SCCG50 & SCCP50
Service Manual
Controller
High
Voltage Evaporator
ConnectorThermistor
| Bin |
| Thermostat |
Comp | Water Sensor |
| |
Water | Bin Light |
| |
Hot Gas |
|
Fan |
|
Power |
|
Power Supply | Control Panel |
Connector | Ribbon |
The controller is located at the front of the unit, | Control Safeties: |
under the top panel. |
|
It is powered by a 12 volt transformer. It has 5 indicator lights:
•Compressor - Light is ON if compressor is powered
•Water - Light is ON if inlet water solenoid valve is powered
•Hot Gas - Light is ON when Hot Gas Valve is powered
•Fan - Light is ON when Fan motor is powered
•Power - Light is ON when power is connected to controller
No Water. If the Water Sensor cannot detect water, and the inlet water solenoid valve has been on for the maximum fill time, the controller will stop all action and wait 20 minutes to
Maximum Freeze Time. If the freeze cycle should extend to 60 minutes, the controller will automatically put the machine into a Harvest cycle.
Maximum Harvest Time. 6 minutes
Time between restarts. After the machine has operated and then turned off, the controller will not restart the machine for four minutes.
June 2008
Page 22