5-2. Heating Capacity (Heat pump Performance)
Model STB0823H1
Fan speed : High
Heating capacity ratio (%)
NOTE
120
110
100
90
80
70
60
50
40
30
20
10
0
17 | 20 | 30 | 40 | 47 | 50 | 60 |
Outdoor ambient temperature (°F DB)
1) ● … Point of rating condition
Black dot in the chart indicates the following rating condition.
Indoor: 70°F (21.1°C) D.B.
Outdoor: 47°F (8.3°C) D.B. / 43°F (6.1°C) W.B.
2)Above characteristics indicates heat pump heating operation, which does not include elctric heater operation.
3)Because this air conditioner heats a room by drawing in the heat of the outside
air (heat pump system), the heating efficiency will fall off when the outdoor temperature is very low, which consequently makes the room temperature decrease. At this time, heat is provided by the electric heater instead of heat pump. See page 44 for detail.