This ice machine use R-134a type refrigerant. There are specific rules for handling that refrigerant.

To check for system pressures, add a field supplied clamp-on type service valve as a temporary means of system access. After diagnosis and before final repair, replace the clamp-on type valve with valves that are brazed onto the process tubes of the system.

Use a low flow of dry nitrogen when brazing on the system.

Install a new filter drier when replacing a refrigeration component or after a refrigerant leak repair.

Evacuate the system to at least 300 microns and use a micron gauge to measure the evacuation level.

Weigh in the nameplate charge. The machine is critically charged and a partial ounce mis-charge will affect performance.

September 2009

Page 29

Image 29
Contents Introduction Table of ContentsSpecifications Cabinet Layout LEG Adjustment Places Drain Flexible TubingAir flow Filters and Treatment Installation OverviewWater Quality Door Panel Custom Panel Door CoveringDoor Panel Attachment Custom Panel Door swing change Installation NotesDrain Pump Model drain installation Installation Water & DrainGravity Drain Initial Start Up Installation check listElectrical & Start Up Side Views of Cubes Cube Size AdjustmentHarvest Time Adjustment Use Condenser cleaning How to clean the condenser and winterizeHow to remove scale from the ice making system Electrical Components System InformationOverall Water System Components Performance Information Refrigeration System Problem Likely Cause Probable Solution Service DiagnosisMakes excessive noise Removal and Repair Cube Size Thermostat Harvest TimerRemoval and Repair Cabinet Removal SCCG30 & SCCP30 Refrigeration Service