Emerson E2 operation manual Derivative Mode, I Mode Calculation, Saturation

Page 239

TEMPERATURE

 

TEMPERATURE

 

S E T

P O I N T

S E T

P O I N T

 

TIME

 

TIME

“P” MODE ONLY

“P” + “I” MODES

 

 

Figure D-2- Comparison of “P” Mode vs. “P” + “I” Mode

Saturation

Once the input value has wandered outside Propor- tional Mode’s throttling range, the output percentage will be at 0% (if below the Throttling Range) or at 100% (if above the Throttling Range). At this point, PID is consid- ered to be in saturation, meaning it is operating at full (or zero) capacity and is not able to react any further to changes that occur beyond the throttling range.

Proportional Mode cannot distinguish between a satu- rated and an unsaturated system; it simply makes propor- tional adjustments to the output percentage. Therefore, once an input value in a saturated system changes direc- tion, Proportional Mode reacts to correct the movement, regardless of how much error exists. As the temperature changes direction and again moves in the direction of the

.

setpoint, Proportional Mode will reduce the 100% output percentage in an attempt to stop the movement and stabi- lize the temperature.

To put it another way, when a system is saturated, the input changes the placement of the Throttling Range. As shown in Figure D-2, as the input rises above the Throt- tling Range, the top end of the Throttling Range rises with it. When the input finally changes direction, the Throttling Range remains at its new position.

The “I” Mode covers for Proportional Mode’s inability to account for saturation. When the input value is outside the throttling range, “I” Mode will continue to adjust the output percentage to bring the input value towards the set- point

 

 

CHANGES DIRECTION, THROTTLE RANGE REMAINS

 

 

AS INPUT IN SATURATED SYSTEM

 

SATURATION

 

 

 

CHANGES DIRECTION, THROTTLE RANGE REMAINS

 

 

 

SATURATION

 

 

 

 

 

 

“I” CORRECTS ERROR AND BRINGS

 

 

 

 

 

 

 

THROTTLING RANGE

100%

 

 

THROTTLING RANGE

100%

 

THROTTLING RANGE BACK TO NORMAL

 

 

 

 

 

S E T

P O I N T

 

S E T

P O I N T

0%

THROTTLING RANGE

0%

THROTTLING RANGE

 

 

FOLLOWS INPUT DURING

 

 

FOLLOWS INPUT DURING

 

 

SATURATION

 

 

 

SATURATION

 

“P” MODE ONLY

TIME

 

“P” + “I” MODES

TIME

 

 

 

Figure D-3- Saturation in “P” vs. “P” + “I” Modes

The “I” Mode Calculation

To determine the “I” Mode adjustment for each update, the following calculation occurs:

When changing the value of Ki, it should be noted that small adjustments yield large results. For this reason, it is suggested that Ki should remain close to 1.0 and certainly no less than 0.5 and no greater than 2.0.

“I” mode adjustment = Ki * (current error)

Ki in this equation is called the integral constant. It is simply a multiplier that increases or decreases the speed at which the “I” Mode will increase or decrease the percent- age.

Derivative Mode

The Proportional and Integral Modes provide a good method of controlling a closed-loop system. However, in special circumstances where the input value is changing rapidly, there may be a lag time between when the error is noted and the length of time it takes the system to compen-

