External Supplies

External Supplies

For proper communication between the washer- extractor and an external chemical supply system, it is important for the low-voltage signal power to be connected properly. The included wiring diagram (F8133502) shows several different options for safe and correct wiring of this interface.

The preferred method for connecting the wiring from the external chemical supply system to the washer- extractor is to use the 300mA power of the washer- extractor’s 24VAC control transformer, which is intended strictly for this purpose. Other voltage and current options are available, but require some wiring changes and must be provided with an external power source. Under no circumstances should the high- voltage machine supply connections or source be used for the communication wiring.

Basically, wash-cycle signals are provided to the external chemical supply equipment and a “wait for the next step” signal can be received from the supply equipment. Communication wiring connections, which include a single row of identified terminal blocks, can be found under a service panel at the upper back of the machine.

1.Use the Internal 24VAC 300 Control Transformer (Recommended by Alliance Laundry Systems)

There are 3 terminals necessary for this connection option. Terminal “24VAC COM” is used to connect 1 side of the internal control transformer to the external dispenser input signals common. The second terminal is used to connect the other side of the control transformer to the washer-extractor output signals common through a red jumper wire between “24VAC” and “RELAY COM”. Do not use the transformer terminals if an external power supply is used.

 

 

Installation

 

 

1

 

 

 

CONNECTIONS

 

 

 

EXAMPLE FOR EXTERNAL

 

 

 

DISPENSER CONNECTION

 

 

2

RELAY COM

 

 

ES 3

Supply 1

 

 

 

 

 

ES 4

External

 

 

 

Dispensing

 

 

RELAY

System

 

 

24VAC COM

 

 

COM

 

 

 

 

 

RED

 

 

 

24VAC

Internal

 

 

 

Supply

 

 

24VAC COM

300mA Max

 

 

JUMPER FOR INTERNAL

 

 

24 VAC SUPPLY

 

 

CONNECTED TO RELAY

 

 

. (REMOVE IF NOT

 

 

 

TO INTERNAL

 

 

 

SUPPLY

 

 

STEP 1: Insert screwdriver &

down

 

 

to open cage clamp.

 

 

STEP 2: Insert Wire

2

 

Wire Size 28-

 

 

0.08-1.5mm

 

8.5mm

 

 

Strip Length

 

 

 

4

 

3

 

 

 

 

 

 

CHM2336N

 

 

 

CHM2336N

1

Relay Com

 

 

2

Red Jumper Wire

 

 

3

24 VAC

 

 

4

Transformer

 

 

2.Use an External AC Power Source (Not Provided by Alliance Laundry Systems)

NOTE: Power for external supplies must not be derived from the high-voltage main power connection point.

The external power must supply power of 240VAC or less and be protected at 3 Amps or less. Remove the red jumper wire installed by the factory between “24VAC” and “RELAY COM”. Connect 1 side of the external power to the “RELAY COM” and the other to the external dispenser input signals common.

F8208301

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

53