American Dryer Corp MLG-460 manual AIR Fault Message

Models: MLG-460

1 100
Download 100 pages 5.4 Kb
Page 73
Image 73

Check that “NONE” of the thermal and magnetic overloads have “TRIPPED.”

Check circuitry; MLG-464 Main Panel Wiring Diagram

Retest

7b) To verify burner fan motor contactor (MS8) operation:

Apply a 110 VAC voltage to MS8’s terminals A1 and A2 and verify that the contactor activates.

If MS8 cycles this will indicate that its OK. Verify wiring to the device using the dryer Main Panel Wiring Diagram.

If MS8 “DOES NOT” cycle;

Check device and replace if necessary

Retest

8b) Flame Detector & Burner Chassis Ground

To test the flame detector signal refer to Section VI, Part D, Gas Burner and Ignition Systemon page 37 thru page 45.

If the flame detector test fails:

Verify that the flame detector and burner chassis connections, located on the left side if the burner, are sound and tight.

Check wiring (See dryer Main Electrical Panel Wiring Diagram and dryer Solenoid Junction Box Wiring Diagram).

Retest

9b) To test the burner controller module itself;

Refer to Section VI, Part D, Gas Burner and Ignition System on page 37 thru page 45 for wiring information, concerning the Burner Controller Module (BCM), refer to the Main Panel Wiring Diagram, the Solenoid Junction Box Wiring Diagram, and the Ladder Diagram. (Supplied with the dryer.)

5.“AIR FAULT” Message

PLC (Programmable Logic Controller) MESSAGE “AIR FAULT”

a)PROBABLE CAUSES;

1a) Incorrect Fan (Blower) Rotation.

2a) Lint Chamber Air Pressure Switch.

69

Page 73
Image 73
American Dryer Corp MLG-460 manual AIR Fault Message