American Dryer Corp MLG-460 manual Drum Fault Message Malfunction Probable Causes

Models: MLG-460

1 100
Download 100 pages 5.4 Kb
Page 84
Image 84

If yes, wiring is OK:

Check switch placement and door actuation.

If no, check associated:

Switch and wiring

Check wiring back to the tumbler junction box

Check wiring back to the Rear Controls

Check PLC (Programmable Logic Controller) Refer to wiring diagrams:

Tumbler Junction Box Wiring Diagram

Rear Panel Controls Wiring Diagram

Retest; verify that the signal is operational

6.”DRUM FAULT MESSAGE” Malfunction

a)PROBABLE CAUSES;

1a) Stop Motion Detector Module or Sensor.

2a) Wiring back to Main Electrical Enclosure

b)POSSIBLE SOLUTIONS;

Open the Main Electrical Enclosure locate input #0, 10 on the PLC (Programmable Logic Controller). With control voltage “ON” (“GREEN” Push-Button), use the pendant to rotate the tumbler. Notice a L.E.D. (light emitting diode) on as the tumbler (basket) is rotating.

If the L.E.D. is off, refer to paragraph 6 (section a) above.

1b) If the L.E.D. (light emitting diode) is off:

Check Fuse #2; replace if necessary.

Rotate the tumbler using the pendant control, and adjust the stop.

Does the module’s L.E.D. (light emitting diode) respond?

If yes, adjust the “Time Adjust” until the LED is on during rotation 12 to 15 seconds after.

If no, check:

Inductive Proximity Sensor for Damage

80