Introduction to PID Control

Appendix D: PID Control D-3

Image 239
Contents Rev 13 14-SEP-2011 BX HVAC, and CX Convenience Store ControllersPage FCC Compliance Notice Page Table of Contents E2 Hardware Setup Serial Configuration E2 Ethernet Peer Communications Quick Start Software Overview Logging Groups Multiflex CUB Board Holiday Schedules OPERATOR’S Guide to Using the E2 LOW Battery Notification Page E2 Refrigeration Controller IntroductionMrlds E2 Building Con- trollerE2 Convenience Store Controller 1 E2 I/O Network Networking OverviewAble for the RS485 Network NetworkInterconnection With Other E2s Documentation Over ViewOn-Line Help System Overview Software Licensing E2 Hardware Hardware OverviewPIB LEDs Status 1 E2 Main Processor Board 3 E2 KeypadLEDs Keyboard Status I/O Network Boards and PeripheralsGateway Board Main Board Status CPU LEDsModel Name Description MultiFlex BoardsMultiFlex 16 Input Board Gateway ModelModel Description Name MultiFlex Combination Input/ Output BoardsE2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 MultiFlex PAK Board MultiFlex CUBMultiFlex RTU BX and CX Only MultiFlex Rooftop Control Board RCB BX and CX OnlyHand-held Terminal P/N MultiFlex ESR Board10- Hand-held Terminal 8RO and 8ROSMT Relay Boards13- 4AO Analog Output Board P/N 6 4AO Analog Output Board8ROe Dis 16AIe Dis20- Case Controller CC-100P shown ESR8 DisFacility Status Display FSD 6 TD3 Temperature DisplayPage Recessed Mount MountingMounting the E2 Standard MountStandard Mount Inside Rear of Enclosure Retrofit MountingSingle/Double Enclosures Mounting I/O BoardsBlank Face 1 16AIe and 8ROe Echelon DevicesBoards Without Enclosures Snap Track 5 TD3 3 ESR8 DisMultiFlex ESR Mounting the Two-Channel Repeater Two-Channel and Four- Channel RepeatersInternal Modem Mounting Repeaters OverviewPressure Transducers Inside Temperature SensorSensors and Transduc Ers Supply and Return Air Sen Sors Outside Temperature Sen SorInsertion Temperature Probe Indoor RH Sensor Product Temperature ProbesHumidity Sensors and Humidistats Mounting Bullet and Pipe Mount SensorsOutdoor RH sensor P/N Outdoor RH SensorsDuct-mounted Insertion RH Probe Refrigerant Leak Detectors Dewpoint ProbeLight Level Sensor Liquid Level SensorsPage Main Processor Board E2 Hardware SetupSetting up the E2 EnclosurePowering the E2 Echelon Card Plug-In P/N 537-4860with mounting screw P/N Add-On E2 PeripheralsModem P/N Description Plug-In Digital I/O Network Card P/NLEDs Battery Testing and Replacement5 E2 RS485 Port Card P/N 537-4890 Plug-In Four-Channel Inter- nal RepeaterBattery Replacement Qual- ified Technicians Only Low Battery NotificationBattery Enable Switch Battery TestEchelon Earth Page COM Ports Serial Configura- tionSerial Device and Soft Ware Setup OverviewE2 COM# Associations Connector Board RS485 Network and Hardware SetupI/O Network 1 I/O Board Names and Termi NologyNetwork Noise Minimiza Tion Wiring TypesMultiFlex-Plus + Board I/O Network Structure Daisy ChainsNetwork ID Numbers Board Numbers Setting the Baud RatePowering the I/O Boards Setting the Terminating and Biasing JumpersIMC/Prodigy Rooftop Unit Controllers Board InstallationWiring Types 3.1 XR75CX-Case Display Copeland Discus with Core- Sense Diagnostics ISDControl Techniques Drive 3 XR35CX, XR75CX, XEV22 Case ControllersSupported System Types IPro DACEnergy Meter OverviewLight Commercial Thermo Stat Advisory and AlarmsDiagnostic Alarm Descriptions E2 Advisory Copeland Discus with Core- Sense ProtectionComfort Alert Descriptions Cause E2 Advisory Comfort Alert CodesConditions for Return to Normal RTN on Diag- nostic Codes High/Low Occ/Unocc Space Temperature AlarmsSupply Sensor Fail Alarm Copeland Scroll K5 Refrig- eration Compressor Diagnostic AlarmsDiagnostic Alarm Descriptions Refrigerant Leak Detection System Rlds11.3 XM678 XM Series of Case Control Lers11.1 XM670 11.2 XM679RS485 Network and Hardware Setup 6 14 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 NET 16 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 120/208/240 VAC 16AI Installation Guide MultiFlex ESR Installation Guide XEV22D Driver to E2 Installation Guide XR35CX, XR75CX to E2 Installation Guide Page Hardware Specifica Tions Ethernet IP Configura TionsEquipment Specifications Type E2 Ethernet Peer CommunicationsClosed Network Layout Software Specifica TionsEthernet Network Layouts Open Network Layout Software Setup5Peer Network Tab Set Group Name TroubleshootingLoop Resistance Echelon Network and Hardware SetupWiring Type Cable Type Retail Solutions Part NumberMaximum Number of Eche- lon Devices Device TerminationMaximum