Allied Air Enterprises 4HP16LT manual Flash Codes cont, 24VAC Power Wiring

Models: 4HP16LT

1 30
Download 30 pages 11.16 Kb
Page 23
Image 23

60 seconds. The module will continue to display the previous flash code until the condition returns to normal or 24VAC is removed from the module. TRIP and ALERT LEDs flashing at the same time means control circuit voltage is too low for operation.

24VAC Power Wiring

The diagnostic module requires a constant nominal 24VAC power supply. The wiring to the module’s R and C terminals must be directly from the indoor unit or thermo- stat. The module cannot be powered by R and C terminals on the defrost board without experiencing nuisance alerts.

 

 

 

Flash Codes (cont.)

 

 

 

 

 

 

LED

Fault Description

Troubleshooting Information

 

 

Status

 

 

 

 

 

 

 

 

 

 

 

ALERT

Short Cycling

1. Thermostat demand signal is intermittent

 

 

(Yellow)

Compressor is

2. Time delay relay or control board defective

 

 

Flash

running

3. If high pressure switch present, go to Flash Code 2 info

 

 

Code 3

only briefly

4. If low pressure switch present, go to Flash Code 1 info

 

 

 

 

 

 

 

 

 

1. Run capacitor has failed

 

 

ALERT

 

2. Low line voltage (contact utility if voltage at disconnect is low)

 

 

(Yellow)

Locked Rotor

* Check wiring connections

 

 

Flash

3. Excessive liquid refrigerant in compressor

 

 

 

 

 

Code 4

 

4. Compressor bearings are seized

 

 

 

 

*Measure compressor oil level

 

 

 

 

 

 

 

 

 

1. Outdoor unit power disconnect is open

 

 

 

 

2. Compressor circuit breaker or fuse(s) is open

 

 

 

 

3. Compressor contactor has failed open

 

 

 

 

* Check compressor contactor wiring and connectors

 

 

ALERT

 

* Check for compressor contactor failure (burned, pitted, or open)

 

 

(Yellow)

Open Circuit

* Check wiring and connectors between supply and compressor

 

 

Flash

* Check for low pilot voltage at compressor contactor coil

 

 

 

 

 

Code 5

 

4. High pressure switch is open and requires manual reset

 

 

 

 

5. Open circuit in compressor supply wiring or connections

 

 

 

 

6. Unusually long compressor protector reset time due to extreme ambient temperature

 

 

 

 

7. Compressor windings are damaged

 

 

 

 

* Check compressor motor winding resistance

 

 

 

 

 

 

 

ALERT

 

1. Run capacitor has failed

 

 

Open Start Circuit

2. Open circuit in compressor start wiring or connections

 

 

(Yellow)

 

 

Current only in run

* Check wiring and connectors between supply and the compressor S terminal

 

 

Flash

 

 

circuit

3. Compressor start winding is damaged

 

 

Code 6

 

 

 

* Check compressor motor winding resistance

 

 

 

 

 

 

 

 

 

 

 

ALERT

Open Run Circuit

1. Open circuit in compressor run wiring or connections

 

 

(Yellow)

* Check wiring and connectors between supply and the compressor R terminal

 

 

Current only in start

 

 

Flash

2. Compressor run winding is damaged

 

 

circuit

 

 

Code 7

* Check compressor motor winding resistance

 

 

 

 

 

 

 

 

 

 

ALERT

Welded Contactor

 

 

 

(Yellow)

1. Compressor contactor has failed closed

 

 

Compressor always

 

 

Flash

2. Thermostat demand signal not connected to module

 

 

runs

 

 

Code 8

 

 

 

 

 

 

 

 

 

 

 

 

ALERT

Low Voltage

1. Control circuit transformer is overloaded

 

 

(Yellow)

 

 

Control circuit less

2. Low line voltage (contact utility if voltage at disconnect is low)

 

 

Flash

 

 

than 17VAC

* Check wiring conditions

 

 

Code 9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 11

Page 23

Issue 1004

506468-01

Page 23
Image 23
Allied Air Enterprises 4HP16LT manual Flash Codes cont, 24VAC Power Wiring