Required Breaker Settings

The Symmetra® MW is a fault-tolerant system capable of handling and surviving overloads and internal/external faults. The overload performances and fault clearings are possible when the system meets specified minimum requirements for breaker settings. The settings are specified in the tables below, but some of them can also be found in the Electrical Specification section. The settings are all minimum settings and may not result in a drop-out.

See separate guide on parallel operation for information on required breaker settings in parallel systems.

See also

Input and upstream breakers — minimum settings

Q1, Q5, and any upstream breaker

Duration [S]

Current [A]

Total load [%]

Event/Operation

 

 

 

 

< 0.005

18 kA

--

Internal fault clearing

 

 

 

 

1880*

130

Overload on-line

 

 

 

 

1245

100

On-line

 

 

 

 

1370

110

On-line + Max. Battery

 

 

 

Charge

 

 

 

 

 

* Only applicable to Q1

 

Output and downstream breakers — minimum settings

Q2, Q4, Q6, and any downstream breaker

Duration [S]

Current [A]

Total load [%]

Event/Operation

 

 

 

 

< 0.005

18 kA

--

Internal fault clearing.

 

 

 

 

60

2406*

200

Overload on-line

 

 

 

 

600

1504*

125

Overload on-line

 

 

 

 

1203

100

On-line

 

 

 

 

* Only applicable to Q2 and Q4

Symmetra MW 1000 kW 480 V Installation - 990-4112E

35

Page 39