ERROR CODES
CODE AND | PROBABLE CAUSE | SOLUTION | |
PROBLEM | |||
|
| ||
|
|
| |
Er01 - ROM check | Internal ROM malfunction | Cycle power. | |
sum error | |||
|
| ||
|
|
| |
Er02 - RAM check | Internal RAM malfunction | Cycle power. | |
sum error | |||
|
| ||
|
|
| |
Er03 - Ambient sensor | Ambient temperature is below 32°F | Check ambient temperature at the control. | |
error | |||
|
| ||
|
|
| |
Er04 - Configuration | Microprocessor malfunction | Cycle Power. | |
error | |||
|
| ||
|
|
| |
Ero5 - EEprom error | Power loss while storing data | Cycle Power. | |
|
|
| |
|
| · Check the InP1 setup parameter. Verify that | |
| · Incorrect sensor type | it matches the sensor. | |
Er06 - Zone 1 A/D | · Check sensor and connections for a | ||
· Measuring temperature outside | |||
under flow error | reversed or open sensor. If the condition | ||
the sensor range | |||
| causing the error is resolved, the error will | ||
|
| ||
|
| clear. | |
|
|
| |
|
| · Check the InP1 setup parameter. Verify that | |
|
| it matches the sensor. | |
Er07 - Zone 1 A/D | Open sensor | · Check sensor and connections for a | |
overflow error | reversed or open sensor. If the condition | ||
| |||
|
| causing the error is resolved, the error will | |
|
| clear. | |
|
|
| |
Er10 - Stack overflow |
| · Cycle Power. | |
Microprocessor malfunction | · Check sensor and connections for a | ||
error | |||
| reversed or open sensor. | ||
|
| ||
|
|
| |
|
| · Check the InP1 setup parameter. Verify that | |
Er11 - Open sensor | Open sensor | it matches the sensor. | |
error | · Check sensor and connections for a | ||
| |||
|
| reversed or open sensor. | |
|
|
| |
| · Incorrect sensor type | · Check the InP1 setup parameter. Verify that | |
| it matches the sensor. | ||
Er12 - Shorted sensor | · Measuring temperature outside | ||
· Check sensor and connections for a | |||
| the sensor range | ||
| reversed or open sensor. | ||
|
| ||
|
|
|
FORM 35626 Rev. A | – 44 – | PRINTED IN U.S.A. |