Brown and Son WA Cooler & Freezer manual Replacing The Digital Thermometer

Page 24

Replacing The Digital Thermometer

Turn off breaker before disconnecting wires.

If the thermometer does not register correctly you will need to check the following:

1.Check the voltage on the load side of the transformer. It should be 12 volts.

2.If the voltage is not 12 volts on the load side of the transformer, check the line side to confirm that proper voltage is reaching the transformer.

3.If you have 115 volts on the line side and nothing on the load side you will need to change the transformer.

4.If the transformer checks good you will need to change the digital display. This is done by removing the two screws from the front of the display and pulling out the whole module. Take the two wire nuts off the incoming power located behind the display. Pull the probe out through the insulated section. Push the new probe through the same hole in the insulated section and secure. Hook the two wires back to the incoming power from the transformer. Replace the display on the door section and secure with the screws. Turn the power on and check the display.

Description Of Numbered Parts, Figure #24 and #25

1.Junction Box

2.Optional wire guard for vapor proof light

3.Plastic coated glass globe for vapor proof light

Replacing A Pressure Relief Port

After determining the pressure relief port is defective use the following guidelines:

(NOTE: THE HEATER IS NOT AVAILABLE SEPARATELY.)

1.Turn off the electrical supply to the pressure relief port.

2.Remove the inside and outside louvers and remove any sealant that might be holding the port in place.

3.Open square J. Box and disconnect two small white wires and one green wire to PRP.

4.Pull out the PVC portion of the port along with the wiring.

5.Feed the wire from the new port through the hole up to the junction box.

6.Put the PVC portion back into the wall section making sure that the heater is in the interior of the walk-in.

7.Seal around the interior with silicone (not provided) then install the interior louvered flange.

8.Push the vent in tight against the interior flange.

9.Seal around the exterior PVC portion with silicone (not provided) and install the exterior louver.

10.Connect the electrical wires and turn the electricity on.

11. After 15 minutes check to see if the heater is working on the new port.

Description Of Numbered Parts, Figure #27, and #28

1.4" Urethane wall

2.45 degree 1/2" hole

3.1/2" groove to hole

4.Wire

5.Junction Box at header of door

6.2 1/2" hole

Figure #25

Figure #27

21/2"

Pressure Relief Port

Figure #28

22

Image 24
Contents For All W. A. Brown & Son, Inc. Models Table of Contents Receiving and Uncrating TerminologyFloor Preparation and Installation Installation of floor panelsDiamond Aluminum Treadplate Overlay Instructions Layout of the FloorCam Lock Installation Floor Spline Layout and InstallationFloorless Walk-In Layout Ramset Studs Or ScrewsPVC Panel Track Installation for Floorless Walk-In Figure #4Wall Panel Installation Wall Protector Plate Wainscotting InstructionsTop Panel Installation Multiple Compartment Walk-Ins With a Tee PanelInstallation of Membrane Roof Cap For Outside Units Membrane Roof CapPenetrations of Panels Duro-LastRoof Cap Installation for outside installation Install to existing wallFiber Cement Finish Panels Installation Painting Fiber CementWhen ceiling is not Top Panel Trim Installation Installation of 1/2 x 5 Trim on Top PanelsDrop-Off Walk-In Coolers and Freezers EZ Pack Installation Instructions Installing the Refrigeration SystemSetting Controls Final Checks Before OperationRoof Cap & Curb Installation Figure #14 Wiring the Door Heater, Lights & WindowsVapor Proof Light Fluorescent LightsHousekeeping and Safety Housekeeping and Safety RecommendationsCleaning of Stucco Aluminum & Galvalume Plus Cleaning Stainless Steel FinishesHow To Call for Service Repair Replacement PartsSize Lifetime Limited Cabinet Warranty Adjusting Door Closer See Figure #17 Instructions for removing Door Leaf with SpringLoaded Hinges See Figure #15 See sketchReplacement Keys Description Of Numbered Door Section ComponentsGuidelines For Replacing Door Heater Cable Description Of Numbered Parts in Figure #19 and #20Relacing Door Gasket Cross Section Of Door LeafDescription Of Numbered Parts in Figure #21 Installing Surface Dial Thermometer Figure #23 Replacing Flush Dial ThermometerReplacing The Digital Thermometer Replacing a Pressure Relief PortDescription Of Numbered Parts, Figure #24 and #25 Description Of Numbered Parts, Figure #27, and #28Electrical Hook-Up to Junction Box Figure #26Figure #30 Refrigeration Trouble Shooting Guide Malfunction Possible Cause SolutionInput Voltage