Hoshizaki KMD-901MRH Installation of Remote Condenser Unit, Checks Before Installation, Location

Page 13

F. Installation of Remote Condenser Unit

1.Checks Before Installation

1)Remove the shipping carton, tape, and packing material.

2)Check that the refrigerant lines do not rub or touch lines or other surfaces, and that the fan blade moves freely.

2.Location

IMPORTANT

The remote condenser unit is intended for outdoor use. Normal operating ambient temperature should be within -20°F to +122°F (-29°C to +50°C). Operation of the remote condenser unit, for extended periods, outside of this normal temperature range may affect icemaker performance.

The remote condenser unit must be positioned in a permanent site under the following guidelines:

A firm and flat site.

A dry and well ventilated area with 24" (61 cm) clearance in both front and rear for ease of maintenance and service should they be required.

The maximum line length for the standard refrigerant charge is 66 feet. Should an installation require a longer line length, additional refrigerant must be added to the system. Add .4 oz. of R-404A for each foot over 66 feet to a maximum of 100 feet or call 1-800-233-1940 for recommendations.

The maximum vertical distance between the remote condenser unit and the icemaker is 33 feet above or 10 feet below the icemaker. These distances are measured fitting to fitting.

CAUTION

Failure to install the equipment within these guidelines may adversely affect performance, component life, and warranty coverage.

Min. 24" (61 cm) Clearance

AirAir

Locate

Legs

Fig. 4

13

Image 13
Contents KMD-901MAH KMD-901MWH KMD-901MRH Hoshizaki AMERICA, INC Contents KMD-901MAH air-cooled Specifications Nameplate RatingKMD-901MWH water-cooled KMD-901MRH remote air-cooled KMD-901MAH Dimensions / ConnectionsKMD-901MWH KMD-901MRH See Fig How to Remove PanelsLocation SetupElectrical Connection Electrical ConnectionChecks Before Installation Installation of Remote Condenser UnitLocation Line Set SetupField Fabricated Line Set Installation Factory Line Set InstallationStacking Remote Condenser Unit Electrical ConnectionWater Supply and Drain Connections KMD-901MRH With Storage BinFinal Checklist Startup Cleaning and Sanitizing Instructions III. Cleaning and MaintenanceCleaning Procedure Sanitizing Procedure Following Cleaning Procedure Stainless Steel Exterior MaintenanceStorage Bin and Scoop Air Filters air-cooled model only Preparing the Icemaker for Long StorageCondenser air-cooled and remote air-cooled models only Remove the water from the icemaker water supply lineDrain the water tank Hoshizaki AMERICA, INC