2.Electrical Service Specifications

MLG-460

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

exact voltage .

NOTES: A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.

Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to

B.appliance

amp draw rating and type of breaker used.

C.Circuit breakers for 3Ø dryers must be 3-pole type.

SERVICE

 

WIRE

APPROX.

MINIMUM

FUSING

CIRCUIT

PHASE

AMP DRAW

 

VOLTAGE

 

SERVICE

60 Hz

50 Hz

WIRE SIZE*

Dual Element

BREAKER

 

 

 

 

Time Delay

 

 

 

 

 

 

 

 

208

3/4

107

---

1/0

150

150

240

3

104

109

1/0

150

150

380

3/4

---

60

4

100

90

 

 

 

 

 

 

 

 

416

3/4

---

57

4

90

90

460

3/4

52

---

4

80

90

DEDICATED SPRINKLER SERVICE

Dryer

Nameplate

---

2

16

3.5

5

* AWG Stranded Wire Type...for individual lengths less than 100 feet (31 m).

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is affixed to the right side of the main electrical enclosure. In the case of 208 VAC or 240 VAC, the supply voltage must match the electric service specifications of the data label exactly.

WARNING: 208 VAC and 240 VAC ARE NOT THE SAME. Any damage done to the dryer components due to improper voltage will automatically VOID THE WARRANTY.

IMPORTANT: For proper sprinkler and dryer operation, sprinkler must be powered by a “separate or dedicated” single-phase (1ø) multi-wire branch circuit at dryer’s nameplate voltage.

NOTE: For 4-wire service, cap the neutral.

NOTE: Contact the factory for electrical information not listed.

NOTE: ADC reserves the right to make changes in specifications at any time, without notice or obligation.

23