Allied Air Enterprises 4HP16LT manual Normal Operating Pressures

Models: 4HP16LT

1 30
Download 30 pages 11.16 Kb
Page 15
Image 15
Normal Operating Pressures

Normal Operating Pressures

Heating & Cooling

Cooling Indoor: 80 db; 67 wb

Heating (indoor): 70°F

± 2 psi

L - Liquid S- Suction

Values provided above are for HSV match pressures; different indoor unit match, and indoor load will cause pressures to vary.

Table 7

due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system. Pressures higher than those listed indicate that the system is overcharged. Pressures lower than those listed indicate that the

system is undercharged. Verify adjusted charge using the approach method.

4.Use the same digital thermometer to check liquid line temperature.