b) Connection to a Closed Loop System
•Condenser water supply inlet is 1/2" female pipe thread (FPT). A minimum of 3/8" OD copper tubing is recommended for the condenser water supply line.
•Condenser return outlet is 3/8" FPT. A minimum of 3/8" OD hard pipe is recommended for the condenser return line.
•
•The water supply to the condenser should not drop below 4 GPM.
•The pressure differential between the condenser water supply inlet and condenser return outlet must be no less than 10 PSIG.
•When using a glycol blend, the solution mixture should be less than 30% glycol.
•In order to maintain the proper high side pressure, the condenser water supply inlet temperature should not drop below 45°F (7°C) and the condenser return outlet temperature must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker installation is complete, confirm the condenser return outlet temperature 5 minutes after a freeze cycle starts. If the outlet temperature is not in the proper range, adjust the water‑regulating valve to bring it into range.
Icemaker Water
Supply Inlet
1/2" FPT
Condenser Water
Supply Inlet
1/2" FPT
Condenser
Return Outlet
3/8" FPT
Condensation
Drain Outlet
3/8" OD Stainless
Tube
Icemaker
Drain Outlet
3/4" FPT
Icemaker
Bin
Icemaker Water Supply
Line
Condenser Water Supply Line
Condenser Return Line
Icemaker Water Supply Line Drain Valve
Condenser Water Supply Line
Drain Valve
Separate piping to approved drain. Leave a
Bin Drain Outlet | ||
3/4" FPT | (5 cm) air | |
gap | ||
|
Condenser Return Line
Drain Valve
Fig. 13 |
| Floor | Drain |
|
| ||
| Connection to a Closed Loop System |
|
|
23