Delfield T40, T20C, T5, T24C Information on Alarms, List of other operating faults not indicated

Page 21

INFORMATION ON ALARMS:

During alarms, the beeper is activated and the display shows the message “ALL xx”.

The alarm message is alternated on the display even when the beeper has been silenced, until the alarm has been cleared.

Alarm relays remain activated as long as the alarm is displayed.

In the case that more than one alarm has been activated, each one is alternately displayed.

When the beeper is activated, the operator can silence it by pressing the relative push-button, after which the alarm can be cleared, by pressing the beeper reset button again.

Power failures will not erase current alarms.

List of other operating faults not indicated:

FAULT

CAUSE

SOLUTION

Compressor does not operate

1 - Overload switch has cut in 1

- Seek assistance from a service technician

 

2

- Power failure

2

- Check connection to power lines

Fans do not rotate

1 - Power failure

1

- Check connection to power lines

 

2

- Fan fault

2

- Seek assistance from a service technician

 

 

 

 

to replace fan

 

3

- Condenser fault

3

- Seek assistance from a service technician

 

 

 

 

to replace condenser

 

4

- Protective fuse faulty

4

- Seek assistance from a service technician

 

 

 

 

to replace fuse

Electronic panel does

1 - Power failure

1

- Check connection to power lines not

 

 

 

 

switch on

 

2

- Protective fuses broken

2

- Seek assistance from a service technician

 

 

 

 

to replace fuses

Compressor operates but

1 - Shortage of refrigerant gas 1 - Seek assistance from a service

does not cool cell

 

 

 

technician

 

2

- Solenoid valve fault

2

- Seek assistance from a service technician

 

3

- Condenser is soiled

3

- Clean the condenser (see par. 4.2)

Image 21
Contents T5, T14D, T20C, T24C, T40 Blast Chiller/Shock Freezers Installation Contents General DocumentationAdvice to Ensure Efficient Appliance Operation Description of the Control PanelAlarm Management Maintenance and CleaningAppliance Functions General Documentation Avoid InstallationSafety and control systems Condensate drainage connectionAppliance disposal Operating tips Shut-down proceduresPre-cooling Loading the applianceDescription of the Vertical Control Panel PUSH-BUTTONS Programming and operating instructions Bottom right of display Flashes Soft Blast Chilling by Temperature pre-cooked, hot foodsHard Blast Chilling Soft Timed Blast ChillingHard Timed Blast Chilling Hard Blast Chilling by TemperatureBlast Freezing by Temperature LED 5B Timed Blast FreezingAdditional Functions Appliance functionsProgram Storage PUSH-BUTTON Recalling a Stored ProgramPrinting OUT Stored Data PUSH-BUTTON ExampleForced Ventilation Function Manual DefrostingAlarm Management Display/Led Compressor preventive maintenance alarm ALL Blackout alarm ALLTemperature not reached in set time alarm ALL Keyboard/membrane alarm ALLInformation on Alarms List of other operating faults not indicatedFault Cause Solution Maintenance and cleaning T5 Blast T14D Blast Chiller/Shock Freezer Blast Chiller/Shock Freezer Blast Chiller/Shock Freezer T40 Blast Chiller/Shock Freezer Btuh @ -32˚F, 90 amb, 104.4 Cond 27,500BTUH T20-24CUW Remote Water Cooled Condensing Unit Unit T40CUW Remote Water Cooled Condensing Unit T5/T14D refrigeration system schematic Wiring diagrams Page Page Page Page T40 Installation and Assembly T40 Installation and Assembly Hole for Probes Electrical Hole Refrigerant Line Holes T40 Installation and Assembly Page Page Thank you for choosing Delfield