Page 32

Protect PV.500-MH Operating Instructions

5.2.3Cabinet Fan Control Parameters

Unit exhaust air temperature limit value for switching on the fan:

If the highest exhaust air temperature rises above this limit value, the fans which were switched off are switched to the fast fan stage.

Unit exhaust air temperature limit value for switching off the fan:

If the highest exhaust air temperature falls below this limit value, the fans which were running in the slow fan stage are switched off.

Unit exhaust air temperature limit value for switching to the fast fan stage:

If the highest exhaust air temperature rises above this limit value, the fans which were running in the slow fan stage are switched to the fast fan stage.

Unit exhaust air temperature limit value for switching to the slow fan stage,

minimum time in the fast fan stage:

If the highest exhaust air temperature falls below this limit value, the fans which were running in the fast fan stage are switched to the slow fan stage if the minimum time in the fast fan stage has elapsed.

5.2.4Fan Control, Inverter Stack Fan

As soon as the equipment's control module is supplied with volt- age, fan control always starts with the maximum fan speed. This means that the control can be restarted to check whether the fan is working correctly. For example, after maintenance work, it is not necessary to wait for the fan to reach the temperature criterion to switch on the maximum fan speed.

The maximum fan speed is always active for at least a certain time. The IGBT temperatures are checked after this time. The fan speed is then determined using the highest of these temperatures. If the highest temperature from the two sensors is below a certain value, the fan is switched off completely.

If, when the fans are switched off, the highest temperature from the two sensors rises above a certain value, the fan is again oper- ated at the maximum speed for a certain time.

32 of 68

80000043212 BAL

Image 32
Contents Protect PV.500-MH Operating InstructionsAEG Power Solutions GmbH Table of Contents Interfaces Monitoring Systems, Messages and FaultsSystem Function Graphical Display and Operation Unit Information on How to Use these Instructions WarrantyGeneral Information ValidityTarget Groups Explanations of Target GroupsObligations of the Equipment Operator HandlingSkilled Personnel Skills and Training Storing Instructions Obligations of skilled personnelSymbol Meaning Explanation of Symbols and Safety InstructionsExplanation of Symbols Safety Instructions Signal Words UsedHazard Symbols Used Symbol Meaning for skilled personnelSigns Containing Orders for Personal Protective Equipment Abbreviations Emergency Procedure e.g. in the Event of a FireSafety Awareness Lightning protection Particular Dangers associated with Photovoltaic SystemsThin-film cells Safety Signs and Warning Notices on the Equipment Safety and Protection Devices for the EquipmentSystem stop switch Protective CoversResidual Hazards Lockable Equipment DoorsGuard Electrical Hazards Risks Due to Moving Parts Fire-Related RisksWater in electrical equipment Risk of injury due to rotating fansRisks from Maintenance and Repair Work Risks due to Loss of ControlImportant information about equipment documenta- tion Product DetailsProduct Description Dimensions and Views SafetyAppropriate Use Inappropriate UseStandards, Directives and CE Mark NameplateTechnology Operating Elements System Description Individual OperationSystem Function Description of Sequence ControlOFF Status Waiting for Feed Conditions StatusOperation Status Waiting StatusFault Status Night StatusSequence Control During the Course of the Day Early morningDay EveningLater in the evening NightInverter stack switch-on time Permissible voltage dip after switching on the stackPower limit value for shutdown, delay time for shutdown Sequence Control ParametersDescription of Fan Control General Fan Control, Cabinet FanCabinet Fan Control Parameters Fan Control, Inverter Stack FanIgbt temperature limit value for switching off the fan Igbt temperature limitParameters of Inverter Stack Fan Control Insulation Monitoring and Earthing of PV Cells GeneralProtect PV.500-MH Operating Instructions Maintenance mode Operation with Thin-Film Solar CellsGeneral Sequence controlDelay for shutdown of K21 in night operation Minimum time in maintenance modeInsulation Monitoring Parameters MPP TrackerMonitoring Systems, Messages and Faults Table of Faults Temperature monitoring systemsCan I/O monitoring systems Fault/Message Unit Monitoring Systems Fault/Message DC voltage monitoring systems Fault/Message Interfaces Communication InterfaceTechnical Data MultiCom CCC hardware data assembly A29.1 Communication data port 1Communication data port 2 Communication data port 3Configuration jumpers Structure of the MultiCom CCC InterfaceConnections ButtonDescription of serial interfaces Port 2 X5 RS485 pin assignment default Shield connection of the RS485 bus lineConfiguration Port 2 X5 RS232 pin assignmentController Area Network can at Port 3 X4 can pin assignmentConfiguration Preparations Setting the terminal programProtect PV.500MH Operating Instructions Configuring the Modbus Protocol Data protocol configurationConfiguring Modbus Data Transmission Modbus/JBus data transmission configurationNetwork Connection Structure of the COM Server internally wired to A93COM Server General Installation of the COM Server Network Integration Configuration Configuration of the Virtual COM PortStructure Remote SignallingTechnical data Following default signals are used for remote signalling Graphical Display and Operation Unit DOUSignalling Acoustic signal generatorKeyboard Operation LEDsPossible symbol keys and their function Start-upMenu Structure Menu Tree Main MenuOperating Display Operating display Normal operationExamples of possible displays Example of operating displaySolar radiation is too low, the inverter is in standby mode Monthly data t = day 1 31 for the last 12 months Example of yearly overview Menu Status/Measured ValuesBlocking Menu Inverter exampleFault History SettingsService Information