Fluke Rev. 4 user manual Adjusting the Transmitter

Page 76

701/702

Users Manual

value is shown in the top left of the measure window.

15.The calibrator moves on to the remaining set of points. For temperature and electrical parameter calibration, the points are done automatically. If you are sourcing pressure, the calibrator pauses at each step for you to adjust the pressure source. When the tests are complete, an error summary table, such as the following is displayed.

failures were outside the ±0.5% tolerance that we selected.

17.Either press the Done softkey to save the data, or the Abort softkey to delete the data and start over. You have to go back to As Found to restart the calibration. You can see the saved data entry and recall the table for later viewing through the Review Memory softkey during normal operation. With Model 702 you can upload this data to a PC using PMLink software. See the PMLink Manual for instructions.

16.In the results summary test, failures are highlighted. An adjustment is required in this example because three tests show failures. The

Adjusting the Transmitter

Proceed as follows to make the calibration adjustments to the transmitter. (Always refer to the transmitter manufacturer’s instructions to locate the adjustment controls and connection points for your transmitter).

1.Press the Done softkey while viewing the results summary.

2.Press the Adjust softkey. The calibrator sources 0% of span (100°C in this example) and displays the following softkeys:

66

Image 76
Contents 701/702 Page Table of Contents 701/702 Iii 100 List of Tables 701/702 List of Figures 103 Documenting Process Calibrator Introduction701/702 Measure FunctionSource Standard Equipment Standard Equipment Users ManualMail-in Card Documenting Process Calibrator Accessories PMLink Software Safety Information CATSafety Information Feature Getting Acquainted with YourCalibrator Input and Output JacksGetting Acquainted with Your Calibrator Keys KeysKey Functions Key Numeric keypad Using the Strap and Bail Setting Up the CalibratorDisplay Elements of a Typical Display Installing the Strap and Using the Bail Charging the Battery Battery Life Removing the Battery and Using the ChargerBacklight OFF Operating ModesBacklight on Automatically Saving Battery Life Using the Optional Battery EliminatorSetting Up the Date and Time Display Adjusting the Display ContrastSelecting the Display Language Using the Backlight Personalizing the Calibrator Using Measure Mode Measurement RangesMeasuring Electrical Parameters Electrical Measurement Connections Testing Continuity Measuring PressureDocumenting Process Calibrator Connections for Measuring Pressure Measuring Temperature Using ThermocouplesType Positive Lead MaterialPositive Lead Color ANSI* IEC Negative Lead MaterialMeasuring Temperature with a Thermocouple RTD Type ICE Point R0 Material Range CDocumenting Process Calibrator Wrong Measuring Temperature with an RTD Measurements in Percent of Scale Damping Your MeasurementsUsing Source Mode Sourcing Electrical ParametersElectrical Sourcing Connections Simulating a 4 to 20 mA Transmitter Connections for Simulating a 4 to 20 mA Transmitter Providing Loop Power Connections for Supplying Loop Power Sourcing Pressure 701/702 Connections for Sourcing Pressure Simulating Thermocouples Connections for Simulating a Thermocouple Simulating RTDs PS S +PS Z +IN Stepping and Ramping the Output Value Sourcing in Percent of ScaleStepping the Output Ramping the Output 701/702 Documenting Process Calibrator Checking a Relay Output Trip Alarm Simultaneous Measure/Source Measure Function Source Function 2W RTDSource Function Calibrating a Process Instrument Generating As Found Test DataCalibrating a Process Instrument 701/702 Documenting Process Calibrator Adjusting the Transmitter As Left Test Run Memory Operations Saving ResultsReviewing Memory Memory OperationsData Logging Model 702 Only Reading Rate MAX. Number Observing Min and Max Measurements Viewing the Task List Model 702 OnlyQuick Guide to Applications Clearing MemoryCalibrating a Chart Recorder Monitoring AC Line Voltage and Frequency Calibrating a Current-to-Pressure I/P Transducer Measuring the Output Current of a Transmitter Measuring a Precision Resistor Checking a Switch Calibrating a Pressure-to-Current P/I Transducer Calibrating a mV to Current Transmitter Checking a Vortex Shedding Flowmeter Maintenance Replacing the Battery PackInternal Lithium Backup Battery Cleaning the CalibratorReplacement Parts Service Center Calibration or RepairCalibration Data Maintenance Specifications Resolution DC Voltage MeasurementRange Model Reading +% of Full Scale YearFrequency Range AC Voltage MeasurementReading + Number of Counts Year Range Resolution Model Reading +% of Full Scale Range Resolution ModelDC Current Measurement Resistance MeasurementContinuity Testing Frequency MeasurementDC Voltage Output Range ResolutionsModel Output +% of Full Scale Output + % of Full Scale DC Current Output Output +% of Full Scale YearRanges Resolution Model Output + Ohms Year Resistance SourcingFrequency Sourcing Frequency RangesTypes C Temperature, ThermocouplesMeasure Degrees C Year Source Degrees C Temperture, Thermocouples Maximum Input Voltage 30 Temperature, Resistance Temperature Detectors Measure Degrees C Source Degrees C YearLoop Power Supply SettingTop and Bottom Limits of Ranges with Auto Range On RANGE, Current Source RANGE, Measure V CCRANGE, Frequency Measure General Specifications SafetyOperating Environment Specification 104 Index 701/702 Index