Multiquip DCA40SSKU4i Generator Output Voltages, Voltage Selector Switch, Generator Amperage

Page 24

GENERATOR OUTPUTS

Generator Output Voltages

A wide range of voltages are available to supply voltage for many different applications.Voltages are selected by using the voltage selector switch (Figure 13). To obtain some of the voltages as listed in Table 7 (see below) will require a fine adjustment using the voltage regulator (VR) control knob located on the control panel.

Voltage Selector Switch

The voltage selector switch (Figure 13) is located above the output terminal panel’s Hard Wire Hook-up Panel. It has been provided for ease of voltage selection.

Generator Amperage

Table 8 shows the maximum amps the generator can provide. DO NOT exceed the maximum amps as listed..

Table 8. Generator Maximum Amps

Rated Voltage

Maximum Amps

 

 

1Ø 120 Volt

82 amps (4 wire)

89A x 2 (Zigzag)

 

1Ø 240 Volt

41 amps (4 wire)

89A (Zigzag)

 

3Ø 240 Volt

89 amps

 

 

3Ø 480 Volt

44 amps

 

 

Figure 13. Voltage Selector Switch

Voltage Selector Switch Locking Button

To lock the voltage selector switch, press and hold the red button located at the bottom of the switch. While holding the red button down, insert a pad lock into the hole next to the button to retain it in the inward locked position. When the lock is removed, the red button is spring loaded and will return to its normal outward unlocked position.

CAUTION

NEVER change the position of the voltage selector switch while the engine is running. ALWAYS place circuit breaker in the OFF position before selecting voltage.

Table 7. Voltages Available

UVWO Output

Voltage Selector Switch

Voltage Selector Switch

Terminal Lugs

3-Phase 240/139V Position

3-Phase 480/270V Position

 

 

 

 

 

 

 

Line-Line

208V

220V

240V

416V

440V

480V

 

 

 

 

 

 

 

Line-Neutral

120V

127V

139V

240V

254V

277V

 

 

 

 

 

 

 

Voltage Selector Switch Single-Phase 240/120V Position

 

 

 

 

 

 

 

 

Line-Neutral/

120V

N/A

N/A

240V

N/A

N/A

Line-Line

Line-Neutral

Line-Line

 

 

 

 

 

 

 

 

 

 

 

GFCI Receptacle Load Capability

The load capability of the GFCI receptacles is directly related to the voltage being supplied at either the output terminals or the 2 twist lock auxiliary receptacles.

Table 9 and Table 10 show what amount of current is available at the GFCI receptacles when the output terminals and twist lock receptacles are in use. Be careful that your load does not to exceed the available current capability at the receptacles.

Table 9. 1Ø GFCI Receptacle Load Capacity

KW in Use

Available Load

Twist Lock (C6369)

Current (Amps)

1Ø 240/120V

GFCI Duplex

5-20R 120V

 

21.0

0

19.8

5 amps/receptacle

18.6

10 amps/receptacle

 

 

17.4

15 amps/receptacle

 

 

16.2

20 amps/receptacle

 

 

Table 10. 3Ø Generator Maximum Amps

KVA in Use

Available Load

(UVWO Terminals)

Current (Amps)

3Ø 240/480V

GFCI Duplex

5-20R 120V

 

37

0 amps/receptacle

 

 

32.8

5 amps/receptacle

 

 

28.7

10 amps/receptacle

 

 

24.5

15 amps/receptacle

 

 

20.4

20 amps/receptacle

 

 

page 24 — DCA40sskU/ku4i 60 hz Generator • operation and parts manual — rev. #1 (03/11/13)