Total Segment Length Wire RestrictionsInstalling Echelon Devices Powering Echelon DevicesOpen Echelon Device Connectivity Configuring Echelon DevicesLEDs Connected I/O Screen E2 firmware versions 2.81 and above TroubleshootingE2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 One pin when unterminating an E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 8IO and Artc Boards All Analog Temperature Sensors and Air Flow SensorsMultiFlex Boards 16AI BoardsPower Connection Down Sensor Input Type Wiring Dip SwitchWall-mounted Down 207-1000 Refrigerant Pulse Sensor Input TypeMA output to input board 20mA, Up forAssociation ApplicationPulse on Sensor Type DescriptionSetting Up Digital Inputs Set 8RO, 8ROe, 8IO, and MultiFlex OutputsNew 8ROs and 8RO-FCs Old 8ROsSetting Up Digital Outputs Setting Up Analog Outputs Connection Temperature and Digital SensorsHand-Held Terminal Jack Auxiliary Analog Input335-3260 Generic Stepper and Emerson Flow Controls ESV Valve 335-3263 Pulse ValvePin Page Logging On Cleaning Out the Con- trollerPerforming a Clean Out Quick StartUnit Controllers Echelon Setting Number of Network DevicesBoards on the I/O Network Customizing the Home Screen Setting Number of ApplicationsHelp Line Common Screen Ele- mentsHeader Function KeysMain Menu Screen TypesStatus Screens Actions Menu Item Description Actions MenuKey Function for Menu Option Description Setup ScreensSystem Configuration Menu 13- System Information Menu System Information MenuSetting the Time and Date Time/Date SetupSet Up Modem 17- TCP/IP Addressing Set Up TCP/IP10.11.2 I/O Network Baud Rate Set Up Network Baud Rates10.11.1 COM1 Serial RS232 Baud Rate Level Set Up User AccessDeleting a User Changing Required User Access LevelsCreating a New User Account Specify Number of Boards Set Up I/O NetworkSpecifying Number Devices Set Up Echelon Net WorkChecking Online Status Modbus Commissioning Service Button MethodCommissioning a Device How Echelon Commissioning WorksCommissioning the EC-2 CC-100’s Service ButtonTD3’s Service Button ESR8’s Service ButtonManual ID Entry Method License Management33- TCP/IP Screen Locating the Mac Address Web Services37- Alarm Setup Menu Set Up AlarmingSetting up an E2 to be an Alarm Annunciator Specifying Alarm Reporting TypesIntroduction Alarm Report Ing Alarm Dial-OutPriority Settings Set Up Global DataExample Setting Up an Outdoor Temperature Sen- sor Set Up ApplicationsDelete an Application Using and Configuring a Setup Screen10.18.1 Add/Delete an Application Add an ApplicationEntering Setpoints Navigating the Setup ScreenEdit Menu Help Line Function Keys For SetupIndex Tabs Using the Help Key to get Property Help Page Standard Suction Group Application Software OverviewSuction Groups IntroductionControl/Cycles Parameter Learning ModeHardware Overview Circuit Load AnalysisAir Cooled Condensers Temperature Differential Strat EgyInput Sensor Type Wiring Instructions Condenser ControlFan Control Condenser Split ModeFast Recovery Evaporative CondensersRefrigeration Control Standard CircuitsDefrost Control Clean and Door Switches Control Link CD Case Display TD3 Temperature DisplayWiring Typical Case in a Standard Circuit Case Circuit Control Soft- ware Overview Case Control CircuitsOverview EEVs Liquid Pulse and Liquid Stepper Valve ControlOff Cycle Timed EEPRs Suction StepperThermostatic Expansion Valves TXVs Wait State Temperature TerminationAnti-Sweat Control Demand DefrostDewpoint Input Sources Clean/Wash ModeDual Temp Control Light ControlWalk-In Freezer Control Fail-Safe ModeRecoverable Sensor Failures Logging Groups Setting Up An Individual Case ControllerClipping Possible Data ErrorsData Compression Base Log GroupLogging Setup Menu Setting Up LoggingLog Reports Logging Group Status ScreenSystem Log Report Logging Group ReportApplication Log Report Single-Speed Fans Temperature ControlAir Handling Units Alternate SetpointsVariable-Speed Fans Economization EnableEconomizer Control Two-Speed FansCurtailment Digital Economizer ControlAnalog Economizer Control Dehumidification ControlIntelligent Pre-Starts and Pre-Stops Inputs Sensor Type Wiring InstructionsSeparate Setpoints AHU Zone ControlTion Zone ControlSection MultiFlex RCB Board How Zones WorkApplications That May Be Connected To Zones MultiFlex RTU BoardEconomization Enable Zone TemperatureMultiFlex RTUs and RCBs Effect of Enabling Econ- omizationZone Humidity Input Effect of Enabling Dehu- midificationMultiFlex RTU/ARTC and AHU Zone Association Losing Contact With Zone ApplicationsStand-Alone MultiFlex RTUs Lighting Schedules MultiFlex CUB BoardMultiFlex