AEG PV.500-MH manual Sequence Control Parameters, Inverter stack switch-on time

Page 30

Protect PV.500-MH Operating Instructions

5.1.8Sequence Control Parameters

Switch-on conditions

Underfrequency, overfrequency, undervoltage, overvoltage:

The equipment will only switch from the "Waiting for feed condi- tions" status to the "Operation" status if the feed conditions are met. These conditions include the mains voltage and the mains frequency. These values must be within certain limits described by the switch-on conditions.

Voltage limit value for night detection, delay time for night detection:

If the DC voltage falls below the voltage limit value for longer than the delay time, the unit switches to the "Night" status.

Voltage limit value for day detection, delay time for day detection:

If the DC voltage rises above the voltage limit value for longer than the delay time, the equipment switches to the "Waiting for feed conditions" status.

Inverter stack switch-on time:

The time for which the inverter stack is switched on during a start- up attempt

Permissible voltage dip after switching on the stack:

Prior to the start-up attempt, a limit value is calculated from the present DC voltage and the permissible voltage dip.

If the start-up attempt causes the DC voltage to fall below this cal- culated limit value, this start-up attempt will fail.

Delay until the next start-up attempt following failure on ac- count of excess voltage dip:

After the failure of a start-up attempt, this delay must elapse before the next start-up attempt is made.

Power limit value for shutdown, delay time for shutdown:

If the power fed into the mains remains below the limit value for longer than the delay time, the unit switches to the "Waiting" sta- tus.

Standard delay for a renewed start-up attempt following shut- down,

offset delay added to the standard delay after shutdown, maximum number of times the offset delay can be added to the standard delay:

Variable delay in the "Waiting" status Chapter 5.1.4.

Minimum DC voltage,

fill factor (PV system parameter):

If the DC voltage rises above a value resulting from the minimum

DC voltage divided by the fill factor, a start-up attempt is made.

30 of 68

80000043212 BAL

Image 30
Contents Protect PV.500-MH Operating InstructionsAEG Power Solutions GmbH Table of Contents Monitoring Systems, Messages and Faults System FunctionInterfaces Graphical Display and Operation Unit General Information Information on How to Use these InstructionsWarranty ValidityObligations of the Equipment Operator Target GroupsExplanations of Target Groups HandlingSkilled Personnel Skills and Training Storing Instructions Obligations of skilled personnelExplanation of Symbols and Safety Instructions Explanation of SymbolsSymbol Meaning Hazard Symbols Used Safety InstructionsSignal Words Used Symbol Meaning for skilled personnelSigns Containing Orders for Personal Protective Equipment Emergency Procedure e.g. in the Event of a Fire Safety AwarenessAbbreviations Particular Dangers associated with Photovoltaic Systems Thin-film cellsLightning protection System stop switch Safety Signs and Warning Notices on the EquipmentSafety and Protection Devices for the Equipment Protective CoversLockable Equipment Doors GuardResidual Hazards Electrical Hazards Water in electrical equipment Risks Due to Moving PartsFire-Related Risks Risk of injury due to rotating fansRisks from Maintenance and Repair Work Risks due to Loss of ControlProduct Details Product DescriptionImportant information about equipment documenta- tion Appropriate Use Dimensions and ViewsSafety Inappropriate UseStandards, Directives and CE Mark NameplateTechnology Operating Elements System Description Individual OperationOFF Status System FunctionDescription of Sequence Control Waiting for Feed Conditions StatusOperation Status Waiting StatusSequence Control During the Course of the Day Fault StatusNight Status Early morningLater in the evening DayEvening NightPower limit value for shutdown, delay time for shutdown Inverter stack switch-on timePermissible voltage dip after switching on the stack Sequence Control ParametersDescription of Fan Control General Fan Control, Cabinet FanCabinet Fan Control Parameters Fan Control, Inverter Stack FanParameters of Inverter Stack Fan Control Igbt temperature limit value for switching off the fanIgbt temperature limit Insulation Monitoring and Earthing of PV Cells GeneralProtect PV.500-MH Operating Instructions General Maintenance modeOperation with Thin-Film Solar Cells Sequence controlInsulation Monitoring Parameters Delay for shutdown of K21 in night operationMinimum time in maintenance mode MPP TrackerMonitoring Systems, Messages and Faults Table of Faults Temperature monitoring systemsCan I/O monitoring systems Fault/Message Unit Monitoring Systems Fault/Message DC voltage monitoring systems Fault/Message Interfaces Communication InterfaceCommunication data port 2 Technical Data MultiCom CCC hardware data assembly A29.1Communication data port 1 Communication data port 3Connections Configuration jumpersStructure of the MultiCom CCC Interface ButtonDescription of serial interfaces Port 2 X5 RS485 pin assignment default Shield connection of the RS485 bus lineController Area Network can at ConfigurationPort 2 X5 RS232 pin assignment Port 3 X4 can pin assignmentConfiguration Preparations Setting the terminal programProtect PV.500MH Operating Instructions Configuring the Modbus Protocol Data protocol configurationConfiguring Modbus Data Transmission Modbus/JBus data transmission configurationStructure of the COM Server internally wired to A93 COM Server GeneralNetwork Connection Installation of the COM Server Network Integration Configuration Configuration of the Virtual COM PortRemote Signalling Technical dataStructure Following default signals are used for remote signalling Graphical Display and Operation Unit DOUKeyboard Operation SignallingAcoustic signal generator LEDsPossible symbol keys and their function Start-upMenu Structure Menu Tree Main MenuOperating Display Operating display Normal operationExamples of possible displays Example of operating displaySolar radiation is too low, the inverter is in standby mode Monthly data t = day 1 31 for the last 12 months Example of yearly overview Menu Status/Measured ValuesBlocking Menu Inverter exampleService Fault HistorySettings Information