Emerson E2 operation manual Multiflex CUB Board

Page 12

11.7.2

How Zones Work

11-26

11.7.3 Applications That May Be Connected To Zones

11-26

 

 

11.7.3.1

MultiFlex RTU Board

11-26

 

 

11.7.3.2

MultiFlex RCB Board

11-26

 

 

11.7.3.3

AHUs

11-26

11.7.4

Temperature Control

11-27

11.7.5

Zone Temperature

11-27

11.7.6

Economizer Control

11-27

11.7.7

Economization Enable

11-27

11.7.8 The Effect of Enabling Economization

11-28

11.7.9

Dehumidification Control

11-28

11.7.10 The Zone Humidity Input

11-28

11.7.11 The Effect of Enabling Dehumidification

11-28

 

 

11.7.11.1 MultiFlex RTUs and RCBs

11-28

 

 

11.7.11.2

AHUs

11-28

11.7.12

Optimum Start/Stop (OSS)

11-28

11.7.13 Losing Contact With Zone Applications

11-29

11.7.14

Stand-Alone MultiFlex RTUs

11-29

11.7.15 MultiFlex RTU/ARTC and AHU Zone Association

11-29

11.8

MULTIFLEX CUB BOARD

11-30

11.9

MULTIFLEX PAK BOARD

11-30

11.10

LIGHTING SCHEDULES

11-30

11.10.1

Overview

11-30

11.10.2 Functions of the Lighting Schedule Application

11-31

11.10.3

Control Method Select

11-31

11.10.4

Standard Control

11-31

 

 

11.10.4.1 The Light Level Interface Cell (LLEV INTERFACE)

11-31

 

 

11.10.4.2 The Schedule Interface Cell (SCHEDIF)

11-32

11.10.5

Alternate Control

11-32

 

 

11.10.5.1

Multi-Logic Combiner

11-32

 

 

11.10.5.2

Offset Solar Control

11-33

11.10.6 The Basic Schedule Cell

11-33

 

 

11.10.6.1

Slave Scheduling

11-33

11.10.7 The Min ON/OFF Cell

11-33

11.10.8

The Proof Cell

11-33

11.10.9

Output Light Dimming

11-34

11.11

DEMAND CONTROL

11-34

11.11.1 Introduction to Demand Limit Control

11-34

11.11.2

Demand Monitoring

11-34

11.11.3

Load Shedding

11-35

 

 

11.11.3.1

Definition

11-35

11.11.4

Shedding Levels

11-35

11.11.5

Priority Levels

11-35

11.11.6 How Demand Control Uses Load Shedding

11-37

 

 

11.11.6.1

Power Monitoring Input

11-38

11.12

SENSOR CONTROL

11-38

11.12.1

Overview

11-38

11.12.2

Analog Sensor Control

11-38

11.12.3 Cut In/Cut Out Setpoint Control

11-38

11.12.4

Digital Sensor Control

11-38

11.12.5

Logical Combination

11-39

11.13

LOOP/SEQUENCE CONTROL

11-39

11.13.1 Layout of the Loop/Sequence Control Application

11-39

 

 

11.13.1.1

Control Cells

11-39

 

 

