Electrical Installation: Relay Board (Optional)

Relay

Name

Events that will trigger the alarm

Mode

Comment

ID

 

 

 

 

 

 

 

 

 

K11

Bypass operation

• UPS is running in normal operation/

Active on

Opr. mode

 

 

bypass operation according to AS400/

 

 

 

 

Novell.

 

 

 

 

 

 

 

K12

Maintenance bypass ON

• The maintenance bypass switch is active.

Active on

Opr. mode

 

 

 

 

 

K13

Stand-by operation

• UPS is in stand-by operation.

Active on

Opr. mode

 

 

 

 

 

K14

Boost charge operation

• UPS is boost charging the batteries.

Active on

Opr. mode

 

 

 

 

 

K15

Fan fault

• Blocked or faulty fan.

Fail safe

Fault

 

 

 

 

 

K16

High equipment

• Static Switch temperature is high;

Fail safe

Warning

 

temperature or inverter

• Main Inverter failure (high temperature

 

 

 

fuse blown

or blown fuse);

 

 

 

 

• Delta Inverter temperature is high;

 

 

 

 

• Magnetics temperature is high;

 

 

 

 

• Isolation Transformer temperature is high

 

 

 

 

(optional);

 

 

 

 

• Battery temperature is high.

 

 

 

 

 

 

 

IN1

Generator active

• System on generator

 

System is

 

 

 

 

running on

 

 

 

 

generator.

 

 

 

 

Battery

 

 

 

 

charging is

 

 

 

 

derated.

 

 

 

 

 

IN2

Battery room ventilation

• Battery room ventilation

 

Ventilation

 

fault

 

 

fault in

 

 

 

 

battery

 

 

 

 

room.

 

 

 

 

Battery

 

 

 

 

charging is

 

 

 

 

off.

 

 

 

 

 

IN3 -

Reserved for future use

 

 

 

IN8

 

 

 

 

 

 

 

 

 

Symmetra MW 1000 kW 480 V Installation - 990-4112E

25