Delfield T20C, T40, T5, T24C, T14D manual Unit

Page 30

Delfield®

Unit

 

 

 

30.00

Condensing

 

 

 

35.00

 

 

 

 

 

 

48.00

 

36.00

 

Ambient Operating Limits: -20˚F to 120˚F

 

Remote

Note: The Delfield Blast

Chiller/Shock Freezer is wired independently of the remote

condensing unit. No interconnecting wiring is required between the blast chiller

 

 

and the condensing unit. All condensing units have units have crankcase heaters.

 

Condensing unit control systems are provided wired from the factory. Field

 

Connection is made by connecting supply power to the compressor contactor.

 

Outdoor condensing unit applications require the use of an optional UL listed hood,

 

delfield P/N CUHOOD, for protection from the elements. Water cooled units are not

 

recommended for outdoor installation.

 

 

Freezer

Interconnecting piping, curbs or other mounting methods and refrigerant are not

included. Installation must be made by a qualified refrigeration technician. Piping runs

Refrigerant

 

 

404A

 

of greater than 100 feet require consultaion with the factory.

 

 

 

T40

 

 

 

 

Delfield

Model#: T40CU

 

Chiller/Shock

 

 

 

6 HP Compressor

 

Compressor and Capacity

24,150 BTUH @ -32˚F, 90 amb, 102.2 Cond: 46,740BTUH

 

 

 

Compressor and wiring

 

 

@ -5˚, 90 amb110.3 Cond.

 

 

 

208/230V/60Hz/3Ph

 

 

 

 

 

 

Condensing Unit Wiring

Max Fuse Size: 60A

 

 

 

 

Max Circuit Ampacity:42.3A

 

 

High Pressure Switch

Set Point: 450 psig, 380 psig re-set

 

Control System

Low pressure switch

Set Point: 25psig, Range = 15in to 100psig

 

 

Oil Pressure Differential Switch

Sensotronic Oil Pressure Switch

 

Compressor Reliability

Crankcase Heater

65 watts

 

 

Condenser Capacity Control

Head Pressure Control Set at 84˚F, 185psig

Blast

 

Reciever Capacity

55.4lbs. @ 90% liquid refrigerant fill (37.5lbs. max

 

refrigerant charge)

 

 

 

 

 

 

 

 

Flow Control

Accumulator

500 Cubic Inch Capacity

 

 

 

 

Oil Separator

Yes

T40:

 

Oil Filter

 

Yes

Optional Outdoor Hood

Delfield

Model Number: CUHOOD

 

 

 

 

Shipping Weight

Condensing Unit

600 Lbs.

 

Outdoor Hood

100 Lbs.

 

 

27.00

48.00

Image 30
Contents T5, T14D, T20C, T24C, T40 Blast Chiller/Shock Freezers Advice to Ensure Efficient Appliance Operation Contents General DocumentationInstallation Description of the Control PanelAlarm Management Maintenance and CleaningAppliance Functions General Documentation Installation AvoidSafety and control systems Condensate drainage connectionAppliance disposal Pre-cooling Shut-down proceduresOperating tips Loading the applianceDescription of the Vertical Control Panel PUSH-BUTTONS Programming and operating instructions Soft Blast Chilling by Temperature pre-cooked, hot foods Bottom right of display FlashesSoft Timed Blast Chilling Hard Blast ChillingHard Blast Chilling by Temperature Hard Timed Blast ChillingBlast Freezing by Temperature Timed Blast Freezing LED 5BProgram Storage PUSH-BUTTON Appliance functionsAdditional Functions Recalling a Stored ProgramForced Ventilation Function ExamplePrinting OUT Stored Data PUSH-BUTTON Manual DefrostingAlarm Management Display/Led Temperature not reached in set time alarm ALL Blackout alarm ALLCompressor preventive maintenance alarm ALL Keyboard/membrane alarm ALLInformation on Alarms List of other operating faults not indicatedFault Cause Solution Maintenance and cleaning T5 Blast T14D Blast Chiller/Shock Freezer Blast Chiller/Shock Freezer Blast Chiller/Shock Freezer T40 Blast Chiller/Shock Freezer Btuh @ -32˚F, 90 amb, 104.4 Cond 27,500BTUH T20-24CUW Remote Water Cooled Condensing Unit Unit T40CUW Remote Water Cooled Condensing Unit T5/T14D refrigeration system schematic Wiring diagrams Page Page Page Page T40 Installation and Assembly T40 Installation and Assembly Hole for Probes Electrical Hole Refrigerant Line Holes T40 Installation and Assembly Page Page Thank you for choosing Delfield