Document 50934 Rev B 5/15/00 PN 50934:B 43
7.0 Programming Reference Sheets
--- To enter Programming, press Mode: 7 7 6 4, Enter

00010203040506070809101112131415

Addresses 00 to 15 store the Primary Phone Number. Enter 'F' to represent the end of the number.
16 Primary Comm Format:

Enter 0 - F.

17181920 Primary Account Code: Valid keys are 0-F.

21222324 Primary 24-Hour Test Time.

Enter military time (i.e. 1400 for 2 PM).

25 Primary Number Test Time Interval. Enter '0' for 24-hour; '1' - 12-hour.

26272829303132333435363738394041

Addresses 26-41 store the Secondary Phone Number.

Enter 'F' to represent the end of the number.

42 Secondary Comm Format: Enter 0-F.
43444546 Secondary Account Code: Valid keys are 0-F.
47484950 Secondary 24-Hour Test Time.

Enter military time (i.e. 1400 for 2 PM)

.
51 Secondary Number Test Time Interval. Enter '0' for 24-hour; '1' - 12-hour.

5253 Start Monitoring Address. Valid entries are 01 through 32.

54 55 End Monitoring Address. Valid entries are 01 through 32.
56 ADT-UDACT Communication Selection. Enter '0' to disable ADT-UDACT communication; '1' for zone
reporting receive only communication; '2' for zone reporting receive/transmit communication; '3' for point
reporting receive only; or '4' for point reporting receive/transmit.
57 Backup Reporting. Enter '0' to have secondary phone number act as backup only; '1' to have secondary
phone number receive all reports and messages along with primary phone number.
58 Touchtone/Rotary Select. Enter '0' for touchtone dialing; '1' for rotary dialing.
59 Make/Break Ratio. If rotary dialing is selected in Address 58; Enter '0' for a 67/73 make/break ratio; '1'
for a 62/38 make/break ratio.
60 Leave default of 0.
61 Leave default of 0.
62 AC Loss Reporting Delay. Enter '0' for no time delay after AC loss; '1' for 6 hour delay; '2' for 7 hour
delay; '3' for 8 hour delay; '4' for 9 hour delay; '5' for 10 hour delay; '6' for 11 hour delay; '7' for 15 hour
delay; '8' for 16 hour delay; '9' for 17 hour delay; 'A' for 18 hour delay; 'B' for 19 hour delay; 'C' for 20
hour delay; 'D' for 21 hour delay; 'E' for 22 hour delay; or 'F' for 23 hour delay.
63 Host Panel ID. Enter '7' for Unimode 2020/1010 and ADT-MNNA; '8' for Unimode 300/400; all other
entries are invalid.
64 65 Loop Number. Factory set to '00'. Valid entries are 00 through 97
66 6768 Device/Zone Number for General Reports. Factory set to '000'. Valid entries are 000
through 999.