Required Breaker Settings
The Symmetra® MW is a
See separate guide on parallel operation for information on required breaker settings in parallel systems.
See also
Input and upstream breakers — minimum settings
Q1, Q5, and any upstream breaker
Duration [S] | Current [A] | Total load [%] | Event/Operation |
|
|
|
|
< 0.005 | 18 kA | Internal fault clearing | |
|
|
|
|
∞ | 1880* | 130 | Overload |
|
|
|
|
∞ | 1245 | 100 | |
|
|
|
|
∞ | 1370 | 110 | |
|
|
| Charge |
|
|
|
|
| * Only applicable to Q1 |
|
Output and downstream breakers — minimum settings
Q2, Q4, Q6, and any downstream breaker
Duration [S] | Current [A] | Total load [%] | Event/Operation |
|
|
|
|
< 0.005 | 18 kA | Internal fault clearing. | |
|
|
|
|
60 | 2406* | 200 | Overload |
|
|
|
|
600 | 1504* | 125 | Overload |
|
|
|
|
∞ | 1203 | 100 | |
|
|
|
|
* Only applicable to Q2 and Q4
Symmetra MW 1000 kW 480 V Installation - | 35 |