Hoshizaki KMD-901MAH Factory Line Set Installation, Field Fabricated Line Set Installation

Page 15

Factory Line Set Installation

1)Route the factory line set (1/2" OD discharge line and 3/8" OD liquid line) from the remote condenser unit to the icemaker. See Fig. 6. Factory fabricated line sets are precharged and do not need to be evacuated.

Note: Care should be taken that the icemaker, line set, and remote condenser unit contain the same type of refrigerant prior to making connections. Mixing of refrigerants will result in improper operation and possible damage to the refrigeration system.

2)Attach the refrigerant lines to the appropriate male couplings on the remote condenser unit first and then at the icemaker. Apply two drops of POE oil to the male threads of the couplings before tightening.

3)Tighten the couplings 1/4 turn beyond fully seated. A backup wrench is recommended.

Field Fabricated Line Set Installation

1)Route a 1/2" OD copper tubing discharge line and a 3/8" OD copper tubing liquid line between the remote condenser unit and the icemaker. See Fig. 6.

2)Insulate the two copper tubings separately.

3)Install Parker quick connect couplings on each end. OS-QUICK, a universal quick connect coupling kit available as optional equipment from HOSHIZAKI AMERICA, is recommended.

4)Evacuate through the charging ports on the Parker quick connect couplings and charge with R-404A refrigerant vapor to a pressure of 15 to 30 PSIG.

Note: Care should be taken that the icemaker, line set, and remote condenser unit contain the same type of refrigerant prior to making connections. Mixing of refrigerants will result in improper operation and possible damage to the refrigeration system.

5)Attach the refrigerant lines to the appropriate male couplings on the remote condenser unit first and then at the icemaker. Apply two drops of POE oil to the male threads of the couplings before tightening.

6)Tighten the couplings 1/4 turn beyond fully seated. A backup wrench is recommended.

 

Icemaker

 

 

 

 

 

Fan Motor Junction Box

Remote

(Fan Motor Leads Inside)

Condenser

 

Female Coupling

Unit

 

 

Louver Panel

 

 

 

Liquid Line

Junction Box (Fan

 

Discharge

3/8" OD

Motor Leads Inside)

 

1/2" OD

 

Line

 

Liquid Line

 

 

 

 

 

 

 

3/8" OD

Female Coupling

 

 

 

Discharge Line

 

 

Fig. 6

 

 

 

1/2" OD Pipe Insulation

 

 

 

15

Image 15
Contents KMD-901MAH KMD-901MWH KMD-901MRH Hoshizaki AMERICA, INC Contents KMD-901MAH air-cooled Specifications Nameplate RatingKMD-901MWH water-cooled KMD-901MRH remote air-cooled KMD-901MAH Dimensions / ConnectionsKMD-901MWH KMD-901MRH See Fig How to Remove PanelsLocation SetupElectrical Connection Electrical ConnectionInstallation of Remote Condenser Unit Checks Before InstallationLocation Line Set SetupField Fabricated Line Set Installation Factory Line Set InstallationStacking Remote Condenser Unit Electrical ConnectionWater Supply and Drain Connections KMD-901MRH With Storage BinFinal Checklist Startup Cleaning and Sanitizing Instructions III. Cleaning and MaintenanceCleaning Procedure Sanitizing Procedure Following Cleaning Procedure Maintenance Stainless Steel ExteriorStorage Bin and Scoop Remove the water from the icemaker water supply line Preparing the Icemaker for Long StorageAir Filters air-cooled model only Condenser air-cooled and remote air-cooled models onlyDrain the water tank Hoshizaki AMERICA, INC