| Section 7 | ||
| DIAGNOSTIC TESTS | ||
|
| ||
|
|
| |
INTRODUCTION | 3. If AC output voltage and frequency are both “zero”, go to Test 12. | ||
The “Diagnostic Tests” in this chapter may be per- | 4. If the | ||
formed in conjunction with the “Flow Charts” of | go to Test 13. | ||
Section 6. Test numbers in this chapter correspond to | NOTE: The term “low voltage” refers to any volt- | ||
the numbered tests in the “Flow Charts”. | |||
age reading that is lower than the unit's rated volt- | |||
Tests 1 through 17 are procedures involving problems | |||
age. The term “residual voltage” refers to the out- | |||
with the generator's AC output voltage and frequency | put voltage supplied as a result of Rotor residual | ||
(Problems 1 through 4 in the “Flow Charts”). | magnetism (approximately | ||
Tests 18 through 42 are procedures involving prob- |
|
| |
lems with engine operation (Problems 5 through 9 in | TEST 2 - CHECK & ADJUST | ||
the “Troubleshooting Flow Charts”). | |||
ENGINE GOVERNOR | |||
Review and become familiar with Section 4, | |||
|
| ||
“Measuring Electricity”. |
|
|
NOTE: Test procedures in this Manual are not nec- essarily the only acceptable methods for diagnos- ing the condition of components and circuits. All possible methods that might be used for system diagnosis have not been evaluated. If any diagnos- tic method other than the method presented in this Manual is utilized, ensure that neither personnel safety nor the product's safety will be endangered by the procedure or method utilized.
TEST 1- CHECK NO-LOAD VOLTAGE AND
FREQUENCY
DISCUSSION:
The first step in analyzing any problem with the AC generator is to determine the unit's AC output voltage and frequency.
PROCEDURE:
1.Set a
2.Disconnect or turn OFF all electrical loads. Initial checks and adjustments are accomplished at
3.Start the engine, let it stabilize and warm up.
4.Read the AC voltage.
5.Connect an AC frequency meter across AC output leads T1 (Red) and T2 (White) on the customer connection. Repeat the above procedure.
RESULTS:
For units rated
DISCUSSION:
Rotor operating speed and A/C output frequency is proportional. The generator will deliver a frequency of 60 HERTZ at 1950 RPM or 62 HERTZ at 2015 RPM. The voltage regulator should be adjusted to deliver 120 VAC
ENGINE GOVERNOR ADJUSTMENT:
Initial adjustment of governed speed should be accomplished at
Figure 7-1. – Governor Adjustment Points
1. | If AC voltage and frequency are BOTH correspondingly high or | PROCEDURE: | |
| low, go to Test 2. | 1. | Connect an accurate A/C frequency meter and voltmeter to the |
2. | If AC frequency is good but low or residual voltage is indicated, |
| proper generator leads. |
| go to Test 3. | 2. | Start the engine, let it stabilize and warm up at |
|
| 3. | Frequency meter should read between |
Page 37