FUEL CONVERSION
“Warning” This conversion kit shall be installed by a qualified service technician in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a fire, explosion or CO poisoning may result. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper or complete until the operation of the converted appliance is checked as specified in the owner’s conversion kit.
Please read and follow these instructions. Also please read the instruction guide lines provided by S.I.T on how to remove and install the
STEP 1. Carefully inspect all parts supplied with this conversion kit.
STEP 2. Shut the gas off the main gas line to the appliance.
STEP 3. Open the door by undoing the three screws on the bottom of the door, pull door towards you then lift up and out. Remove the logs and the burner tray from the unit, this will expose the main burner orifices and the pilot assembly
STEP 4. Change the regulator on the front of the gas valve. (Follow the instructions provided by S.I.T)
STEP 5. To change the pilot orifice: First, remove the two (2)
(BE CAREFUL WHEN TIGHTENING THE PILOT FITTING, YOU COULD BREAK THE CERAMIC IGNITER ELECTRODE). STEP 6.
STEP 7. Remove the two (2) main burner orifices using a ½” deep socket
STEP 8. Install the two (2) new orifices supplied making sure that the orifices are in the correct location. Be sure to put a bead of pipe thread sealant or approved Teflon tape on the orifices before installing them into the burner assembly.
STEP 9. Reinstall the burner tray, log set and door.
STEP 10. Turn the gas line to the unit back on. Do a leak check using a soap and water solution or an approved manner on the gas supply line and the pilot tubing.
STEP 11.
STEP 12. MAKE SURE that the sticker provided by S.I.T is installed to signify that this valve has been converted to a different type of fuel. Also make sure that the rating plate has a conversion label provided, to show that this unit has been converted to a different fuel type.
A VISUAL CHECK OF THE REGULATOR KNOB IS NECESSARY TO DETERMINE WHETHER OR NOT THE REGULATOR IS THE CORRECT PART. A 50% TURN DOWN REGULATOR WILL HAVE ONLY ONE CORNER ON THE KNOB.
CONVERSION KIT PARTS LIST
1 50% turn down
2 Main orifices
1 Pilot assembly mounting gasket
NATURAL GAS | PROPANE |
Pilot Orifice. | .51 mm | .35 mm |
Burner Orifice. | Front #48 | Front #56 |
| Rear #50 | Rear #57 |
Venturi Settings | Front 1/16” | Front 1/4” |
| Rear 1/16” | Rear 1/4“ |