Protect PV.500_MH Operating Instructions

The set monitoring values are regularly checked.

In this status, no power is fed into the mains.

Possible change of status:

If the DC voltage rises above a certain value for a certain time and the mains voltage and mains frequency are within a certain range, the unit switches to the "Operation" status. A start-up attempt is made, which involves switching on the inverter stack. If the DC voltage collapses too dramatically during this start-up attempt, the inverter stack is switched off again and there is a delay before at- tempting to start up again. The equipment will not switch to the "Operation" status until any dip in the DC voltage that occurs dur- ing a start-up attempt is within acceptable limits.

If the DC voltage falls below a certain value for a certain time, the equipment switches to the "Night" status.

If a deactivating or self-acknowledging fault is triggered, the equipment switches to the "Fault" status.

The status can be switched from "Waiting for feed conditions" to "OFF" using the "Off" control command.

5.1.3The "Operation" Status

The equipment has met all conditions for operation and no deac- tivating or self-acknowledging faults are present.

The set monitoring values are regularly checked.

In this status, power is fed into the mains and inverter output con- tactor K7 is closed.

Possible change of status:

If the generated power falls below a certain value for a certain time, the operating conditions are no longer met. The equipment then switches to the "Waiting" status.

If a deactivating or self-acknowledging fault is triggered, the equipment switches to the "Fault" status.

The status can be switched from "Operation" to "OFF" using the "Off" control command.

5.1.4The "Waiting" Status

If the power fed in falls below a certain value when the equipment is in "Operation", it switches to the "Waiting" status. Although the incoming power is low, the DC voltage of the PV cell could still be high enough and even stable enough to meet the feed conditions in the "Waiting for feed conditions" status. So that the inverter does not switch back on again immediately, thereby subjecting inverter output contactor K7 to unnecessary strain due to frequent switch- ing, after the "Operation" status the unit initially switches to the "Waiting" status. It remains in this status for a certain time, only switching to the "Waiting for feed conditions" status once this time has elapsed.

The set monitoring values are regularly checked.

Possible change of status:

Once the delay has elapsed, the unit switches to the "Waiting for feed conditions" status.

80000043212 BAL

27 of 68

Image 27
Contents Operating Instructions Protect PV.500-MHAEG Power Solutions GmbH Table of Contents Monitoring Systems, Messages and Faults System FunctionInterfaces Graphical Display and Operation Unit Validity Information on How to Use these InstructionsWarranty General InformationHandling Target GroupsExplanations of Target Groups Obligations of the Equipment OperatorSkilled Personnel Skills and Training Obligations of skilled personnel Storing InstructionsExplanation of Symbols and Safety Instructions Explanation of SymbolsSymbol Meaning Symbol Meaning for skilled personnel Safety InstructionsSignal Words Used Hazard Symbols UsedSigns Containing Orders for Personal Protective Equipment Emergency Procedure e.g. in the Event of a Fire Safety AwarenessAbbreviations Particular Dangers associated with Photovoltaic Systems Thin-film cellsLightning protection Protective Covers Safety Signs and Warning Notices on the EquipmentSafety and Protection Devices for the Equipment System stop switchLockable Equipment Doors GuardResidual Hazards Electrical Hazards Risk of injury due to rotating fans Risks Due to Moving PartsFire-Related Risks Water in electrical equipmentRisks due to Loss of Control Risks from Maintenance and Repair WorkProduct Details Product DescriptionImportant information about equipment documenta- tion Inappropriate Use Dimensions and ViewsSafety Appropriate UseNameplate Standards, Directives and CE MarkTechnology Operating Elements Individual Operation System DescriptionWaiting for Feed Conditions Status System FunctionDescription of Sequence Control OFF StatusWaiting Status Operation StatusEarly morning Fault StatusNight Status Sequence Control During the Course of the DayNight DayEvening Later in the eveningSequence Control Parameters Inverter stack switch-on timePermissible voltage dip after switching on the stack Power limit value for shutdown, delay time for shutdownFan Control, Cabinet Fan Description of Fan Control GeneralFan Control, Inverter Stack Fan Cabinet Fan Control ParametersInsulation Monitoring and Earthing of PV Cells General Igbt temperature limit value for switching off the fanIgbt temperature limit Parameters of Inverter Stack Fan ControlProtect PV.500-MH Operating Instructions Sequence control Maintenance modeOperation with Thin-Film Solar Cells GeneralMPP Tracker Delay for shutdown of K21 in night operationMinimum time in maintenance mode Insulation Monitoring ParametersMonitoring Systems, Messages and Faults Temperature monitoring systems Table of FaultsCan I/O monitoring systems Fault/Message Unit Monitoring Systems Fault/Message DC voltage monitoring systems Fault/Message Communication Interface InterfacesCommunication data port 3 Technical Data MultiCom CCC hardware data assembly A29.1Communication data port 1 Communication data port 2Button Configuration jumpersStructure of the MultiCom CCC Interface ConnectionsDescription of serial interfaces Shield connection of the RS485 bus line Port 2 X5 RS485 pin assignment defaultPort 3 X4 can pin assignment ConfigurationPort 2 X5 RS232 pin assignment Controller Area Network can atSetting the terminal program Configuration PreparationsProtect PV.500MH Operating Instructions Data protocol configuration Configuring the Modbus ProtocolModbus/JBus data transmission configuration Configuring Modbus Data TransmissionStructure of the COM Server internally wired to A93 COM Server GeneralNetwork Connection Installation of the COM Server Configuration of the Virtual COM Port Network Integration ConfigurationRemote Signalling Technical dataStructure Following default signals are used for remote signalling DOU Graphical Display and Operation UnitLEDs SignallingAcoustic signal generator Keyboard OperationStart-up Possible symbol keys and their functionMain Menu Menu Structure Menu TreeOperating display Normal operation Operating DisplayExample of operating display Examples of possible displaysSolar radiation is too low, the inverter is in standby mode Monthly data t = day 1 31 for the last 12 months Example of yearly overview Status/Measured Values MenuMenu Inverter example BlockingInformation Fault HistorySettings Service