11.13.1.2

Output Cells

11-40

xii • Table of Contents

026-1610 Rev 13 14-SEP-2011

Image 12
Contents BX HVAC, and CX Convenience Store Controllers Rev 13 14-SEP-2011Page FCC Compliance Notice Page Table of Contents E2 Hardware Setup Serial Configuration E2 Ethernet Peer Communications Quick Start Software Overview Logging Groups Multiflex CUB Board Holiday Schedules OPERATOR’S Guide to Using the E2 LOW Battery Notification Page Introduction E2 Refrigeration ControllerE2 Building Con- troller MrldsE2 Convenience Store Controller Networking Overview 1 E2 I/O NetworkNetwork Able for the RS485 NetworkDocumentation Over View Interconnection With Other E2sOn-Line Help System Overview Software Licensing Hardware Overview E2 Hardware1 E2 Main Processor Board 3 E2 Keypad LEDsPIB LEDs Status I/O Network Boards and Peripherals Gateway BoardMain Board Status CPU LEDs Keyboard StatusMultiFlex Boards MultiFlex 16 Input BoardGateway Model Model Name DescriptionMultiFlex Combination Input/ Output Boards Model Description NameE2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 MultiFlex CUB MultiFlex RTU BX and CX OnlyMultiFlex Rooftop Control Board RCB BX and CX Only MultiFlex PAK BoardMultiFlex ESR Board Hand-held Terminal P/N8RO and 8ROSMT Relay Boards 10- Hand-held Terminal6 4AO Analog Output Board 13- 4AO Analog Output Board P/N16AIe Dis 8ROe DisESR8 Dis 20- Case Controller CC-100P shown6 TD3 Temperature Display Facility Status Display FSDPage Mounting Mounting the E2Standard Mount Recessed MountRetrofit Mounting Standard Mount Inside Rear of EnclosureMounting I/O Boards Blank FaceSingle/Double Enclosures Echelon Devices Boards Without Enclosures Snap Track1 16AIe and 8ROe 3 ESR8 Dis MultiFlex ESR5 TD3 Two-Channel and Four- Channel Repeaters Internal ModemMounting Repeaters Overview Mounting the Two-Channel RepeaterInside Temperature Sensor Sensors and Transduc ErsPressure Transducers Outside Temperature Sen Sor Insertion Temperature ProbeSupply and Return Air Sen Sors Product Temperature Probes Humidity Sensors and HumidistatsMounting Bullet and Pipe Mount Sensors Indoor RH SensorOutdoor RH Sensors Duct-mounted Insertion RH ProbeOutdoor RH sensor P/N Dewpoint Probe Light Level SensorLiquid Level Sensors Refrigerant Leak DetectorsPage E2 Hardware Setup Setting up the E2Enclosure Main Processor BoardPowering the E2 Add-On E2 Peripherals Echelon Card Plug-In P/N 537-4860with mounting screw P/NPlug-In Digital I/O Network Card P/N Modem P/N DescriptionBattery Testing and Replacement 5 E2 RS485 Port Card P/N 537-4890Plug-In Four-Channel Inter- nal Repeater LEDsLow Battery Notification Battery Enable SwitchBattery Test Battery Replacement Qual- ified Technicians OnlyEchelon Earth Page Serial Configura- tion Serial Device and Soft Ware SetupOverview COM PortsE2 COM# Associations Connector RS485 Network and Hardware Setup I/O Network1 I/O Board Names and Termi Nology BoardWiring Types MultiFlex-Plus + BoardI/O Network Structure Daisy Chains Network Noise Minimiza TionSetting the Baud Rate Network ID Numbers Board NumbersSetting the Terminating and Biasing Jumpers Powering the I/O BoardsBoard Installation Wiring TypesIMC/Prodigy Rooftop Unit Controllers Copeland Discus with Core- Sense Diagnostics ISD Control Techniques Drive3 XR35CX, XR75CX, XEV22 Case Controllers 3.1 XR75CX-Case DisplayIPro DAC Energy MeterOverview Supported System TypesAdvisory and Alarms Diagnostic Alarm Descriptions E2 AdvisoryCopeland Discus with Core- Sense Protection Light Commercial Thermo StatComfort Alert Codes Comfort Alert Descriptions Cause E2 AdvisoryHigh/Low Occ/Unocc Space Temperature Alarms Supply Sensor Fail AlarmConditions for Return to Normal RTN on Diag- nostic Codes Diagnostic Alarms Diagnostic Alarm DescriptionsRefrigerant Leak Detection System Rlds Copeland Scroll K5 Refrig- eration CompressorXM Series of Case Control Lers 11.1 XM67011.2 XM679 11.3 XM678RS485 Network and Hardware Setup 6 14 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 NET 16 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 120/208/240 VAC 16AI Installation Guide MultiFlex ESR Installation Guide XEV22D Driver to E2 Installation Guide XR35CX, XR75CX to E2 Installation Guide Page Ethernet IP Configura Tions Equipment Specifications TypeE2 Ethernet Peer Communications Hardware Specifica TionsSoftware Specifica Tions Ethernet Network LayoutsClosed Network Layout Software Setup Open Network LayoutTroubleshooting 5Peer Network Tab Set Group NameEchelon Network and Hardware Setup Wiring TypeCable Type Retail Solutions Part Number Loop ResistanceDevice Termination Maximum Number of Eche- lon DevicesWire Restrictions Installing Echelon DevicesPowering Echelon Devices Maximum Total Segment LengthConfiguring Echelon Devices LEDsOpen Echelon Device Connectivity Troubleshooting Connected I/O Screen E2 firmware versions 2.81 and aboveE2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 One pin when unterminating an E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 All Analog Temperature Sensors and Air Flow Sensors MultiFlex Boards16AI Boards 8IO and Artc BoardsPower Connection Sensor Input Type Wiring Dip Switch DownWall-mounted Down 207-1000 Refrigerant Sensor Input Type MA output to input board20mA, Up for PulseApplication AssociationSensor Type Description Pulse onSetting Up Digital Inputs 8RO, 8ROe, 8IO, and MultiFlex Outputs SetOld 8ROs New 8ROs and 8RO-FCsSetting Up Digital Outputs Setting Up Analog Outputs Temperature and Digital Sensors ConnectionAuxiliary Analog Input Hand-Held Terminal Jack335-3263 Pulse Valve 335-3260 Generic Stepper and Emerson Flow Controls ESV ValvePin Page Cleaning Out the Con- troller Performing a Clean OutQuick Start Logging OnSetting Number of Network Devices Boards on the I/O NetworkUnit Controllers Echelon Setting Number of Applications Customizing the Home ScreenCommon Screen Ele- ments HeaderFunction Keys Help LineScreen Types Status ScreensMain Menu Actions Menu Key Function forActions Menu Item Description Setup Screens System Configuration MenuMenu Option Description System Information Menu 13- System Information MenuTime/Date Setup Setting the Time and DateSet Up Modem Set Up TCP/IP 17- TCP/IP AddressingSet Up Network Baud Rates 10.11.1 COM1 Serial RS232 Baud Rate10.11.2 I/O Network Baud Rate Set Up User Access LevelChanging Required User Access Levels Creating a New User AccountDeleting a User Set Up I/O Network Specify Number of BoardsSet Up Echelon Net Work Checking Online StatusSpecifying Number Devices Service Button Method Commissioning a DeviceHow Echelon Commissioning Works Modbus CommissioningCC-100’s Service Button TD3’s Service ButtonESR8’s Service Button Commissioning the EC-2License Management Manual ID Entry MethodWeb Services 33- TCP/IP Screen Locating the Mac AddressSet Up Alarming 37- Alarm Setup MenuSpecifying Alarm Reporting Types Setting up an E2 to be an Alarm AnnunciatorAlarm Dial-Out Introduction Alarm Report IngSet Up Global Data Priority SettingsSet Up Applications Example Setting Up an Outdoor Temperature Sen- sorUsing and Configuring a Setup Screen 10.18.1 Add/Delete an ApplicationAdd an Application Delete an ApplicationNavigating the Setup Screen Edit MenuEntering Setpoints Function Keys For Setup Index TabsHelp Line Using the Help Key to get Property Help Page Software Overview Suction GroupsIntroduction Standard Suction Group ApplicationLearning Mode Hardware OverviewCircuit Load Analysis Control/Cycles ParameterTemperature Differential Strat Egy Input Sensor Type Wiring InstructionsCondenser Control Air Cooled CondensersCondenser Split Mode Fast RecoveryEvaporative Condensers Fan ControlStandard Circuits Refrigeration ControlDefrost Control Clean and Door Switches TD3 Temperature Display WiringControl Link CD Case Display Typical Case in a Standard Circuit Case Control Circuits OverviewCase Circuit Control Soft- ware Overview Valve Control EEVs Liquid Pulse and Liquid StepperEEPRs Suction Stepper Thermostatic Expansion Valves TXVsOff Cycle Timed Temperature Termination Anti-Sweat ControlDemand Defrost Wait StateClean/Wash Mode Dual Temp ControlLight Control Dewpoint Input SourcesFail-Safe Mode Recoverable Sensor FailuresWalk-In Freezer Control Setting Up An Individual Case Controller Logging GroupsPossible Data Errors Data CompressionBase Log Group ClippingSetting Up Logging Logging Setup MenuLogging Group Status Screen Log ReportsLogging Group Report Application Log ReportSystem Log Report Temperature Control Air Handling UnitsAlternate Setpoints Single-Speed FansEconomization Enable Economizer ControlTwo-Speed Fans Variable-Speed FansDigital Economizer Control Analog Economizer ControlDehumidification Control CurtailmentInputs Sensor Type Wiring Instructions Separate SetpointsAHU Zone Control Intelligent Pre-Starts and Pre-StopsZone Control SectionTion How Zones Work Applications That May Be Connected To ZonesMultiFlex RTU Board MultiFlex RCB BoardZone Temperature Economization EnableEffect of Enabling Econ- omization Zone Humidity InputEffect of Enabling Dehu- midification MultiFlex RTUs and RCBsLosing Contact With Zone Applications Stand-Alone MultiFlex RTUsMultiFlex RTU/ARTC and AHU Zone Association MultiFlex CUB Board MultiFlex PAK BoardLighting