Image 24
Contents Model DCA40SSKU Model DCA40SSKU4i Proposition 65 warning Reporting Safety Defects AdministratorTable of Contents DCA45SSKU/SSKU4i 60 Hz GeneratorChoose from three easy options Safety Information SaFeTY messagesGeneral saFeTY GeneraTor saFeTYEngine saFeTY Restricted. If the air fl ow isIf operating in speed ranges above the maximum allowable FUel saFeTY ToWing saFeTY„ never use fuel as a cleaning agent From fuel vapors or if fuel is spilled on a hot engineEleCTriCal saFeTY Grounding safetyPower Cord/Cable safety BaTTerY saFeTY EnvironmenTal saFeTYSpecifications 240/120Dimensions DimensionsInstallation Typical Generator Grounding ApplicationOutdoor Installation Indoor InstallationMounting Generator GroundingGeneral Information Major Components Item noWill remain OFF. When the ignition Engine Control PanelGenerator control Panel Generator Control PanelOutput Terminal Familiarization Terminal legs O and Ground are considered bonded groundsOutput Terminal Panel is provided with the following Removing the Plastic Face Plate Hard Wire Hookup Panel VAC Gfci ReceptaclesConnecting Loads Over Current RelaySingle Phase Load Three Phase LoadLoad Application Voltage Selector Switch Voltage Selector Switch Locking ButtonGenerator Output Voltages Generator AmperageHow to Read the ac ammeter and ac voltage gauges Generator OUTPUTS/gauge readingAC Voltmeter Gauge Reading AC Ammeter Gauge ReadingUvwo Terminal Output Voltages 3Ø-240/139 Uvwo Terminal Output Voltages3Ø-208V/1Ø-120V Uvwo Terminal Output Voltages 3Ø-480/277V Uvwo Terminal Output Voltages 1Ø-240/120V Uvwo Terminal Output VoltagesInspection/SETUP Circuit BreakersLubrication Oil Fuel CheckRefueling Procedure Remove fuel cap and fill tank as shown in FigureCleaning the Radiator Air Cleaner Fan Belt TensionCoolant Antifreeze/Summer Coolant/ Water Operation in Freezing WeatherBattery Battery Cable InstallationWiring AlternatorBefore Starting StartingEngine’s exhaust contains harmful emissions Place the engine speed control switch in the RUN position up Normal Shutdown Procedure Emergency Shutdown ProcedureAutomatic Shut-down System Maintenance General Inspection Air CleanerAir Cleaner with Dust Indicator Cleaning Inside the Fuel Tank Fuel AdditionRemoving Water from the Fuel Tank Fuel Tank InspectionRadiator Cleaning Air RemovalCheck Oil Level Replacing Oil FilterJacketWater Heater and Internal Battery Optional Battery Charger and Jacket Water Heater optionTrailer Maintenance Trailer MaintenanceCoupler Type of hitch used on the trailer for towing Brake Adjustment BrakesHydraulic Surge Brakes ActuatorTires/Wheels/Lug Nuts Tire Wear/InflationSuspension Lug Nut Torque Requirements Never use an pneumatic air gun to tighten wheel lug nutsTrailer Wiring Diagram Trailer/Towing Vehicle Wiring DiagramGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramTroubleshooting Generator Generator TroubleshootingPage Explanation of Code in Remarks Column Suggested Spare Parts To 3 unitsGenerator Assy B3110001302 06018200830601822664 B3120100804Control box Assy M1213002012 Y0330000555Y0330000255 Y0330000190Control box Assy 0601806859 0601808986 AC AMMETER, 0~75/150A5A 06018076410601801040 0601840073Engine and Radiator Assy M1923200164 1G541970101663143560 HH1C032430Engine and Radiator Assy 0193601300 0605515170M1310200904 M1310201004Output Terminal Assy 8111860303 0801831704A0039310000 0041410000Battery Assy 0602220199 M9310500014M9103000304 0602220920Muffler Assy M1330101403 M1333003503Y0602320157 0030410000Fuel Tank Assy M1363002602 06055050700605501072 0605516090Enclosure Assy M1413004202 M1413400004M1423003102 M1493110203Enclosure Assy 0019108055 36A 004230800036B 031108160 M1453006213Rubber Seals Assy Y0228901240 Y0228900625Y0228900595 0229400970Nameplate and Decals Assy M9522000504 M9520000104M9522000604 M9500400204Terms and Conditions of Sale Parts FreighT poliCYPage HERE’S HOW to GET Help