Heat Pump Model
Model STB0823H1
■Cooling
●Once the compressor stops, it will not start running again for about 3 minutes.
●Thermo. ON : When the room temperature rises above T + 1°F (T°F is set temperature). Compressor ➞ ON
●Thermo. OFF : When the room temperature falls below set temperature T°F. Compressor ➞ OFF
|
| Room temp. |
|
|
| T+1°F |
|
|
|
set temp. | T °F |
|
|
|
|
| 3 minutes |
| 3 minutes |
Compressor | or more | ON | ||
ON | ON | |||
|
| OFF |
| OFF |
■Heating (Except during defrosting operation)
●Once the compressor stops, it will not start running again for about 3 minutes.
●Thermo. ON : When the room temperature falls below T°F (T°F is set temperature). Compressor ➞ ON
●Thermo. OFF : When the room temperature rises above T + 1°F.
Compressor ➞ OFF
●Changeover to Heater ON : When the room temperature falls below T – 4°F, the unit turns off heat pump operation and electric heater comes on instead of compressor.
●Changeover to Heat pump : When the room temperature rises above T – 3°F, the unit resumes heat pump operation and compressor comes on instead of electric heater.
Room temp.
| T+1 | °F |
set temp. | T | °F |
|
|
| 3 minutes |
| 3 minutes |
| 3 minutes |
|
|
|
|
| or more |
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
Compressor | OFF | ON | OFF | ON | OFF | ON | OFF | ON | OFF |
|
|
|
|
|
Heater
OFF
ON
OFF
ON
OFF
ON
OFF