Section 4 — Maintenance
3.7.2 HIGH TEMPERATURE SWITCH
This switch’s contacts (Figure 3.3) close if the tem- perature should exceed approximately 140º C (284º F), initiating an engine shutdown. The generator will automatically restart and the LED will reset once the temperature has returned to a safe operating level.
Figure 3.3 – Low Oil Pressure and
High Temperature Switches
Low Oil Switch |
| High Temp Switch |
|
|
|
|
|
|
4.1FUSE
The generator panel’s 15 amp fuse (Figure 4.1) pro- tects the DC control circuit against overload. The fuse is wired in series with the battery output lead to the panel. If the fuse element has melted open, the engine cannot crank or start. Replace the fuse using only an identical
The generator panel’s 5 amp fuse protects the battery charge circuit against overload. If the fuse element has melted open, battery charging capability will not be possible. Replace the fuse using only an identical 5 amp replacement. To remove fuse, push cap down and rotate counterclockwise.
Figure 4.1 – Generator Control Panel
Loosen
Oil
Drain
Hose
Oil Filter
3.7.3 OVERCRANK
FUSE
5A
AUTO OFF MAN.
FUSE
15ASET EXERCISE
TIME
L o c a t e y o u r n e a r e s t d e a le r a t :
POWER SYSTEMS, INC.
SYSTEM SET
LOW OIL
HIGH TEMP.
OVER SPEED
OVER CRANK
F L A S H IN G G R E E N L E D =
N O U T IL IT Y S E N S E 4 F L A S H IN G R E D L E D S =
E X E R C IS E R N O T S E T
This feature prevents the generator from damaging itself when it continually attempts to start and anoth- er problem, such as no fuel supply, prevents it from starting. The unit will crank and rest for a preset time limit. Then, it will stop cranking, and the LED will light indicating an overcrank failure. The AUTO/OFF/ MANUAL switch will need to be set to OFF and then back to AUTO to reset the generator control board.
NOTE:
If the fault is not repaired, the overcrank feature will continue to activate.
4.2CHECKING THE ENGINE
OIL LEVEL
For oil capacities, see “Specifications,” Section 1.5. For engine oil recommendations, see Section 4.3.1. To check the engine oil level, proceed as follows (Figure 4.2):
1.Start the generator by moving the Auto/Off/ Manual switch to the MANUAL position. Allow it to run for a short while and then shut it down by moving the switch to the OFF position.
3.7.3.1 Approximate Crank Cycle Times
•15 seconds ON
•7 seconds OFF
•7 seconds ON
•7 seconds OFF
•Repeat for 45 seconds Approximately 90 seconds total
3.7.4 OVERSPEED
This feature protects the generator from damage by shutting it down if it happens to run faster than the preset limit. This protection also prevents the gen- erator from supplying an output that could poten- tially damage appliances connected to the generator circuit. Contact the nearest Authorized Dealer if this failure occurs.
Figure 4.2 — Oil Dipstick and Fill, 7 kW
Oil Dipstick and Fill
2.Remove the dipstick and wipe it dry with a clean cloth.
17