Allied Air Enterprises 4HP16LT manual Flushing Existing Line Set and Indoor Coil

Models: 4HP16LT

1 30
Download 30 pages 11.16 Kb
Page 7
Image 7
Flushing Existing Line Set and Indoor Coil

Refrigerant Line Sets: Installing Vertical Runs (new construction shown)

NOTE: Similar installation practices

Outside Wall

 

should be used if line set is to be

Wood Block

installed on exterior of outside wall.

Between Studs

 

Vapor Line Wrapped with Armaflex

Liquid Line

Outside Wall

IMPORTANT:

Refrigerant lines must not contact structure.

Caulk

IMPORTANT: Refrigerant lines must not contact wall.

Vapor Line Liquid Line

R22 refrigerant will be used to flush the system: Wire Tie

Manual background Inside Wall

Manual background Strap

Sleeve

Wire Tie

Manual background Wood Block

Manual background Wire Tie

Manual background Strap

PVC Pipe Fiberglass

Insulation

Sleeve

Figure 7

Flushing Existing Line Set and Indoor Coil

This procedure should not be performed on systems which contain contaminants, such as compressor burn out.

Manual background CAUTION

When flushing existing line set and/or indoor coil, be sure to empty all existing traps. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the thermal expansion valve, reducing system performance and capacity. Failure to properly flush system as explained in these instructions will void warranty.

Required Equipment

The following equipment is needed to flush the existing line set and indoor coil (see Figure 8 on page 8): Two clean R22 recovery bottles, an oil-less recovery machine

with a “pump down” feature, and two sets of gauges (one for use with R22 and one for use with R410A).

Flushing Procedure

IMPORTANT: The line set and/or indoor coil must be flushed with at least the same amount of refrigerant that previously charged the system. Check the charge in the flushing cylinder before flushing the unit.

1.Remove existing R22 refrigerant using the appropriate procedure.

If the existing outdoor unit is not equipped with shutoff valves, or if the unit is not operational AND the existing

R22 refrigerant will be used to flush the system:

Disconnect all power to the existing outdoor unit. Connect the existing unit, a clean recovery cylinder, and the recovery machine according to the instructions provided with the recovery machine. Remove all R22 refrigerant from the existing system. Refer to the gauges after shutdown to confirm that the entire system is completely void of refrigerant. Disconnect the liquid and suction lines from the existing outdoor unit.

506468-01

Issue 1004

Page 7

Page 7
Image 7
Allied Air Enterprises 4HP16LT manual Flushing Existing Line Set and Indoor Coil