SECTION 11: OPERATION AND MAINTENANCE
DANGER |
| WARNING |
| |
Electrical Shock Hazard | Explosion Hazard | Burn Hazard | Cut/Pinch Hazard | |
Disconnect electric | Turn off gas supply to | Allow heater to cool | Wear protective gear | |
heater before service. | before service. | during installation, | ||
before service. | ||||
|
| operation and service. | ||
Heater must be |
| Tubing may still be hot | ||
|
| |||
connected to a properly |
| after operation. | Edges are sharp. | |
grounded electrical |
|
|
| |
source. |
|
|
|
Failure to follow these instructions can result in death, electric shock, injury or property damage.
11.1 Sequence of Operation
The control inside the heater's control compartment is equipped with a
1.When the control is powered and there is no call for heat from external heat demand device, the LED on the control flashes slow green; LED is ON for the same period it is OFF.
2.On a call for heat from the heat demand device, the heater will go to
3.After the igniter warms up, the heater will go to the IGNITION state. Power is supplied to the gas valve operator, gas flows, ignites and the flame is proven. The LED shows two green flashes on the LED. If a flame is not sensed, the heater will RETRY, See Item 6 below for further details.
4.When the IGNITION state is completed, the heater will go to WARM UP state. The unit will fire at maximum input for 15 seconds. When the WARM UP state is completed the device will go into RUN state. The control board will monitor the heat demand device and modulate the heater input to meet the demand. The LED still shows two green flashes.
5.When the call for heat has been satisfied, the heater closes the gas valve. The blower
56 of 71
continues to run for a 45 second
6.If flame is lost at any time during heater operation, the heater will RETRY for ignition. Upon RETRY the LED shows a fast yellow flash (LED rapidly flashes). The heater will RETRY for ignition three times. After four ignition attempts, the heater will lockout for one hour or until reset. To reset the heater, remove power for 10 seconds, then
11.2 To Shut Off Heater
Set external heat demand device to lowest setting. Turn OFF electric power to heater.
Turn OFF manual gas valve in the heater supply line.
11.3 To Start Heater
Turn gas valve and electric power OFF and wait five minutes for unburned gases to vent from heater.
Turn ON main gas valve.
Turn ON electric power.
Set heat demand device to desired temperature. Burner should light automatically.
11.4Pre-Season Maintenance and Annual Inspection
To ensure your safety and years of
Turn off gas and electric supplies before performing