Specifications and Dimensions

The terminal strip that furnishes the supply output signal for the chemical injection supply pumps, is located inside the control module at the rear. Access is through the rear panel of the module.

Terminals SUPPLY 1 through SUPPLY 9 and common provide 200 – 240VAC fused at 500mA. These terminals may be used to provide signals to the chemical injection system but must not be used to provide power to the pump. Do not attempt to increase fuse rating as this may cause damage to the washer- extractor’s circuitry.

An external chemical injection system requiring 200 – 240VAC can be powered through LINE 1 and LINE 2 on the external supply terminal strip on UWPVQ, PVT and PVX models. Any chemical injection system used with UWPVN and UWPVP models must be powered by a separate external power source.

Any injection system pump which requires 110VAC must be powered by a separate external power source.

CAUTION

Attempting to obtain 110VAC by using L1 or L2 with the common may damage laundry machine circuitry and/or the chemical injection system. Using a 240VAC power wire in the washer- extractor and an earth ground to obtain 110VAC could cause microprocessor problems.

SW028

Consult the chemical injection supply system instructions for operational details.