Schedules Functions of the Lighting Schedule Application Control Method SelectStandard Control Light Level Interface CellAlternate Control Schedule Interface CellMulti-Logic Combiner Basic Schedule Cell Min ON/OFF CellProof Cell Offset Solar ControlDemand Control Output Light DimmingIntroduction to Demand Limit Control Demand MonitoringLoad Shedding Shedding LevelsPriority Levels DefinitionRotational Shed Last ShedOther Notes About Priority Levels Mode 1 KW Input Is Greater Than Setpoint Mode 3 Integral Error Approaching ZeroHow Demand Control Uses Load Shedding Power Monitoring Input Sensor ControlAnalog Sensor Control Cut In/Cut Out Setpoint Con TrolLoop/Sequence Con Trol Logical CombinationControl Cells Diagram Loop/Sequence Control Cell DescriptionsOutput Cells Select CellOutput Cell Descriptions Time Scheduling and Holidays How Schedules WorkEvents Absolute and Relative EventsPower Monitoring Holiday SchedulesOverlapping RangesLogging HourlyDaily MonthlyAnti-Sweat Setup Heat/Cool ControlHow Anti-Sweat Works Unoccupied HysteresisSetpoint Reset StopsAnalog and Digital Combiners Lead/LagTemperature Differential TD Strategy ConfigurationTD Control TD Control Fail-SafesAlarms Pulse AccumulationInputs OutputsAccumulator Reset Types Irrigation ControlHigh Trip Zones and CyclesCycle Scheduling Zone InhibitZone Bypass Inputs Service Modes Flow Sensor-Related TestsHeat Cut In/Cut Out Set- points For Each Stage Cool Cut In/Cut Out Set- points For Each StageFlexible Combiner Modular Chiller Con- trol MCCLearning Mode Control/Cycles Parame TerCompressor Control Boiler Bypass Valve ControlDigital Scroll Compressor Variable Frequency Drive Com PressorRMS Asset RMS ScaleLog Information Device ConstraintsLogged Changes Unlogged ChangesPage Operator’s Guide to Using the E2 E2 Home ScreenBX Home Screen RX Home Screen Logging On and Access Levels CX Home ScreenSystem Configuration Menu Toggling Full OptionsNavigation MenusSystem Information Menu Actions MenuSetup Screens Screen TypesStatus Screens Summary ScreensE2 Keypad Index TabsHeader Icons CursorTab Key Enter KeyKeypad Log In/Out Key Four Directional Arrow KeysUp/Page Down Keys Ctrl Page Up/Ctrl Page Down KeysManual Defrost and Clean Mode Customizing the Home ScreenKeys Function EditList menu and choose End Manual Mode OverridesChecking Boards Online Checking Status ScreensAlarms Accessing the Alarm Advi Sory LogViewing the Controller Advi Sory Log Date and Time12.10.5 Ack/Reset State Area Ctrl Application Prop ErtyAdvisory Message AcknowledgingResetting ClearingFacility Status Display FSD Alarms Viewing Logs and GraphsLocating Logged Inputs Outputs Home/Status ScreensSetup Screens Setting Up Input and Output PointersLog View Zooming In and OutLow Battery Notifica Tion Appendix a Case Type Defaults High Alarm, Low Alarm, and DelayDefrost Type Hdbx Eclipse Transducers Voltage Pressure PSI 100 lb 200 lb 500 lb XducerPage Appendix C Alarm Advisory Messages Alarm Name Default Definition PriorityE2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 Appendix C Alarm Advisory Messages C-3 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-5 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-7 Alarm Name Default Definition Priority Appendix C Alarm Advisory Messages C-9 10 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 Appendix C Alarm Advisory Messages C-11 12 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 RAM 14 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 Proportional P Mode Appendix D PID ControlThrottling Range Integral Mode Why I Mode is NecessaryProportional Constant Kp Throttling Range on page D-1Derivative Mode I Mode CalculationSaturation D Mode Calculation How Condenser Control Hvac PID Differs From OthersOutput at Setpoint Output at Setpoint for Non-CondenserOther PID Features Changing the Output at SetpointOutput at Minimum / Output at Max- imum Output at Setpoint for Condenser/HVAC PID ControlMinimum Accumulated Error FilteringPage Page Medium Resolution Reuccf Page Page Appendix F Troubleshooting Refer to .1.9, PoweringEchelon Network Appendix F Troubleshooting F-3 Symptom Possible Problem Solution Number of Fans field? TripSymptom Possible Problem Solution Appendix F Troubleshooting F-7 Figured as an analog input Page Page Appendix G Revision Log Page Index NumericsLow 4-6,12-18 CS-100.See Case Controllers, CS-100 Demand Defrost. See Defrost, demand Hot Gas Defrost. See Defrost, hot gas Jumpers PAK 2-7,11-30 Pmac Hansen probe. See Sensors, liquid level 10 E2 RX/BX/CX I&O Manual Rev 13 14-SEP-2011 E2 4-2RS485 jumpers
Related manuals
Manual 283 pages 10.27 Kb