Hoshizaki KM-650MAH instruction manual Setup, Line Set

Page 15

3.Setup

1)Secure the legs to the remote condenser unit with the 8 bolts and nuts provided. See Fig. 5.

2)The legs have 8 mounting holes. Secure the legs with 8 bolts (not included).

Fig. 5

4. Line Set

Bolts with Split Lock Washer and Flat Washer

Nuts

CAUTION

The icemaker, line set, and remote condenser unit must contain the same type of refrigerant. Mixing of refrigerants will result in improper operation and possible damage to the refrigeration system.

Precharged factory line sets, available as optional equipment from Hoshizaki America, are recommended. For details, see "II.F.4.a) Factory Line Set Installation." Field fabricated line sets are allowed. For details, see "II.F.4.b) Field Fabricated Line Set Installation."

The maximum line length for the standard refrigerant charge is 66 feet. Should an installation require a longer line length, line sizes must be increased and additional refrigerant must be added. Instead of the standard 3/8" OD discharge line and 1/4" OD liquid line for this icemaker, increase the line sizes to 1/2" OD discharge line and 3/8" OD liquid line for the entire run. Add 16.5 oz. of R-404A to the system to compensate for the larger diameter line sizes, then add .4 oz. of R-404A for each foot over 66 feet to a maximum of 100 feet. Hoshizaki Technical Support is available at 1800-233-1940 for recommendations.

The maximum vertical distance between the remote condenser unit and the icemaker is 33 feet above or 10 feet below the icemaker. These distances are measured fitting to fitting.

a)Factory Line Set Installation

1)Route the factory line set (3/8" OD discharge line and 1/4" OD liquid line) from the remote condenser unit to the icemaker. Leave a service loop behind the icemaker to allow the icemaker to be pulled out for service. See Fig. 6. Factory fabricated line sets are precharged and do not need to be evacuated.

CAUTION

1.Ensure that there are no traps and no kinks in the line set.

2.Do not coil extra line set. If the line set is too long, recover the line set charge and store it in an approved container. Do not discharge the refrigerant into the atmosphere. Remove the extra line set length, braze the connections, then skip to step 4 in "II.F.4.b) Field Fabricated Line Set Installation."

15

Image 15
Contents KM-650MAH KM-650MWH KM-650MRH Hoshizaki AMERICA, INC Contents Important Safety Information KM-650MAH air-cooled Specifications Nameplate RatingMAX. Hacr Breakerusa only Amps KM-650MWH water-cooledKM-650MRH remote air-cooled KM-650MAH Dimensions / ConnectionsKM-650MWH KM-650MRH II. Installation and Operating Instructions Checks Before InstallationHow to Remove Panels See Fig Location SetupElectrical Connection For All ModelsAdditional Warnings for Remote Air-Cooled Model Installation of Remote Condenser Unit Checks Before InstallationLocation Line Set SetupField Fabricated Line Set Installation Ester Electrical Connection Stacking Remote Condenser Units See , 12, or Water Supply and Drain ConnectionsIcemaker KM-650MAH and KM-650MRHConnection to an Open Drain System Water-Cooled CondenserKM-650MWH Final Checklist Startup Cleaning and Sanitizing Instructions III. Cleaning and MaintenanceCleaning Procedure Sanitizing Procedure Following Cleaning Procedure Air Filters air-cooled model MaintenanceStainless Steel Exterior Storage Bin and ScoopPreparing the Icemaker for Long Storage Remove the water from the icemaker water supply lineDrain the water tank Page Hoshizaki AMERICA, INC