Brown and Son WA Cooler & Freezer manual Duro-LastRoof Cap Installation for outside installation

Page 10

Repeat this procedure on all four sides.

Trim extra material prior to sealing.

Cut, fold, and glue roof membrane using contact cement (not provided)

Position flashing to corner and form to fit by applying hand pressure to outside edges. Secure the corner flashing to the sidewalls.

Install to existing wall

Allow membrane to extend up the existing wall approximately 6".

Position 2 1/2" cove and fasten.

Apply contact cement or caulk (not provided by W. A. Brown) along the top joint where the cove joins the wall, down the edge at each end of the cove and down the edge of flashing at the wall.

Duro-Last®Roof Cap Installation (for outside installation)

The following are general instructions for installing the Duro-Last system. (See Figure #10)

Surface Preparation: The Walk-In Top must be clean, smooth, free of sharp edges, loose debris and standing water.

Placement: Select proper pre-manufactured and marked rolled sheet of Duro-Last membrane according to roof lay-out diagram. Orient roofing membrane so the 3" wide fastening tabs are perpendicular to Top Panel Joints. Secure to Walk-In through 3" fastening tab with approved fasteners and plates in accordance with specifica- tions. Unfold Duro-Last membrane over tab. Continue unfolding until next 3" fastening tab appears. Repeat above procedure until entire sheet is fastened in place. Make sure to have 6" overhang on each side before starting fastening.

Protusions: During the aforementioned procedure, make cutouts in the Duro-Last membrane for protusions. Fasten around cutouts with Duro-Last approved fasteners. The skirts on the factory fabricated accessories, when welded to the deck membrane, will cover these cutouts.

Breather Vents: For every 1,000 square feet of deck membrane install a Duro-Last two way vent. Install vents according to Duro-Last specifications.

Parapet Walls: Use custom fabricated parapet wall flashing designed specifically for each individual application and roof. Secure through 3" fastening tab at bottom of parapet wall using approved Duro-Last fasteners and plates, thus holding down edge of deck membrane. The dielectrically welded skirt will cover these and is then welded to the deck membrane.

Install 2 x 6 flashing as noted on page 7.

Factory Welded Laps

Every 57" Throughout

Section

Duro-Last

Membrane

Factory Welds

Termination bar with Durolast® in hem of 2 x 6 flashing

Duro-Last Stress Distribution

 

Plates and Approved Fasteners

 

Reversed Lap

Fastened 12" On-Center

(Facing Edge)

 

 

30"

Figure #10

8

Image 10
Contents For All W. A. Brown & Son, Inc. Models Table of Contents Receiving and Uncrating TerminologyDiamond Aluminum Treadplate Overlay Instructions Floor Preparation and InstallationInstallation of floor panels Layout of the FloorFloorless Walk-In Layout Cam Lock InstallationFloor Spline Layout and Installation Ramset Studs Or ScrewsPVC Panel Track Installation for Floorless Walk-In Figure #4Wall Panel Installation Wall Protector Plate Wainscotting InstructionsTop Panel Installation Multiple Compartment Walk-Ins With a Tee PanelMembrane Roof Cap Installation of Membrane Roof Cap For Outside UnitsPenetrations of Panels Duro-LastRoof Cap Installation for outside installation Install to existing wallFiber Cement Finish Panels Installation Painting Fiber CementWhen ceiling is not Installation of 1/2 x 5 Trim on Top Panels Top Panel Trim InstallationDrop-Off Walk-In Coolers and Freezers Setting Controls EZ Pack Installation InstructionsInstalling the Refrigeration System Final Checks Before OperationVapor Proof Light Roof Cap & Curb Installation Figure #14Wiring the Door Heater, Lights & Windows Fluorescent LightsCleaning of Stucco Aluminum & Galvalume Plus Housekeeping and SafetyHousekeeping and Safety Recommendations Cleaning Stainless Steel FinishesReplacement Parts How To Call for Service RepairSize Lifetime Limited Cabinet Warranty Loaded Hinges See Figure #15 Adjusting Door Closer See Figure #17Instructions for removing Door Leaf with Spring See sketchReplacement Keys Description Of Numbered Door Section ComponentsGuidelines For Replacing Door Heater Cable Description Of Numbered Parts in Figure #19 and #20Cross Section Of Door Leaf Relacing Door GasketDescription Of Numbered Parts in Figure #21 Installing Surface Dial Thermometer Figure #23 Replacing Flush Dial ThermometerDescription Of Numbered Parts, Figure #24 and #25 Replacing The Digital ThermometerReplacing a Pressure Relief Port Description Of Numbered Parts, Figure #27, and #28Electrical Hook-Up to Junction Box Figure #26Figure #30 Refrigeration Trouble Shooting Guide Malfunction Possible Cause SolutionInput Voltage