Vermont Casting DVRSR, DVRSL Vertical Sidewall Installations, Vertical Sidewall Applications

Page 20

VERTICAL SIDEWALL INSTALLATIONS

Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.

The graph showing the relationship between vertical and horizontal side wall venting will help to determine the various vent lengths allowable. Fig. 45.

Minimum clearance between vent pipes and combustible materials is one (1") inch (25

mm)on top, bottom and sides unless otherwise noted.

When vent termination exits through foundation less than 20" below siding outcrop, the vent pipe must flush up with the siding. A 7DVSS must also be used.

It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.

The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace to the face of the outer wall.

Horizontal plane means no vertical rise exists on this portion of the vent assembly.

For some installations, it may be desirable to have some amount of the horizontal vent run immediately after the fireplace. A vertical rise must be used but can be located any- where in the vent system, to meet the perim- eters identified in the venting graph.

The maximum horizontal vent run is 20 feet (6100mm) when the vertical vent rise is 7.5 feet (2286mm). Fig. 41

 

MAXIMUM

 

 

20 ft. (6100mm)

 

 

48"

 

12"

(1220mm)

 

(305mm)

 

 

15 ft.

 

 

(4572mm)

 

90" (2286mm)

 

 

VERTICAL

 

 

DIMENSION

7TDVRT90

7.5 ft. MINIMUM

ELBOW

 

WHEN HORIZONTAL

 

 

 

RUN IS 20 ft.

 

 

 

SIDE VIEW

Fig. 41

 

 

VERTICAL SIDEWALL APPLICATIONS

The maximum number of 90 degree elbows per side wall installation is four (4), (includes 7TDVRT90 off back of unit)

The maximum number of 45 degree elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run.

When one 90o elbow is installed directly onto another off the back of the fireplace the maximum horizontal vent length is 36" (914mm). Fig. 42.

MAXIMUM 3' (914mm)

7TDVRT90

Fig. 42

SIDE VIEW

For each 45 degree elbow installed in the horizontal run (while maintaining a constant horizontal plane), the length of the horizontal run MUST be reduced by 18" (457mm). This does not apply if the 45 degree elbows are installed on the vertical part of the vent system.

If a 90 degree elbow is used in the horizontal vent run (level height maintained) the maxi- mum horizontal vent length is reduced by 36 inches. Fig. 43. This does not apply if the 90 degree elbows are used to increase or redi- rect a vertical rise.

Example: According to the vent chart the maximum horizontal vent length is 20 ft.when the vertical height is 7.5 ft. from fireplace base height. If one 90 degree elbow is required in the horizontal vent it must be reduced to 17 ft.

- 20 -

Image 20 Contents
DVRS3 Dvrsl Dvrsr Table of Contents Installation and Operating Instructions Locating Your Majestic GAS FireplaceMantels Fireplace DimensionsMantel Chart GAS Specifications Clearance to CombustiblesFraming and Finishing Final FinishingGAS Line Installation Remote Switch InstallationGeneral Venting Termination Clearances Rear Wall Installations Rear Venting ApplicationsVertical Sidewall Applications Maximum120 Vertical Sidewall Venting Graph HOW to USE the Vent GraphVertical Sidewall Installation SCREWS2 Below Grade Installations InstallationVertical Through Roof Applications Vertical Thru the Roof Installation DVR Series Crimped Venting Components General Information on Assembling Twist Lock Vent Pipes Vent Opening Combustible Wall Vertical Sidewall Installations Sidewall Venting Graph Vent Sidewall Installation Zero Clearance Sleeve if Required Firestop Two sets of 45 degree elbow offsets within these Vertical Through the Roof Installation DVR Series Twist Lock Venting Components Louvre Removal Front Glass Removal Side Glass RemovalGlass Cleaning Ceramic Refractory InstallationLava Rock Installation of LogsEmber Material Placement Lighting Instructions To Turn OFF GAS to FireplaceTrouble Shooting the GAS Control System SIT 820 Nova Millivolt ValveFlame Adjustment Flame CharacteristicsMaintenance Cleaning the Standing Pilot Control SystemReplacement Parts DVRS3 & Dvrsl / Dvrsr Replacement Parts List DVRS3/DVRSL/DVRSR DescriptionFAN KIT FK24 Remote ControlOptions