Vulcan-Hart Solid State Temperature Control Calibration SG4D/SG6D, Calibration Steps

Page 21

b.If incorrect, check temperature probe as outlined under Temperature Probe Test (SG4D/SG6D).

1)If temperature probe is functioning properly and the temperature controller failed the test in 8c above, replace the temperature control and check for calibration as outlined under Solid State Temperature Controller Calibration (SG4D/SG6D).

SOLID STATE TEMPERATURE

CONTROL CALIBRATION

(SG4D/SG6D)

Before attempting any calibration, see Section 8C of

SOLID STATE TEMPERATURE CONTROLLER TEST (SG4D/SG6D) on previous page.

Calibration Steps

1.Place a thermocouple in the geometric center of the oven cavity.

2.Set the ON/OFF/OVEN COOL switch to ON.

3.Set the temperature controller dial to 350°F. Set the power control to 100% (10).

4.Allow the oven temperature to stabilize (minimum three heating cycles).

5.Record the temperature at which the Heat lamp comes ON (heating starts) and goes OFF (heating stops). This is the control differential. Heat lamp OFF temp - Heat lamp ON temp = Control Differential.

6.The nominal control differential should be less than 20°F.

A.If the control differential is less than 20°F, the temperature control circuit is functioning properly. Proceed to step 7.

B.If the control differential is more than 20°F, check the temperature probe as outlined under Temperature Probe Test (SG4D/SG6D).

C.If the control differential is more than 20°F and the probe passes its' test parameters, then temperature controller is malfunctioning. Install a new temperature controller and run calibration steps again.

7.Calculate the average oven temperature by adding the actual minimum temperature to the actual maximum temperature and dividing by 2.

EXAMPLE:

Oven set to 350°F.

Actual minimum oven temperature = 335°F Control cuts on at 334°F

Actual maximum oven temperature = 347°F Control cuts off at 340°F

335 + 347 = 682

682/ 2 = 341 (the control is 9°F out of calibration) 340 - 334 = 6°F Control Differential

347 - 335 = 12°F Oven Temperature Differential

A.If the average oven temperature is within +/- 5°F from the dial setting, no calibration is necessary.

B.If the average oven temperature is not within +/- 5°F, calibration is recommended.

8.Loosen the set screw on the temperature controller and carefully remove the knob from the shaft, without rotating the shaft. This will expose the calibration adjustment control access hole in the front panel.

9.Monitor the internal oven temperature and determine at what temperature the control should cut on to give you the required minimum temperature (Example: 350-341=9; 334+9=341. 341°F is the temperature at which you would wish the controller to cut on).

10.After allowing the oven to operate through several cycles (minimum 3 cycles), monitor the temperature as it falls to the desired "cuts on" point. Using a small screw driver, adjust the calibration adjustment until the controller cuts on at the desired "cuts on" temperature.

11.The calibration control is adjusted clockwise in order to increase the set temperature and counter clockwise to decrease the set temperature.

12.The controller has only +/- 25°F of adjustment. 1/4 turn of the calibration adjustment represents approximately 20°F shift in calibration.

– 21 –

Image 21
Contents SG4 & SG6 Series Full Size GAS Convection Ovens VULCAN-HART Table of Contents Table of Contents General Component Location Removal and Replacement of PartsTop Front Cover Covers and PanelsBottom Front Cover Right Side PanelSG4D/SG6D SG4C/SG6C Control Panel ComponentsComponent Panel Components SG4C/SG6C Temperature Probe Shown Temperature ProbeGAS Burners GAS Solenoid Valve GAS OrificeSpark Igniter and Flame Sense Ignition Control ModuleBlower and Motor Oven Doors and Bearings Roller Latch Assembly Independent Doors Door Catch Roller Assembly Independent DoorsDoor Window Door Switch Lamp Assembly High Limit ThermostatInterior Lights Cooling FAN Fan Installation TipsService Procedures and Adjustments Solid State Temperature Controller Test SG4D/SG6DTest Steps Calibration Steps Solid State Temperature Control Calibration SG4D/SG6DTemp F Ohms Temperature Probe Test SG4D/SG6DOperation Setup Mode Computer Controller SG4C/SG6CProbe Test Solid State Relay Test Computer Control Calibration SG4C/SG6CGAS Pressure Adjustment Verification of Spark AT Ignitor Door Switch AdjustmentFlame Current Measurement Blower AdjustmentDoor Strike Adjustment Independent Doors Door AdjustmentDoor Catch Roller Adjustment Component Description Electrical OperationPlug, Socket and Components SG4D/SG6D Front ViewControl Panel Component Panel Front ViewPlug, Socket and Components SG4C/SG6C SG4D/SG6D with Solid State Temperature Controller Sequence of OperationsCook Cycle Cool Down Cycle Solid State Temperature Controller Timer CycleNormal Cook Cycle SG4C/SG6C with Computer ControllerPage Roast and Hold Cycle Temperature and Time Cycle Normal CookingWiring Diagrams 426574 Rev. C Thermostat SchematicsGAS Convection Oven SG4 with Watlow 734 Control Symptoms Possible Causes TroubleshootingSymptoms Possible Causes Computer Control Models only Symptom Possible CausesError Codes Probable Cause Solution Problem