CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

Gas Line

Check for gas leaks. See Page 37, Section 9.

Burner Observation

Make sure it is clean and free of cracks or holes.

Window

Clean and replace as required.

 

 

 

Blower Scroll, Wheel and

Compressed air or a vacuum cleaner may be used to clean dust and dirt.

Motor

 

 

 

Burner Cup and Orifice

Clear of obstructions (even spider webs will cause problems).

 

Carefully remove any dust and debris from the burner.

 

 

Hot-Surface Igniter

Replace if cracked or broken.

 

 

Heat Demand Device:

There should be no exposed wire or damage to the device or wiring.

Thermostat, Zone Sensor,

External Pot or 0-10 Vdc or

See Page 39, Section 10.

4 - 20 mA wiring

 

 

 

Suspension Points

Make sure the heater is hanging securely.

 

Look for signs of wear on the chain or ceiling.

 

See Page 13, Figure 14.

 

 

Decorative and Protective

The grille must be securely attached.

Grille (optional)

Check that the side reflector extensions are installed correctly and secured in

 

 

place if necessary. (Decorative grille only.)

 

See Page 28, Section 7.5 and Page 30, Section 7.6

 

Make sure shield is installed correctly and secured in place if necessary.

 

(Decorative grille only.) See Page 29, Section 7.5.2.

 

 

Lower Clearance Shield

The lower shield must be securely attached.

(optional)

Inspect shield support straps and lower clearance shield anchor points.

 

 

See Page 28, Section 7.4.

 

Make sure shield is installed correctly and secured in place if necessary.

 

See Page 28, Section 7.4.

 

 

Silicone Tubing

Ensure tight, secure fit on all pressure fittings at gas valve, pressure switch,

 

pressure sensor, burner partition, and blower outlet.

 

 

Gas Valve

Verify silicone tubing has a tight secure fit on "vent" fitting.

 

Verify that plastic cap on covering pressure regulator adjustment screw is

 

secure and has not been tampered with.

 

Do not remove plastic regulator cap or attempt to adjust valve pressure

 

regulator.

 

Verify all wiring connections.

 

 

Wall Tag

If wall tag is present, make sure it is legible and accurate. Please contact

 

Roberts-Gordon LLC or your ROBERTS GORDON® independent distributor, if

 

you need a wall tag. See Page 4, Section 2.1.

 

 

Safety Labels

Product safety signs or labels should be replaced by the product user when

 

they are no longer legible. Please contact Roberts-Gordon LLC or your ROB-

 

ERTS GORDON® independent distributor to obtain replacement signs or

 

labels. See Page 2, Figure 1 through Page 3, Figure 2.

 

 