American Dryer Corp MLG-460 manual General Description

Models: MLG-460

1 100
Download 100 pages 5.4 Kb
Page 64
Image 64

General Description:

The six (6) channels accept independent RTD (Resistive Temperature Device) inputs (spare channels have a 100 ohm [100 Ω] 5% tolerance resistors installed) and there is an individual set point for each channel. In operation, the scan rate between channels is four (4) to six (6) seconds, and the display will have the temperature measured by the individual RTD’s. A “red” L.E.D. indicates an alarm condition; in the event of an alarm, scanning is halted and the “ALARM” relay de-energizes until the manual reset button is depressed.

IMPORTANT: If a hi-limit alarm occurs, check that a hi-temperature has not occurred. If no, correct the condition and test.

IMPORTANT: DO NOT TROUBLESHOOT THE SHLC (Sprinkler High Limit Controller)

UNLESS THE WATER VALVE TO THE SPRINKLER IS CLOSED.

SHLC will cause:

The sprinkler water valve to open.

The entire dryer to power down.

The “SPRINKLER RESET” button on the main panel to light.

With the dryer control voltage “ON,” not executing a drying cycle, one should be able to adjust the temperature settings on any of the hi-limit controllers and cause their respective “GREEN” L.E.D.’s (light emitting diodes) to cycle “ON” and “OFF.”

If their corresponding L.E.D.’s (light emitting diodes) do not cycle, check their respective:

temperature sensors (RTD’s [Resistive Temperature Device])

power connections

electrical circuits (refer to the dryer main electrical wiring diagram)

If the previous items are “OK,” replace the hi-limit controller.

60

Page 64
Image 64
American Dryer Corp MLG-460 manual General Description, Unless the Water Valve to the Sprinkler is Closed