Document 50934 Rev B 5/15/00 PN 50934:B 35
To access Type Mode, press the MODE key followed by the 4-digit code 8973 and
then press the [ENTER/STORE] key. The ADT-UDACT will display three digits.
For example, initial entry will display 01 0.
The characters to the left identify the zone or point number. In this example, 01
identifies zone 01 or point address 01. The character to the right (0 in this example)
identifies the type of zone or point as follows:
0 = Zone or point defined as fire alarm
1 = Disable zone or point report
2 = Zone or point defined as supervisory
3 = Zone or point defined as pull station
4 = Zone or point defined as heat detector
5 = Zone or point defined as waterflow
6 = Zone or point defined as duct detector
7 = Zone or point defined as flame sensor
8 = Zone or point defined as smoke zone (Use for group of addressable or
conventional smoke detectors. Also use for addressable monitor
modules monitoring conventional smoke detectors).
9 = Zone or point defined as burglary (Unimode 300/400 and ADT-MNNA)
A = Zone or point defined as 24 hour non-burglary
B = Zone or point defined as high temperature
C = Zone or point defined as low temperature
D = Zone or point defined as low water pressure
E = Zone or point defined as low water level
F = Zone or point defined as pump failure
Factory default is all zones or points set to '0' for fire alarm. The '0' setting for zone
reporting allows the mixing of types of devices on a single zone. To change the type
definition of the zone or point from the factory default of 0, select 2 to F
corresponding to the type of device(s) used (do not mix device types for these
settings), or select 1 to disable alarm reporting of any zone or point. The digit
entered will appear on the far right display. Next press the [ENTER/STORE] key.
This stores the entry into E2 memory and increments to the next higher address.
Use the UP, DOWN and 1st EVENT keys to move through the list of zones/points
(refer to Appendices), similar to the method described in the programming section of
this manual.
To define all zones or points as fire alarm (return to original factory default settings)
enter zone or point 999 and then press the [ENTER/STORE] key. The display will
change to 01 0, indicating a return to the factory default settings.
4.2.1 Disabling of Zones or Points
This feature is primarily used when system points have been defined as remote reset,
acknowledge, silence or drill switches. Refer to the FACP technical manual for
additional information. Activation of remote switches appear as alarms on the EIA-
485 bus. The ADT-UDACT will report these points as fire alarm points unless
disabled in the Type Mode. Disabling zones or points also prohibits the activation
(shorted or alarm activated condition) from being reported by the ADT-UDACT.
Disabling of the zone or point does not affect the reporting of the zone or point
trouble condition.
Note: Type Mode '1' for zones 90-99, disables reports for these zones. To transmit
reports for zones 90-99, use Type Mode entries of '0' or '2' through 'F'.