Document 50934 Rev B 5/15/00 PN 50934:B
22
Note: For additional information on the starting and ending addresses, refer to the host
FACP Technical Manual.
Table 3-1: Start and End Monitoring Addresses
ADT-UDACT Communication Selection (56)
Leaving address 56 at '0' disables communications to the Central Station(s). Enter '1'
for zone reporting, receive only, '2' for zone reporting, receive/transmit, '3' for point
reporting, receive only, or '4' for point reporting, receive/transmit. See Type Mode
Section 4.2 for additional information on detailed reporting. Note: Use receive only
selection when using remote annunciators. Be certain to set one of the annunciators
for receive/transmit for EIA-485 communications bus supervision. Use the receive/
transmit entry when annunciators are not installed or when the ADT-UDACT
receive/transmit function is to be used to supervise the EIA-485 communication bus.
For more information on the receive/transmit function, refer to annunciator
manuals.
Backup Reporting (57) Leaving address 57 at '0' means that reports will be
transmitted to the secondary phone number only if attempts to communicate to the
primary phone number are unsuccessful. Programming a '1' causes all reports to be
transmitted to the secondary phone number.
Touchtone/Rotary Select (58) A '0' programmed in this address by the factory
triggers Touchtone dialing over both phone lines. Select '1' for rotary dialing.
Make Break Ratio (59) Use this address only if you have chosen '1' for address 58.
The make/break ratio is factory set to '0' which is 67/33, but may be changed to '1'
which is a 62/38 ratio.
Address (60) Leave default of 0.
Address (61) Leave default of 0.
AC Loss Reporting Delay (62) '1' is factory default which causes a 6 hour time
delay for AC loss reporting. Valid entries are 0 to 9 and A to F corresponding to the
following reporting delay times: '1' = 6 hour, '2' = 7 hours, '3' = 8 hours, '4' = 9 hours,
'5' = 10 hours, '6' = 11 hours, '7' = 15 hours, '8' = 16 hours, '9' = 17 hours, 'A' = 18
hours, 'B' = 19 hours, 'C' = 20 hours, 'D' = 21 hours, 'E' = 22 hours and 'F' = 23 hours.
'0' entry causes immediate reporting of AC loss.
Host Panel ID (63)
Enter one of the following digits corresponding to the Control Panel in which the
ADT-UDACT is installed. A correct entry is essential for proper operation.
0 = Do not use
1 = Do not use
2 = Do not use
3 = Do not use
4 = Do not use
5 = Do not use
6 = Do not use
7 = Unimode 2020/1010, ADT-MNNA
8 = Unimode 300/400
9 = Do not use