total accumulation, and the last accumulated total informa- tion can be viewed.

The current output shows the rate of consumption of the quantity represented by pulses. Average output shows the average rate value accumulated over the period set in the Average Window parameter. The High Limit Trip out- put will turn on if the total accumulation exceeds a user- specified high limit. Total accumulation shows the total accumulated value since the last reset. Last Total output shows the total accumulated value when the last reset occurred.

11.20.4 Accumulator Reset Types

The Pulse Accumulator is a register that is increased by the value of each update of the Quantity Accumulation input. Each time the Accumulator is reset, before clearing, its value is saved to a Last Total output. The type of reset the Accumulator uses can be user-specified with the Accu- mulator Reset Type parameter. The Accumulator can be set to reset at a certain time of day, day of the month, when a high-limit trip occurs, or not to reset at all.

11.20.5 Logging

Rate and usage data is logged and stored using applica- tion logging. Data is stored in hourly, daily, and monthly formats. All logged data can be erased from memory by using the Applications Command menu. In addition, appli- cation logs show the total and peak rates of consumption for the last day, hour, and month.

The Hourly log will be updated every hour at the top of the hour and contain data for the last 48 hours. Time, date, total accumulation for that hour, maximum average for that hour, maximum peak value, and time of peak value, are stored in this log.

The Daily log will contain data for the last 48 days. Date, total accumulation for that day, maximum average for that day, maximum peak value, time of peak value, and minutes tripped are stored in this log.

The Monthly log will contain data for the last 24 months. The log will be updated on a user-specified day of the month. Date, total accumulation for that month, maxi- mum average for that month, maximum peak value, time of peak value, and date of peak value are stored in this log.

Application graphing generates hourly, daily, and monthly graphs from the application log data. All graphs show the total and max average.

On the main Status screen, consumption for the current hour, day, and month are displayed.

11.20.6 High Trip

Ahigh-trip output can be triggered if the Accumula- tor’s total quantity exceeds a user-defined setpoint. The

trip point output can be controlled by any of three input sources. The output will be turned ON when the input source is equal to or greater than a user-specified value. The total amount of time the application has been in a high trip condition is shown in the Time In Trip Today output.

11.21 Irrigation Control

11.21.1 Overview

Irrigation control is an application used for the control- ling of sprinkler systems. This application controls water- ing by duration of time or water usage parameters. Days of the week and times for watering are set by the user with a maximum of two Irrigation applications allowed in the CX controller.

The master water valve is turned ON and OFF as water is needed for a zone. When disabled, no application con- trol of any outputs will be possible and the System Status output will indicate Disabled.

Under normal control only one zone will be active at a time.

11.21.2 Zones and Cycles

A zone is defined as a single line of irrigation fed from a main water supply valve (i.e., a group of sprinklers that are attached to the same line of irrigation). Up to 16 zones of irrigation per application are supported with six start times for watering. The user will be able to configure each zone to function on different days of the week or odd or even days of the month.

Zones are turned ON one at a time starting from the first enabled zone. The zone that is ON is considered to be the active zone. Its state is set to ON and its valve output is also set to ON. When the active zone completes its time duration, its state will be set to Done and its valve output set to OFF.

For enabled zones that are not active or complete, the states will be set to Pending and the valve output set to OFF.

A cycle is the sequence of all defined zones irrigating one at a time. A cycle is considered complete when the last defined zone finishes irrigating and shuts OFF. Each zone turns ON one at a time, starting with the first defined zone until the last defined zone in the list turns OFF.

The Number of Zones parameter (with a default value of 4) specifies how many zones the application will use. No two zones are ever ON at the same time; each zone starts and stops independently and waits for the other to finish before another zone starts.

11-50 E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011

Image 192
Contents BX HVAC, and CX Convenience Store Controllers Rev 13 14-SEP-2011Page FCC Compliance Notice Page Table of Contents E2 Hardware Setup Serial Configuration E2 Ethernet Peer Communications Quick Start Software Overview Logging Groups Multiflex CUB Board Holiday Schedules OPERATOR’S Guide to Using the E2 LOW Battery Notification Page Introduction E2 Refrigeration ControllerE2 Building Con- troller MrldsE2 Convenience Store Controller Networking Overview 1 E2 I/O NetworkNetwork Able for the RS485 NetworkDocumentation Over View Interconnection With Other E2sOn-Line Help System Overview Software Licensing Hardware Overview E2 Hardware1 E2 Main Processor Board 3 E2 Keypad LEDsPIB LEDs Status I/O Network Boards and Peripherals Gateway BoardMain Board Status CPU LEDs Keyboard StatusMultiFlex Boards MultiFlex 16 Input BoardGateway Model Model Name DescriptionMultiFlex Combination Input/ Output Boards Model Description NameE2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 MultiFlex CUB MultiFlex RTU BX and CX OnlyMultiFlex Rooftop Control Board RCB BX and CX Only MultiFlex PAK BoardMultiFlex ESR Board Hand-held Terminal P/N8RO and 8ROSMT Relay Boards 10- Hand-held Terminal6 4AO Analog Output Board 13- 4AO Analog Output Board P/N16AIe Dis 8ROe DisESR8 Dis 20- Case Controller CC-100P shown6 TD3 Temperature Display Facility Status Display FSDPage Mounting Mounting the E2Standard Mount Recessed MountRetrofit Mounting Standard Mount Inside Rear of EnclosureMounting I/O Boards Blank FaceSingle/Double Enclosures Echelon Devices Boards Without Enclosures Snap Track1 16AIe and 8ROe 3 ESR8 Dis MultiFlex ESR5 TD3 Two-Channel and Four- Channel Repeaters Internal ModemMounting Repeaters Overview Mounting the Two-Channel RepeaterInside Temperature Sensor Sensors and Transduc ErsPressure Transducers Outside Temperature Sen Sor Insertion Temperature ProbeSupply and Return Air Sen Sors Product Temperature Probes Humidity Sensors and HumidistatsMounting Bullet and Pipe Mount Sensors Indoor RH SensorOutdoor RH Sensors Duct-mounted Insertion RH ProbeOutdoor RH sensor P/N Dewpoint Probe Light Level SensorLiquid Level Sensors Refrigerant Leak DetectorsPage E2 Hardware Setup Setting up the E2Enclosure Main Processor BoardPowering the E2 Add-On E2 Peripherals Echelon Card Plug-In P/N 537-4860with mounting screw P/NPlug-In Digital I/O Network Card P/N Modem P/N DescriptionBattery Testing and Replacement 5 E2 RS485 Port Card P/N 537-4890Plug-In Four-Channel Inter- nal Repeater LEDsLow Battery Notification Battery Enable SwitchBattery Test Battery Replacement Qual- ified Technicians OnlyEchelon Earth Page Serial Configura- tion Serial Device and Soft Ware SetupOverview COM PortsE2 COM# Associations Connector RS485 Network and Hardware Setup I/O Network1 I/O Board Names and Termi Nology BoardWiring Types MultiFlex-Plus + BoardI/O Network Structure Daisy Chains Network Noise Minimiza TionSetting the Baud Rate Network ID Numbers Board NumbersSetting the Terminating and Biasing Jumpers Powering the I/O BoardsBoard Installation Wiring TypesIMC/Prodigy Rooftop Unit Controllers Copeland Discus with Core- Sense Diagnostics ISD Control Techniques Drive3 XR35CX, XR75CX, XEV22 Case Controllers 3.1 XR75CX-Case DisplayIPro DAC Energy MeterOverview Supported System TypesAdvisory and Alarms Diagnostic Alarm Descriptions E2 AdvisoryCopeland Discus with Core- Sense Protection Light Commercial Thermo StatComfort Alert Codes Comfort Alert Descriptions Cause E2 AdvisoryHigh/Low Occ/Unocc Space Temperature Alarms Supply Sensor Fail AlarmConditions for Return to Normal RTN on Diag- nostic Codes Diagnostic Alarms Diagnostic Alarm DescriptionsRefrigerant Leak Detection System Rlds Copeland Scroll K5 Refrig- eration CompressorXM Series of Case Control Lers 11.1 XM67011.2 XM679 11.3 XM678RS485 Network and Hardware Setup 6 14 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 NET 16 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 120/208/240 VAC 16AI Installation Guide MultiFlex ESR Installation Guide XEV22D Driver to E2 Installation Guide XR35CX, XR75CX to E2 Installation Guide Page Ethernet IP Configura Tions Equipment Specifications TypeE2 Ethernet Peer Communications Hardware Specifica TionsSoftware Specifica Tions Ethernet Network LayoutsClosed Network Layout Software Setup Open Network LayoutTroubleshooting 5Peer Network Tab Set Group NameEchelon Network and Hardware Setup Wiring TypeCable Type Retail Solutions Part Number Loop ResistanceDevice Termination Maximum Number of