Guardian Technologies 04759-2 Battery Installation, The Battery, 5 - Battery Cable Connections

Page 11
‹1.9.2 TRANSFER SWITCH

Section 1 — General Information

Air-cooled 7 kW, 12 kW and 15 kW Generators

‹1.9.2 TRANSFER SWITCH

1.9.2.1 7 kW, 12 kW and 15 kW Units

Transfer switches for use with these generators are sold separately and can be purchased from Authorized Dealers.

Install the transfer switch on a firm, sturdy sup- porting structure.

To prevent switch distortion, level the switch if necessary. This can be done by placing washers between the switch enclosure and mounting sur- face.

Never install the switch where water or any corro- sive substance might drip onto the enclosure.

Protect the switch at all times against excessive moisture, dust, dirt, lint, construction grit and cor- rosive vapors.

Failure to utilize the manufacturer's transfer switch with this generator will void the warranty.

1.10 BATTERY INSTALLATION

Fill the battery with the proper electrolyte fluid if necessary and have the battery fully charged before installing it.

Before installing and connecting the battery, complete the following steps:

1.Set the generator's AUTO/OFF/MANUAL switch to OFF.

2.Turn off utility power supply to the transfer switch.

3.Remove the 5 amp and 15 amp fuses from the generator control panel.

If the AUTO/OFF/MANUAL switch is not set to its OFF position, the generator can crank and start as soon as the battery cables are connected. If the utility power supply is not turned off, spark- ing can occur at the battery posts and cause an explosion.

Battery cables were factory connected at the genera- tor (Figure 1.5). Connect cables to battery posts as follows:

4.Connect the red battery cable (from starter con- tactor) to the battery post indicated by a positive, POS or (+).

5.Connect the black battery cable (from frame ground) to the battery post indicated by a nega- tive, NEG or (—).

6.Replace the 5 amp and 15 amp fuses in the gen- erator control panel.

NOTE:

Damage will result if battery connections are made in reverse.

Figure 1.5 – Battery Cable Connections

NOTE:

The generator is equipped with a battery trickle charger that is active when the unit is set up for automatic operation. With the battery installed and utility power source voltage available to the transfer switch, the battery receives a trickle charge while the engine is not running, to prevent self-discharge. The trickle charger is designed to help extend the life of the battery by maintain- ing the battery when the unit is not running. The trickle charge feature cannot be used to recharge a discharged battery.

1.11 THE BATTERY

Servicing of the battery is to be performed or super- vised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized person- nel away from batteries.

When replacing the battery, use the following type of battery: Group 26/26R 12-volt battery with a rating of 350 cold-cranking amps minimum for 7 kW; 525 cold-cranking amps minimum for 12 and 15 kW at 18º C (0º F) minimum. When using a maintenance- free battery, it is not necessary to check the specific gravity or electrolyte level. Have these procedures performed at the intervals specified in the “Service Schedule.” A negative ground system is used. Battery connections are shown on the wiring diagrams. Make sure the battery is correctly connected and terminals are tight. Observe battery polarity when connecting the battery to the generator set.

1.10 BATTERY INSTALLATIONFigure 1.5 – Battery Cable Connections DANGER

Do not dispose of the battery in a fire. The battery is capable of exploding.

A battery presents a risk of electrical shock

and high short circuit current. The following pre- cautions are to be observed when working on batteries:

9

Image 11
Contents  Not intended for use as Primary Power in place of utility  Models 04758-2 6 kW NG, 7 kW LP 04759-2 12 kW NG, 12 kW LP04760-2 13 kW NG, 15 kW LP This manual should remain with the unitINTRODUCTION ‹ CONTENTS‹ OPERATION AND MAINTENANCE ‹ HOW TO OBTAIN SERVICESection 5 - Troubleshooting Section 2 - Post Installation Start-upand Adjustments Section 4 - MaintenanceThis product contains or emits chemicals  GENERAL HAZARDS IMPORTANT SAFETY INSTRUCTIONS  WARNING ‹ STANDARDS INDEX  ELECTRICAL HAZARDS  FIRE HAZARDS   EXPLOSION HAZARDS DANGER 1.1 UNPACKING/INSPECTION1.2 PROTECTION SYSTEMS 1.3 SYSTEM SET LEDFigure 1.2 - 12 kW/15 kW, V-twin GT-990/760 Engine 1.4 THE GENERATORFigure 1.1 - 7 kW, Single Cylinder GH-410 Engine ‹ 1.5.2 ENGINE 1.5 SPECIFICATIONS‹ 1.5.1 GENERATOR DANGER 1.8 RECONFIGURING THE FUEL SYSTEM1.6 FUEL REQUIREMENTS AND RECOMMENDATIONS 1.7 FUEL CONSUMPTIONFigure 1.4 - Demand Regulator 1.9 LOCATION‹ 1.8.2 12KW AND 15KW, 990CC ENGINES ‹ 1.9.1 GENERATORFigure 1.5 - Battery Cable Connections 1.10 BATTERY INSTALLATION1.11 THE BATTERY ‹ 1.9.2 TRANSFER SWITCH 1.9.2.1 7 kW, 12 kW and 15 kW UnitsSection 2 - Post Installation Start-up and Adjustments 2.2 CHECK TRANSFER SWITCH OPERATION2.1 BEFORE INITIAL START-UP 2.3 ELECTRICAL CHECKS2.5 CHECKING AUTOMATIC OPERATION 2.4 GENERATOR TESTS UNDER LOADFigure 2.1 - Dual Fuel Regulators 2.6 ADJUSTING THE REGULATOR NATURAL GAS ONLYFigure 2.2 - Placement of Regulator Figure 2.5 - V-twin Full Load Speed Adjust Screw 2.7 ENGINE GOVERNOR ADJUSTMENTFigure 2.3 - Single Cylinder Engine Governor Adjustment Figure 2.4 - V-twin Engine Governor Adjustment‹ 3.2.1 “AUTO” POSITION 2.8 VOLTAGE REGULATOR ADJUSTMENT3.1 BREAK-IN PROCEDURE Figure 2.6 - Voltage Adjustment Potentiometer‹ 3.5.1 TRANSFER TO GENERATOR POWER SOURCE 3.3 AUTOMATIC TRANSFER OPERATION3.4 SEQUENCE OF AUTOMATIC OPERATION 3.5 MANUAL TRANSFER OPERATIONFigure 3.2 - Manual Transfer Switch Operation 3.6 SETTING THE EXERCISE TIMER‹ 3.5.2 TRANSFER BACK TO UTILITY POWER SOURCE ‹ 3.7.1 LOW OIL PRESSURE SWITCH4.2 CHECKING THE ENGINE OIL LEVEL ‹ 3.7.2 HIGH TEMPERATURE SWITCHFigure 3.3 - Low Oil Pressure and High Temperature Switches 4.1 FUSE4.4 CHANGING THE OIL FILTER 4.5 CHANGING THE ENGINE AIR CLEANER‹ 4.3.2 OIL CHANGE PROCEDURE 4.3 CHANGING THE ENGINE OILFigure 4.8 - Setting the Spark Plug Gap 4.7 BATTERY MAINTENANCEFigure 4.6 - 7 kW, Engine Air Cleaner Location Figure 4.7 - 12 kW and 15 kW Engine Air Cleaner4.9 COOLING SYSTEM 4.8 ADJUSTING VALVE CLEARANCEFigure 4.10 - Valve Clearance Adjustment 4.10 ATTENTION AFTER SUBMERSION 4.12 OUT OF SERVICE PROCEDURE‹ 4.12.1 REMOVAL FROM SERVICE ‹ 4.12.2 RETURN TO SERVICEbe performed by the nearest Authorized Dealer 4.13 SERVICE SCHEDULEATTENTION It is recommended that all service work Correction 5.1 TROUBLESHOOTING GUIDEProblem CauseSection 6 - Electrical Data ENGINE WIRINGCONNECTION CONTROL PANEL BOXCUSTOMER Electrical Schematic - 12 & 15 kW - Drawing No. 0D8501-B Section 6 - Electrical Data Section 6 - Electrical Data ENGINE WIRINGCUSTOMER 224A 225AElectrical Schematic - 7 kW - Drawing No. 0D9014-C PRE PACKAGED UNITS ONLY Section 7 - Exploded Views and Parts ListsFOAM, BACK EXHAUST ENCLOSURE COVER PART NO. QTY. DESCRIPTIONCLOTH, HARDWARE 266.7mm x 146mm 7KW FOAM, EXHAUST SIDE ENCLOSURE FRONTSection 7 - Exploded Views and Parts Lists DESCRIPTION PART NO. QTY72 27, 28 73 3, 32, 33, 34, 35, 36, 40 Views and Parts Lists66 2, 5, 19, 20, 39, 40, 47, 64, 93 67 8, 11, 12 68 4, 5 69 16A, 16B, 17ROLLER BEARING, GOVERNOR PLATE ASSEMBLY, CRANKCASE HOUSING WITHASSEMBLY, CRANKSHAFT HORIZONTAL ITEM PART NO. QTY. DESCRIPTIONSection 7 - Exploded Views and Parts Lists ASSY, IGNITION COIL GV-990 CYLINDER 7 kW Generator - Drawing No. 0D3504-E 1.25 FT 1.8 FT32 31 12 kW and 15 kW Generator - Drawing No. 0D3417-L1.44 FT 2.6 FT3 FT Section 7 - Exploded Views and Parts Lists DESCRIPTION Section 7 - Exploded Views and Parts ListsSection 7 - Exploded Views and Parts Lists DESCRIPTION Section 7 - Exploded Views and Parts ListsSection 7 - Exploded Views and Parts Lists DESCRIPTION Air-cooled ALL DIMENSIONS IN MILLIMETERS INCHESSection 8 - Mounting Drawing NoSection 9 - Notes CALIFORNIA AND FEDERAL EMISSION CONTROL WARRANTY STATEMENT YOUR WARRANTY RIGHTS AND OBLIGATIONSMANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIESEMISSION RELATED PARTS INCLUDE THE FOLLOWING EMISSION CONTROL SYSTEM WARRANTYPREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS GENERAC POWER SYSTEMS TWO YEAR LIMITED WARRANTY FOR GUARDIANWARRANTY SCHEDULE THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING