7-2. Air conditioner does not operate.
7-2-1. Circuit breaker trips (or fuse blows).
A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.)
●There is a possibility of ground fault.
●Check insulation resistance.
If resistance value is 2MΩ or less, insulation is defective (“NO”).
Window type air conditioner
Power plug
1
Wall outlet (Receptacle)
Circuit breaker
Ground
Power supply
WARNING
*Set circuit breaker to OFF.
1Pull the power plug out of the wall outlet.
•Measure insulation resistance of unit.
NO
Insulation of unit is defective.
•Measure insulation resistance of electrical parts.
(Example)
Compressor, Fan motor, Capacitor, Relay etc.
NOTE
1.If any poorly insulated part is found, exclude that part from circuit with other parts properly connected, and then measure insulation resistance of entire air conditioner again to locate defective part.
2.Replace defective part with new one.
29