Eche- lon DevicesWire Restrictions Installing Echelon DevicesPowering Echelon Devices Maximum Total Segment LengthConfiguring Echelon Devices LEDsOpen Echelon Device Connectivity Troubleshooting Connected I/O Screen E2 firmware versions 2.81 and aboveE2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 One pin when unterminating an E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 All Analog Temperature Sensors and Air Flow Sensors MultiFlex Boards16AI Boards 8IO and Artc BoardsPower Connection Sensor Input Type Wiring Dip Switch DownWall-mounted Down 207-1000 Refrigerant Sensor Input Type MA output to input board20mA, Up for PulseApplication AssociationSensor Type Description Pulse onSetting Up Digital Inputs 8RO, 8ROe, 8IO, and MultiFlex Outputs SetOld 8ROs New 8ROs and 8RO-FCsSetting Up Digital Outputs Setting Up Analog Outputs Temperature and Digital Sensors ConnectionAuxiliary Analog Input Hand-Held Terminal Jack335-3263 Pulse Valve 335-3260 Generic Stepper and Emerson Flow Controls ESV ValvePin Page Cleaning Out the Con- troller Performing a Clean OutQuick Start Logging OnSetting Number of Network Devices Boards on the I/O NetworkUnit Controllers Echelon Setting Number of Applications Customizing the Home ScreenCommon Screen Ele- ments HeaderFunction Keys Help LineScreen Types Status ScreensMain Menu Actions Menu Key Function forActions Menu Item Description Setup Screens System Configuration MenuMenu Option Description System Information Menu 13- System Information MenuTime/Date Setup Setting the Time and DateSet Up Modem Set Up TCP/IP 17- TCP/IP AddressingSet Up Network Baud Rates 10.11.1 COM1 Serial RS232 Baud Rate10.11.2 I/O Network Baud Rate Set Up User Access LevelChanging Required User Access Levels Creating a New User AccountDeleting a User Set Up I/O Network Specify Number of BoardsSet Up Echelon Net Work Checking Online StatusSpecifying Number Devices Service Button Method Commissioning a DeviceHow Echelon Commissioning Works Modbus CommissioningCC-100’s Service Button TD3’s Service ButtonESR8’s Service Button Commissioning the EC-2License Management Manual ID Entry MethodWeb Services 33- TCP/IP Screen Locating the Mac AddressSet Up Alarming 37- Alarm Setup MenuSpecifying Alarm Reporting Types Setting up an E2 to be an Alarm AnnunciatorAlarm Dial-Out Introduction Alarm Report IngSet Up Global Data Priority SettingsSet Up Applications Example Setting Up an Outdoor Temperature Sen- sorUsing and Configuring a Setup Screen 10.18.1 Add/Delete an ApplicationAdd an Application Delete an ApplicationNavigating the Setup Screen Edit MenuEntering Setpoints Function Keys For Setup Index TabsHelp Line Using the Help Key to get Property Help Page Software Overview Suction GroupsIntroduction Standard Suction Group ApplicationLearning Mode Hardware OverviewCircuit Load Analysis Control/Cycles ParameterTemperature Differential Strat Egy Input Sensor Type Wiring InstructionsCondenser Control Air Cooled CondensersCondenser Split Mode Fast RecoveryEvaporative Condensers Fan ControlStandard Circuits Refrigeration ControlDefrost Control Clean and Door Switches TD3 Temperature Display WiringControl Link CD Case Display Typical Case in a Standard Circuit Case Control Circuits OverviewCase Circuit Control Soft- ware Overview Valve Control EEVs Liquid Pulse and Liquid StepperEEPRs Suction Stepper Thermostatic Expansion Valves TXVsOff Cycle Timed Temperature Termination Anti-Sweat ControlDemand Defrost Wait StateClean/Wash Mode Dual Temp ControlLight Control Dewpoint Input SourcesFail-Safe Mode Recoverable Sensor FailuresWalk-In Freezer Control Setting Up An Individual Case Controller Logging GroupsPossible Data Errors Data CompressionBase Log Group ClippingSetting Up Logging Logging Setup MenuLogging Group Status Screen Log ReportsLogging Group Report Application Log ReportSystem Log Report Temperature Control Air Handling UnitsAlternate Setpoints Single-Speed FansEconomization Enable Economizer ControlTwo-Speed Fans Variable-Speed FansDigital Economizer Control Analog Economizer ControlDehumidification Control CurtailmentInputs Sensor Type Wiring Instructions Separate SetpointsAHU Zone Control Intelligent Pre-Starts and Pre-StopsZone Control SectionTion How Zones Work Applications That May Be Connected To ZonesMultiFlex RTU Board MultiFlex RCB BoardZone Temperature Economization EnableEffect of Enabling Econ- omization Zone Humidity InputEffect of Enabling Dehu- midification MultiFlex RTUs and RCBsLosing Contact With Zone Applications Stand-Alone MultiFlex RTUsMultiFlex RTU/ARTC and AHU Zone Association MultiFlex CUB