Hoshizaki F-80 I MWH (-c), F-80 I MAH (-c) service manual Problem, Possible Cause, Remedy

Page 36

 

PROBLEM

 

POSSIBLE CAUSE

 

REMEDY

[4]

Water has been

a)

Gear Motor Fuse

1.

Blown Fuse.

1.

See "3. [3]." Find out

 

supplied, Fan Motor

 

(BUSSMAN GMD

 

 

 

the cause and replace

 

starts, but Gear

 

1.5A)

 

 

 

the Fuse.

 

 

 

 

 

 

 

 

Motor and

 

 

 

 

 

 

 

b)

Thermal Protector

1.

Bad contacts.

1.

Check for continuity

 

Compressor will not

 

 

(Gear Motor)

 

 

 

and replace.

 

start.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[5]

Gear Motor and

a)

Pressure Switch

1.

Dirty Air Filter or

1.

Clean.

 

Compressor start

 

 

 

Condenser.

 

 

 

but operate

 

 

2.

Ambient or

2.

Get cooler.

 

intermittently.

 

 

 

 

 

 

condenser water

 

 

 

 

 

 

 

temperature too

 

 

 

 

 

 

 

warm.

 

 

 

 

 

 

3.

Condenser water

3.

Check and get

 

 

 

 

 

pressure too low or

 

recommended

 

 

 

 

 

off. (Water-cooled

 

pressure.

 

 

 

 

 

model only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.

Water Regulating

4.

Adjust it lower.

 

 

 

 

 

Valve set too high.

 

 

 

 

 

 

 

(Water-cooled model

 

 

 

 

 

 

 

only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.

Fan not rotating.

5.

See "3. [1] a) Fan

 

 

 

 

 

 

 

Motor."

 

 

 

 

6.

Refrigerant

6.

Recharge.

 

 

 

 

 

overcharged.

 

 

 

 

 

 

7.

Refrigerant line or

7.

Clean and replace

 

 

 

 

 

components

 

drier.

 

 

 

 

 

plugged.

 

 

 

 

 

 

8.

Bad contacts.

8.

Check for continuity

 

 

 

 

 

 

 

and replace.

 

 

 

 

9.

Loose connections.

9.

Tighten.

 

 

 

 

 

 

 

 

[6]

Gear Motor starts,

a)

X2 Relay on Control

1.

Bad contacts.

1.

Replace.Check for

 

but Compressor will

 

Timer

 

 

 

continuity and replace.

 

not start or operates

 

 

2.

Coil winding opened.

2.

Replace Timer.

 

intermittently.

b)

Starter

1.

Bad contacts.

1.

Check for continuity

 

 

 

 

 

 

 

and replace.

 

 

 

 

2.

Coil winding opened.

2.

Replace.

 

 

 

 

 

 

 

 

 

 

 

 

3.

Loose Connections.

3.

Tighten.

 

 

 

 

 

 

 

 

 

 

c)

Start Capacitor or

1.

Defective.

1.

Replace.

 

 

 

Run Capacitor

 

 

 

 

 

 

d)

Compressor

1.

Loose connections.

1.

Tighten.

 

 

 

 

 

 

 

 

 

 

 

 

2.

Motor winding

2.

Replace.

 

 

 

 

 

opened or grounded.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.

Motor Protector

3.

Find out the cause of

 

 

 

 

 

tripped.

 

overheat or

 

 

 

 

 

 

 

overcurrent.

 

 

e)

Power Supply

1.

Circuit Ampacity too

1.

Install a larger-sized

 

 

 

 

 

low.

 

conductor.

[7]

Gear Motor and

a)

Refrigerant Line

1.

Gas leaks.

1.

Check for leaks with a

 

Compressor start,

 

 

 

 

 

leak detector. Reweld

 

but no ice is

 

 

 

 

 

leak, replace drier and

 

 

 

 

 

 

charge with

 

produced.

