inspection/SETUP

Battery

This unit is of negative ground DO NOT connect in reverse. Always maintain battery fluid level between the specified marks. Battery life will be shortened, if the fluid level are not properly maintained. Add only distilled water when replenishment is necessary.

DO NOT over fill. Check to see whether the battery cables are loose. Poor contact may result in poor starting or malfunctions. Always keep the terminals firmly tightened. Coating the terminals with an approved battery terminal treatment compound. Replace battery with only recommended type battery.

The battery is sufficiently charged if the specific gravity of the battery fluid is 1.28 (at 68° F). If the specific gravity should fall to 1.245 or lower, it indicates that the battery is dead and needs to be recharged or replaced.

Before charging the battery with an external electric source, be sure to disconnect the battery cables.

Battery Cable Installation

ALWAYS be sure the battery cables (Figure 35) are properly connected to the battery terminals as shown below. The red cable is connected to the positive terminal of the battery, and the black cable is connected to the negative terminal of the battery.

CAUTION

ALWAYS disconnect the negative terminal FIRST and reconnect negative terminal LAST.

Figure 35. Battery Connections

When connecting battery do the following:

1.NEVER connect the battery cables to the battery terminals when the MPEC Control Switch is in either the MANUAL position. ALWAYS make sure that the MPEC Control Switch is in the OFF/RESET position when connecting the battery.

2.Place a small amount of battery terminal treatment compound around both battery terminals. This will ensure a good connection and will help prevent corrosion around the battery terminals.

NOTICE

If the battery cable is connected incorrectly, electrical damage to the generator will occur. Pay close attention to the polarity of the battery when connecting the battery.

CAUTION

Inadequate battery connections may cause poor starting of the generator, and create other malfunctions.

Alternator

The polarity of the alternator is negative grounding type. When an inverted circuit connection takes place, the circuit will be in short circuit instantaneously resulting the alternator failure.

DO NOT put water directly on the alternator. Entry of water into the alternator can cause corrosion and damage the alternator.

Wiring

Inspect the entire generator for bad or worn electrical wiring or connections. If any wiring or connections are exposed (insulation missing) replace wiring immediately.

Piping and Hose Connection

Inspect all piping, oil hose, and fuel hose connections for wear and tightness. Tighten all hose clamps and check hoses for leaks.

If any hose (fuel or oil) lines are defective replace them immediately.

DCA40sskU/ku4i 60 hz Generator • operation and parts manual — rev. #1 (03/11/13) — page 31

Image 31
Contents Model DCA40SSKU Model DCA40SSKU4i Proposition 65 warning Administrator Reporting Safety DefectsDCA45SSKU/SSKU4i 60 Hz Generator Table of ContentsChoose from three easy options SaFeTY messages Safety InformationGeneraTor saFeTY General saFeTYRestricted. If the air fl ow is Engine saFeTYIf operating in speed ranges above the maximum allowable From fuel vapors or if fuel is spilled on a hot engine FUel saFeTYToWing saFeTY „ never use fuel as a cleaning agentGrounding safety EleCTriCal saFeTYPower Cord/Cable safety EnvironmenTal saFeTY BaTTerY saFeTY240/120 SpecificationsDimensions DimensionsTypical Generator Grounding Application InstallationGenerator Grounding Outdoor InstallationIndoor Installation MountingGeneral Information Item no Major ComponentsEngine Control Panel Will remain OFF. When the ignitionGenerator Control Panel Generator control PanelTerminal legs O and Ground are considered bonded grounds Output Terminal FamiliarizationOutput Terminal Panel is provided with the following VAC Gfci Receptacles Removing the Plastic Face Plate Hard Wire Hookup PanelOver Current Relay Connecting LoadsThree Phase Load Single Phase LoadLoad Application Generator Amperage Voltage Selector SwitchVoltage Selector Switch Locking Button Generator Output VoltagesAC Ammeter Gauge Reading How to Read the ac ammeter and ac voltage gaugesGenerator OUTPUTS/gauge reading AC Voltmeter Gauge Reading3Ø-240/139 Uvwo Terminal Output Voltages Uvwo Terminal Output Voltages3Ø-208V/1Ø-120V Uvwo Terminal Output Voltages 1Ø-240/120V Uvwo Terminal Output Voltages 3Ø-480/277V Uvwo Terminal Output VoltagesFuel Check Inspection/SETUPCircuit Breakers Lubrication OilRemove fuel cap and fill tank as shown in Figure Refueling ProcedureOperation in Freezing Weather Cleaning the RadiatorAir Cleaner Fan Belt Tension Coolant Antifreeze/Summer Coolant/ WaterAlternator BatteryBattery Cable Installation WiringStarting Before StartingEngine’s exhaust contains harmful emissions Place the engine speed control switch in the RUN position up Emergency Shutdown Procedure Normal Shutdown ProcedureAutomatic Shut-down System General Inspection Air Cleaner MaintenanceAir Cleaner with Dust Indicator Fuel Tank Inspection Cleaning Inside the Fuel TankFuel Addition Removing Water from the Fuel TankReplacing Oil Filter Radiator CleaningAir Removal Check Oil LevelBattery Charger and Jacket Water Heater option JacketWater Heater and Internal Battery OptionalTrailer Maintenance Trailer MaintenanceCoupler Type of hitch used on the trailer for towing Actuator Brake AdjustmentBrakes Hydraulic Surge BrakesTire Wear/Inflation Tires/Wheels/Lug NutsSuspension Never use an pneumatic air gun to tighten wheel lug nuts Lug Nut Torque RequirementsTrailer/Towing Vehicle Wiring Diagram Trailer Wiring DiagramGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramGenerator Troubleshooting Troubleshooting GeneratorPage Explanation of Code in Remarks Column To 3 units Suggested Spare PartsGenerator Assy B3120100804 B31100013020601820083 0601822664Control box Assy Y0330000190 M1213002012Y0330000555 Y0330000255Control box Assy 0601840073 06018068590601808986 AC AMMETER, 0~75/150A5A 0601807641 0601801040Engine and Radiator Assy HH1C032430 M19232001641G54197010 1663143560Engine and Radiator Assy M1310201004 01936013000605515170 M1310200904Output Terminal Assy 0041410000 81118603030801831704A 0039310000Battery Assy 0602220920 0602220199M9310500014 M9103000304Muffler Assy 0030410000 M1330101403M1333003503 Y0602320157Fuel Tank Assy 0605516090 M13630026020605505070 0605501072Enclosure Assy M1493110203 M1413004202M1413400004 M1423003102Enclosure Assy M1453006213 001910805536A 0042308000 36B 031108160Rubber Seals Assy 0229400970 Y0228901240Y0228900625 Y0228900595Nameplate and Decals Assy M9500400204 M9522000504M9520000104 M9522000604FreighT poliCY Terms and Conditions of Sale PartsPage HERE’S HOW to GET Help