PAK Board Light Level Interface Cell Functions of the Lighting Schedule ApplicationControl Method Select Standard ControlMulti-Logic Combiner Alternate ControlSchedule Interface Cell Offset Solar Control Basic Schedule CellMin ON/OFF Cell Proof CellDemand Monitoring Demand ControlOutput Light Dimming Introduction to Demand Limit ControlDefinition Load SheddingShedding Levels Priority LevelsOther Notes About Priority Levels Rotational ShedLast Shed How Demand Control Uses Load Shedding Mode 1 KW Input Is Greater Than SetpointMode 3 Integral Error Approaching Zero Cut In/Cut Out Setpoint Con Trol Power Monitoring InputSensor Control Analog Sensor ControlControl Cells Loop/Sequence Con TrolLogical Combination Select Cell DiagramLoop/Sequence Control Cell Descriptions Output CellsOutput Cell Descriptions Absolute and Relative Events Time Scheduling and HolidaysHow Schedules Work EventsRanges Power MonitoringHoliday Schedules OverlappingMonthly LoggingHourly DailyUnoccupied Hysteresis Anti-Sweat SetupHeat/Cool Control How Anti-Sweat WorksStops Setpoint ResetLead/Lag Analog and Digital CombinersTD Control Fail-Safes Temperature Differential TD StrategyConfiguration TD ControlOutputs AlarmsPulse Accumulation InputsZones and Cycles Accumulator Reset TypesIrrigation Control High TripZone Bypass Inputs Cycle SchedulingZone Inhibit Cool Cut In/Cut Out Set- points For Each Stage Service ModesFlow Sensor-Related Tests Heat Cut In/Cut Out Set- points For Each StageModular Chiller Con- trol MCC Flexible CombinerCompressor Control Learning ModeControl/Cycles Parame Ter Variable Frequency Drive Com Pressor BoilerBypass Valve Control Digital Scroll CompressorDevice Constraints RMS AssetRMS Scale Log InformationUnlogged Changes Logged ChangesPage BX Home Screen RX Home Screen Operator’s Guide to Using the E2E2 Home Screen CX Home Screen Logging On and Access LevelsMenus System Configuration MenuToggling Full Options NavigationActions Menu System Information MenuSummary Screens Setup ScreensScreen Types Status ScreensCursor E2 KeypadIndex Tabs Header IconsKeypad Tab KeyEnter Key Ctrl Page Up/Ctrl Page Down Keys Log In/Out KeyFour Directional Arrow Keys Up/Page Down KeysEdit Manual Defrost and Clean ModeCustomizing the Home Screen Keys FunctionOverrides List menu and choose End Manual ModeChecking Status Screens Checking Boards OnlineDate and Time AlarmsAccessing the Alarm Advi Sory Log Viewing the Controller Advi Sory LogAcknowledging 12.10.5 Ack/Reset StateArea Ctrl Application Prop Erty Advisory MessageClearing ResettingHome/Status Screens Facility Status Display FSD AlarmsViewing Logs and Graphs Locating Logged Inputs OutputsSetting Up Input and Output Pointers Setup ScreensZooming In and Out Log ViewLow Battery Notifica Tion Defrost Type Appendix a Case Type DefaultsHigh Alarm, Low Alarm, and Delay Hdbx 100 lb 200 lb 500 lb Xducer Eclipse Transducers Voltage Pressure PSIPage Alarm Name Default Definition Priority Appendix C Alarm Advisory MessagesE2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 Appendix C Alarm Advisory Messages C-3 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-5 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-7 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-9 10 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 Appendix C Alarm Advisory Messages C-11 12 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 RAM 14 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 Throttling Range Proportional P ModeAppendix D PID Control Throttling Range on page D-1 Integral ModeWhy I Mode is Necessary Proportional Constant KpSaturation Derivative ModeI Mode Calculation Output at Setpoint for Non-Condenser D Mode CalculationHow Condenser Control Hvac PID Differs From Others Output at SetpointOutput at Setpoint for Condenser/HVAC PID Control Other PID FeaturesChanging the Output at Setpoint Output at Minimum / Output at Max- imumFiltering Minimum Accumulated ErrorPage Page Medium Resolution Reuccf Page Page Refer to .1.9, Powering Appendix F TroubleshootingEchelon Network Appendix F Troubleshooting F-3 Symptom Possible Problem Solution Trip Number of Fans field?Symptom Possible Problem Solution Appendix F Troubleshooting F-7 Figured as an analog input Page Page Appendix G Revision Log Page Numerics IndexLow 4-6,12-18 CS-100.See Case Controllers, CS-100 Demand Defrost. See Defrost, demand Hot Gas Defrost. See Defrost, hot gas Jumpers PAK 2-7,11-30 Pmac Hansen probe. See Sensors, liquid level 10 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 E2 4-2RS485 jumpers
Related manuals
Manual 283 pages 10.27 Kb