 

 

 

 

 

 

 

 

 

 

 

refrigerant. The

 

 

 

 

 

 

 

 

 

 

 

 

 

 

amount of refrigerant

 

 

 

 

 

 

 

is marked on

 

 

 

 

 

 

 

Nameplate or Label.

 

 

 

 

2.

refrigerant line

2.

Replace the clogged

 

 

 

 

 

clogged.

 

component.

 

 

 

 

 

 

 

 

36

Image 36
Contents Number Issued Revised “A Superior Degree of Reliability”Modular Flaker Models F-801MAH-C F-801MWH-C HoshizakiHoshizaki America, IncPhone 1-800-233-1940 Technical Service 770 487-2331 Fax Complete and detailed explanation of the problemHOSHIZAKI AMERICA, INC 618 Highway 74 South Peachtree City, GA Attn HOSHIZAKI Technical Support DepartmentCONTENTS 5. Removal and Replacement of Expansion Valve 7. Removal and Replacement of Evaporator Assembly8. Removal and Replacement of Fan Motor 9. Removal and Replacement of Control Water ValveI. Specification 1. Icemaker F-801MAHF-801MWH F-801MAH-C F-801MWH-C II. General Information 1. Construction F-801MAH/-CF-801MWH/-C Water Supply Inlet Junction Box Water Regulator Compressor Drier2. Control Box Layout GEAR MOTORCONTROL TIMER FLUSHRUN CAPACITOR III. Technical Information 1. Water Circuit and Refrigeration Circuit F-801MWH/-C 2. Wiring Diagrams F-801MAH/-C, F-801MWH/-C3. Sequence of Electrical Circuit b When reservoir has been filled, gear motor starts immediately c Compressor starts about 60 sec. after gear motor starts Page e Low water except water-cooled model Page Page h When flush timer operates for 15 min. every 12 hours Page Page 4. Timing Chart Miswiring. Circuit Protect Relay operatesProper wiring. The unit starts 150 sec 1 sec60 sec 1. CIRCUIT PROTECT RELAY 2. WATER LEVEL UPPER 3. FLOAT SWITCH LOWER 5. Performance Data WATER FLOW FOR CONDENSER F-801MAH-C F-801MWH-C IV. Adjustment of Components 1. Adjustment of Water Regulating Valve water-cooled model only2. Adjustment of Flake Size V. Service Diagnosis 1. No Ice Production PROBLEMPOSSIBLE CAUSE REMEDYPROBLEM PROBLEM 2. Low Ice ProductionPOSSIBLE CAUSE REMEDY3. Other VI. Removal and Replacement of Components 1. Service for Refrigerant Linesa Refrigerant Recovery b Evacuation and Recharge R-404A2. Brazing DANGER 3. Removal and Replacement of Compressor 4. Removal and Replacement of Drier 5. Removal and Replacement of Expansion Valve Page 7. Removal and Replacement of Evaporator Assembly CutterExtruding Head AugerBearing-Lower and Mechanical Seal Gear Motor27 When replacing the evaporator c Check for leaks using nitrogen gas 140 PSIG and soap bubbles28 Move the flush switch to the ICE position 30 Turn on the power supplyAuger Mechanical Seal O-ring Bearing Lower Bolt Washer Coupling - SplineRubber O-ring Nylon Ring Bolt Washer Cutter Extruding Head Washer Socket Head Cap Screw Evaporator Washer Socket Head Cap Screw Barrier8. Removal and Replacement of Fan Motor 9. Removal and Replacement of Control Water Valve10. Removal and Replacement of Flush Water Valve VII. Cleaning and Maintenance 1. Preparing the Icemaker for Long Storage2. Cleaning and Sanitizing Instructions a Cleaning Solutionb Cleaning Procedure c Sanitizing Solution d Sanitizing Procedure - Initiale Sanitizing Procedure - Final 18 Move the flush switch to the “ICE” position and run the icemaker 19 Turn off the power supply after 30 minutes21 Flush out any solution from the storage bin 22 Turn on the power supply and start the automatic icemaking process3. Maintenance 3 Air Filter air-cooled model only 4 Condenser except water-cooled model