer Eclipse Transducers Voltage Pressure PSIPage Alarm Name Default Definition Priority Appendix C Alarm Advisory MessagesE2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 Appendix C Alarm Advisory Messages C-3 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-5 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-7 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-9 10 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 Appendix C Alarm Advisory Messages C-11 12 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 RAM 14 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 Proportional P Mode Appendix D PID ControlThrottling Range Why I Mode is Necessary Integral ModeProportional Constant Kp Throttling Range on page D-1Derivative Mode I Mode CalculationSaturation How Condenser Control Hvac PID Differs From Others D Mode CalculationOutput at Setpoint Output at Setpoint for Non-CondenserChanging the Output at Setpoint Other PID FeaturesOutput at Minimum / Output at Max- imum Output at Setpoint for Condenser/HVAC PID ControlFiltering Minimum Accumulated ErrorPage Page Medium Resolution Reuccf Page Page Refer to .1.9, Powering Appendix F TroubleshootingEchelon Network Appendix F Troubleshooting F-3 Symptom Possible Problem Solution Trip Number of Fans field?Symptom Possible Problem Solution Appendix F Troubleshooting F-7 Figured as an analog input Page Page Appendix G Revision Log Page Numerics IndexLow 4-6,12-18 CS-100.See Case Controllers, CS-100 Demand Defrost. See Defrost, demand Hot Gas Defrost. See Defrost, hot gas Jumpers PAK 2-7,11-30 Pmac Hansen probe. See Sensors, liquid level 10 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 E2 4-2RS485 jumpers