2. Condensing Unit
IMPORTANT
This condensing unit is intended for outdoor use. Normal operating ambient temperature should be within
The icemaker must be coupled with the appropriate condensing unit as listed below.
Icemaker | Hoshizaki Condensing Unit |
|
|
The condensing unit must be positioned in a permanent site under the following guidelines:
•A firm and flat site.
•A dry and well ventilated area with 24" (61 cm) clearance in both front and rear for proper air circulation and ease of maintenance and/or service should they be required. See Fig. 1.
•The maximum line length is 55 feet.
Note: If the recommended guidelines of the installation are exceeded, the icemaker performance may be reduced.
CAUTION
Failure to install the equipment within these guidelines may adversely affect performance, component life, and warranty coverage.
Minimum 24" (61 cm) Clearance
AirAir
Fig. 1
10