Board MultiFlex PAK BoardLighting Schedules Functions of the Lighting Schedule Application Control Method SelectStandard Control Light Level Interface CellAlternate Control Schedule Interface CellMulti-Logic Combiner Basic Schedule Cell Min ON/OFF CellProof Cell Offset Solar ControlDemand Control Output Light DimmingIntroduction to Demand Limit Control Demand MonitoringLoad Shedding Shedding LevelsPriority Levels DefinitionRotational Shed Last ShedOther Notes About Priority Levels Mode 1 KW Input Is Greater Than Setpoint Mode 3 Integral Error Approaching ZeroHow Demand Control Uses Load Shedding Power Monitoring Input Sensor ControlAnalog Sensor Control Cut In/Cut Out Setpoint Con TrolLoop/Sequence Con Trol Logical CombinationControl Cells Diagram Loop/Sequence Control Cell DescriptionsOutput Cells Select CellOutput Cell Descriptions Time Scheduling and Holidays How Schedules WorkEvents Absolute and Relative EventsPower Monitoring Holiday SchedulesOverlapping RangesLogging HourlyDaily MonthlyAnti-Sweat Setup Heat/Cool ControlHow Anti-Sweat Works Unoccupied HysteresisSetpoint Reset StopsAnalog and Digital Combiners Lead/LagTemperature Differential TD Strategy ConfigurationTD Control TD Control Fail-SafesAlarms Pulse AccumulationInputs OutputsAccumulator Reset Types Irrigation ControlHigh Trip Zones and CyclesCycle Scheduling Zone InhibitZone Bypass Inputs Service Modes Flow Sensor-Related TestsHeat Cut In/Cut Out Set- points For Each Stage Cool Cut In/Cut Out Set- points For Each StageFlexible Combiner Modular Chiller Con- trol MCCLearning Mode Control/Cycles Parame TerCompressor Control Boiler Bypass Valve ControlDigital Scroll Compressor Variable Frequency Drive Com PressorRMS Asset RMS ScaleLog Information Device ConstraintsLogged Changes Unlogged ChangesPage Operator’s Guide to Using the E2 E2 Home ScreenBX Home Screen RX Home Screen Logging On and Access Levels CX Home ScreenSystem Configuration Menu Toggling Full OptionsNavigation MenusSystem Information Menu Actions MenuSetup Screens Screen TypesStatus Screens Summary ScreensE2 Keypad Index TabsHeader Icons CursorTab Key Enter KeyKeypad Log In/Out Key Four Directional Arrow KeysUp/Page Down Keys Ctrl Page Up/Ctrl Page Down KeysManual Defrost and Clean Mode Customizing the Home ScreenKeys Function EditList menu and choose End Manual Mode OverridesChecking Boards Online Checking Status ScreensAlarms Accessing the Alarm Advi Sory LogViewing the Controller Advi Sory Log Date and Time12.10.5 Ack/Reset State Area Ctrl Application Prop ErtyAdvisory Message AcknowledgingResetting ClearingFacility Status Display FSD Alarms Viewing Logs and GraphsLocating Logged Inputs Outputs Home/Status ScreensSetup Screens Setting Up Input and Output PointersLog View Zooming In and OutLow Battery Notifica Tion Appendix a Case Type Defaults High Alarm, Low Alarm, and DelayDefrost Type Hdbx Eclipse Transducers Voltage Pressure PSI 100 lb 200 lb 500 lb XducerPage Appendix C Alarm Advisory Messages Alarm Name Default Definition PriorityE2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 Appendix C Alarm Advisory Messages C-3 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-5 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-7 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-9 10 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 Appendix C Alarm Advisory Messages C-11 12 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 RAM 14 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 Proportional P Mode Appendix D PID ControlThrottling Range Integral Mode Why I Mode is NecessaryProportional Constant Kp Throttling Range on page D-1Derivative Mode I Mode CalculationSaturation D Mode Calculation How Condenser Control Hvac PID Differs From OthersOutput at Setpoint Output at Setpoint for Non-CondenserOther PID Features Changing the Output at SetpointOutput at Minimum / Output at Max- imum Output at Setpoint for Condenser/HVAC PID ControlMinimum Accumulated Error FilteringPage Page Medium Resolution Reuccf Page Page Appendix F Troubleshooting Refer to .1.9, PoweringEchelon Network Appendix F Troubleshooting F-3 Symptom Possible Problem Solution Number of Fans field? TripSymptom Possible Problem Solution Appendix F Troubleshooting F-7 Figured as an analog input Page Page Appendix G Revision Log Page Index NumericsLow 4-6,12-18 CS-100.See Case Controllers, CS-100 Demand Defrost. See Defrost, demand Hot Gas Defrost. See Defrost, hot gas Jumpers PAK 2-7,11-30 Pmac Hansen probe. See Sensors, liquid level 10 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 E2 4-2RS485 jumpers