7.0 Programming Reference Sheets--- To enter Programming, press Mode: 7 7 6 4, Enter
❑00 ❑01 ❑02 ❑03 ❑04 ❑05 ❑06 ❑07 ❑08 ❑09 ❑10 ❑11 ❑12 ❑13 ❑14 ❑15
Addresses 00 to 15 store the Primary Phone Number. Enter 'F' to represent the end of the number.
❑16 Primary Comm Format:
Enter 0 - F.
❑17 ❑18 ❑19 ❑20 Primary Account Code: Valid keys are 0-F.
❑21 ❑22 ❑23 ❑24 Primary 24-Hour Test Time.
Enter military time (i.e. 1400 for 2 PM).
❑25 Primary Number Test Time Interval. Enter '0' for 24-hour; '1' - 12-hour.
❑26 ❑27 ❑28 ❑29 ❑30 ❑31 ❑32 ❑33 ❑34 ❑35 ❑36 ❑37 ❑38 ❑39 ❑40 ❑41
Addresses 26-41 store the Secondary Phone Number.
Enter 'F' to represent the end of the number.
❑42 Secondary Comm Format: Enter 0-F.
❑43 ❑44 ❑45 ❑46 Secondary Account Code: Valid keys are 0-F.
❑47 ❑48 ❑49 ❑50 Secondary 24-Hour Test Time.
Enter military time (i.e. 1400 for 2 PM)
.
❑51 Secondary Number Test Time Interval. Enter '0' for 24-hour; '1' - 12-hour.
❑52 ❑53 Start Monitoring Address. Valid entries are 01 through 32.
❑54 ❑55 End Monitoring Address. Valid entries are 01 through 32.
❑56 ADT-UDACT Communication Selection. Enter '0' to disable ADT-UDACT communication; '1' for zone
reporting receive only communication; '2' for zone reporting receive/transmit communication; '3' for point
reporting receive only; or '4' for point reporting receive/transmit.
❑57 Backup Reporting. Enter '0' to have secondary phone number act as backup only; '1' to have secondary
phone number receive all reports and messages along with primary phone number.
❑58 Touchtone/Rotary Select. Enter '0' for touchtone dialing; '1' for rotary dialing.
❑59 Make/Break Ratio. If rotary dialing is selected in Address 58; Enter '0' for a 67/73 make/break ratio; '1'
for a 62/38 make/break ratio.
❑60 Leave default of 0.
❑61 Leave default of 0.
❑62 AC Loss Reporting Delay. Enter '0' for no time delay after AC loss; '1' for 6 hour delay; '2' for 7 hour
delay; '3' for 8 hour delay; '4' for 9 hour delay; '5' for 10 hour delay; '6' for 11 hour delay; '7' for 15 hour
delay; '8' for 16 hour delay; '9' for 17 hour delay; 'A' for 18 hour delay; 'B' for 19 hour delay; 'C' for 20
hour delay; 'D' for 21 hour delay; 'E' for 22 hour delay; or 'F' for 23 hour delay.
❑63 Host Panel ID. Enter '7' for Unimode 2020/1010 and ADT-MNNA; '8' for Unimode 300/400; all other
entries are invalid.
❑64 ❑65 Loop Number. Factory set to '00'. Valid entries are 00 through 97
❑66 ❑67 ❑68 Device/Zone Number for General Reports. Factory set to '000'. Valid entries are 000
through 999.