Allied Telesis X610-24SPS/X, X610-48TS-POE+ Power Wiring to a DC AT-PWR250 Power Supply Module

Models: X610-48TS/X-POE+ X610-48TS X610-24TS/X X610-24TS/X-POE+ X610-24SPS/X X610-24TS X610-24TS-POE+ X610-48TS/X X610-48TS-POE+

1 128
Download 128 pages 35 Kb
Page 103
Image 103
Power Wiring to a DC AT-PWR250 Power Supply Module

x610 Series Layer 3 Gigabit Ethernet Switches Installation Guide

Power Wiring to a DC AT-PWR250 Power Supply Module

To power on a switch with a DC AT-PWR250 Power Supply Module, perform the following procedure:

Warning

As a safety precaution, install a circuit breaker with a minimum value of 15 Amps between the equipment and the DC power source.

E9

Warning

Always connect the wires to the LAN equipment first before you connect the wires to the circuit breaker. Do not work with HOT feeds to avoid the danger of physical injury from electrical shock. Always be sure that the circuit breaker is in the OFF position before connecting the wires to the breaker.E9

Warning

For centralized DC power connection, install only in a restricted access area. E23

Note

A tray cable is required to connect the power source if the unit is powered by centralized DC power. The tray cable must be a UL listed Type TC tray cable and rated at 600 V and 90 degrees C, with three conductors, minimum 14 AWG. E24

1.Power off the DC circuit to be used for the chassis.

2.Verify that the On/Off switch on the DC AT-PWR250 Module is in the Off position.

3.Use the legend above the terminal block to identify the terminals. The terminals are positive, power supply ground and negative, from left to right, as shown in Figure 71 on page 104.